CHINT NXB63 Miniature Circuit Breaker MCB
Protection of circuits against short-circuit currents, protection of circuits against overload currents, switch, isolation, NXB63 circuit-breakers are used in domestic installation, as well as in commercial and industry electrical distribution systems.
DESCRIPTION
- Rated current from : 6A to 63A
- Icu 6kA
- Rated Voltage Ue (V) : 230/400 ~ 240/415
- Standard: IEC/EN 60898
- Rate Frequency : 50/60Hz
Compare
-
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Miniature circuit-breaker, Acti9 iC60H, 1P, 6 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84106
Schneider Circuit Breakers, SCHNEIDER SECTIONSMiniature circuit-breaker, Acti9 iC60H, 1P, 6 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84106
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Hpoles description 1Pnumber of protected poles 1[In] rated current 6 Anetwork type AC
DCtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
15 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
42 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
30 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at 60…72 V DC conforming to EN/IEC 60947-2
20 kA Icu at 12…60 V DC conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards EN 60898-1
IEC 60947-2
IEC 60898-1
EN 60947-2Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 21 kA 50 % conforming to EN 60947-2 – 12…60 V AC 50/60 Hz
7.5 kA 50 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
21 kA 50 % conforming to IEC 60947-2 – 12…60 V AC 50/60 Hz
7.5 kA 50 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7500 A 75 % conforming to EN 60898-1 – 230 V AC 50/60 Hz
7500 A 75 % conforming to IEC 60898-1 – 230 V AC 50/60 Hz
15 kA 50 % conforming to IEC 60947-2 – 100…133 V AC 50/60 Hz
15 kA 50 % conforming to EN 60947-2 – 100…133 V AC 50/60 Hz
15 kA 100 % conforming to EN 60947-2 – 72 V DC
15 kA 100 % conforming to IEC 60947-2 – 72 V DC
20 kA 100 % conforming to EN 60947-2 – 12…60 V DC
20 kA 100 % conforming to IEC 60947-2 – 12…60 V DClimitation class 3 conforming to EN 60898-1
3 conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 2height 85 mmwidth 18 mmdepth 78.5 mmnet weight 0.215 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection WithoutSKU: n/a -
LIGHT SWITCHES & ELECTRICAL SOCKETS
32A 1 Gang Full-Flat Double Rocker Switch with Neon, Sliver Bronze E8431D32_SZ
LIGHT SWITCHES & ELECTRICAL SOCKETS32A 1 Gang Full-Flat Double Rocker Switch with Neon, Sliver Bronze E8431D32_SZ
Main range ZENceloproduct or component type Switchload type Resistivecolour tint Silver bronzecover frame colour tint Silver bronzeComplementary device mounting Surface
Flushrated current 32 A at 250 V AC 50/60 Hzlocal signalling Indicator light, neon (amber)number of gangs 1 gangmaterial Polycarbonate + GF 20 %: grid plate
Polycarbonate: base
Polycarbonate: cover
Polycarbonate: surroundconnections – terminals Brass rod terminalsembedding depth 22 mmwidth 87 mmheight 87 mmdepth 30.2 mmSKU: n/a -
ELECTRICAL INDUSTRIAL, Electro, TRANSFORMER
ABB Transformer 500KVA 33/400KV
Distribution transformers are typically oil-immersed and suitable for pole-, pad- or ground-mounting. They represent an economical option for certain networks, particularly those with low population densities.
Depending upon requirements, transformers may be connected between two phases of a three-phase system (two high voltage bushings) or from one phase to ground (single high voltage bushing).
The units are suitable for residential overhead distribution loads, as well as light commercial or industrial loads and diversified power applications.
Product scope
- Primary voltage: up to 36 kV
- Typical fluid: mineral oil
SKU: n/a