Manufactured to BS 6004:2012 Table 3
Annealed Stranded Copper Conductor / PVC Insulated / PVC Sheathed. 300/500V
Designed for use in light industrial and domestic wiring. These cables are particularly suited for installation as meter tails and are intended for fixed installation in dry or damp premises.
These cables can be installed in conduit, in cable trunking and in cable ducting. Or where there is deemed little risk of mechanical damage these cables can be clipped direct, on cable tray, embedded or in free air. These cables are not intended to be laid underground.
Product Details
 | Harmonisation Code | Nominal Cross Sectional Area of Conductor (mm2) | Nominal Stranding of Conductor (mm) | Nominal Radial Thickness of insulation (mm) | Nominal Radial Thickness of sheath (mm) | Overall Diameter Lower Limit (mm) | Overall Diameter Upper Limit (mm) | Approximate Weight(kg/km) |
National Type | 1.0 | 1 / 1.13 | 0.6 | 0.8 | 3.8 | 4.5 | 26 | |
National Type | 1.5 | 1 / 1.38 | 0.7 | 0.8 | 4.2 | 4.9 | 35 | |
National Type | 2.5 | 1 / 1.78 | 0.8 | 0.8 | 4.8 | 5.8 | 55 | |
National Type | 4.0 | 7 / 0.85 | 0.8 | 0.9 | 5.4 | 6.8 | 75 | |
National Type | 6.0 | 7 / 1.04 | 0.8 | 0.9 | 6.0 | 7.4 | 95 | |
National Type | 10.0 | 7 / 1.35 | 1.0 | 0.9 | 7.2 | 8.8 | 155 | |
National Type | 16.0 | 7 / 1.70 | 1.0 | 1.0 | 8.4 | 10.5 | 225 | |
National Type | 25.0 | 7 / 2.14 | 1.2 | 1.1 | 10.0 | 12.5 | 340 | |
National Type | 35.0 | 7 / 2.52 | 1.2 | 1.1 | 11.0 | 13.5 | 445 |
₦455,000.00
Compare-
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Miniature circuit-breaker, Acti9 iC60H, 2P, 10 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84210
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSMiniature circuit-breaker, Acti9 iC60H, 2P, 10 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84210
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Hpoles description 2Pnumber of protected poles 2[In] rated current 10Â Anetwork type AC
DCtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000Â A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
42Â kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
10Â kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
15Â kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
30Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
15Â kA Icu at <= 125 V DC conforming to EN/IEC 60947-2
42Â kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards EN 60898-1
IEC 60947-2
IEC 60898-1
EN 60947-2Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 15Â kA 50Â % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
7.5Â kA 50Â % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz
5Â kA 50Â % conforming to EN 60947-2 – 440 V AC 50/60 Hz
15Â kA 50Â % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5Â kA 50Â % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz
5Â kA 50Â % conforming to IEC 60947-2 – 440 V AC 50/60 Hz
7500Â A 75Â % conforming to EN 60898-1 – 400 V AC 50/60 Hz
7500Â A 75Â % conforming to IEC 60898-1 – 400 V AC 50/60 Hz
21Â kA 50Â % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz
21Â kA 50Â % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz
15Â kA 100Â % conforming to IEC 60947-2 – 72…125 V DC
15Â kA 100Â % conforming to EN 60947-2 – 72…125 V DClimitation class 3 conforming to EN 60898-1
3 conforming to IEC 60898-1[Ui] rated insulation voltage 500Â V AC 50/60 Hz conforming to EN 60947-2
500Â V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6Â kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 4height 85 mmwidth 36 mmdepth 78.5 mmnet weight 0.25 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
Electro, LED LIGHTS, LIGHTING
PHILIPS Essential SmartBright LED Downlight G2 11W Philip
Essential SmartBright G2 LED Downlight is value for money product with high efficacy, good quality and reliability. It offers multiple configurations from 300lm to 2000lm output, to replace conventional downlight. It can be used for shopping mall, retail store, residential and office. It’s an ideal product family to distribute in trade market.
Benefits
- Â Reliability and safety: meets national and international regulation
- Diversity: One stop shopping with multiple choices of recess round, square as well as surface-mount to fit your dedicated applications
- Energy saving: High system efficacy with lower power consumption
- Easy to install with slim design
SKU: n/a -
Schneider "Consort Dado" Trunking, SCHNEIDER SECTIONS
Mita – Consort Dado – external corner – 100 x 50 mm CTO105W
Schneider "Consort Dado" Trunking, SCHNEIDER SECTIONSMita – Consort Dado – external corner – 100 x 50 mm CTO105W
Main range of product Mitaproduct name Consort Dadoproduct or component type External cornercolour tint Whitequantity per set Set of 1Complementary fixing mode Clip-onmaterial with surface finish UPVC (unplasticized polyvinyl chloride)SKU: n/a -
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Easy9 miniature circuit breaker- 2P – 32 A – C curve – 6000 A – 230 V EZ9F56232
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSEasy9 miniature circuit breaker- 2P – 32 A – C curve – 6000 A – 230 V EZ9F56232
Main range Easy9device application Distributionproduct or component type Miniature circuit-breakerdevice short name Easy9 MCBPoles 2Pnumber of protected poles 2[In] rated current 32Â Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000Â A Icn at 220 V AC 50/60 Hz conforming to IEC 60898-1
6000Â A Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1suitability for isolation Yes conforming to IEC 60898-1Complementary network frequency 50/60 Hz[Ue] rated operational voltage 220 V AC 50/60 Hz
400 V AC 50/60 Hzmagnetic tripping limit 5…10 x In[Ics] rated service breaking capacity 6 kA 100 % x Icn at 230 V AC 50/60 Hz conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to IEC 60898-1[Uimp] rated impulse withstand voltage 4 kV conforming to IEC 60898-1contact position indicator Yescontrol type Togglelocal signalling Withoutmounting mode Clip-onmounting support DIN rail9 mm pitches 4height 81 mmwidth 36 mmdepth 66.5 mmcolour Grey (RAL 7035)mechanical durability 10000 cycleselectrical durability 4000 cyclesconnections – terminals Tunnel type terminal (top or bottom) 1…25 mm² flexible
Tunnel type terminal (top or bottom) 1…35 mm² rigidtightening torque 3.5 N.m top or bottomearth-leakage protection WithoutSKU: n/a -