Easy9 miniature circuit breaker- 2P – 10 A – C curve – 6000 A – 230 V EZ9F56210
range |
Easy9
|
|
---|---|---|
device application |
Distribution
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
Easy9 MCB
|
|
Poles |
2P
|
|
number of protected poles |
2
|
|
[In] rated current |
10 A
|
|
network type |
AC
|
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
10000 A Icn at 220 V AC 50/60 Hz conforming to IEC 60898-1
6000 A Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1 |
|
suitability for isolation |
Yes conforming to IEC 60898-1
|
network frequency |
50/60 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
220 V AC 50/60 Hz
400 V AC 50/60 Hz |
|
magnetic tripping limit |
5…10 x In
|
|
[Ics] rated service breaking capacity |
6 kA 100 % x Icn at 230 V AC 50/60 Hz conforming to IEC 60898-1
|
|
[Ui] rated insulation voltage |
500 V AC 50/60 Hz conforming to IEC 60898-1
|
|
[Uimp] rated impulse withstand voltage |
4 kV conforming to IEC 60898-1
|
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Without
|
|
mounting mode |
Clip-on
|
|
mounting support |
DIN rail
|
|
9 mm pitches |
4
|
|
height |
81 mm
|
|
width |
36 mm
|
|
depth |
66.5 mm
|
|
colour |
Grey (RAL 7035)
|
|
mechanical durability |
10000 cycles
|
|
electrical durability |
4000 cycles
|
|
connections – terminals |
Tunnel type terminal (top or bottom) 1…25 mm² rigid
Tunnel type terminal (top or bottom) 1…16 mm² flexible |
|
tightening torque |
2 N.m top or bottom
|
|
earth-leakage protection |
Without
|
₦2,400.00
Compare-
ELECTRICAL FITTINGS, Electro, HOME&OFFICE LIGHTING, LED LIGHTS, LIGHTING, OUTDOOR FITTINGS, OUTDOOR LIGHTS, SOLAR POWERED
LED Win Win 50w Solar Flood Light with Panel
ELECTRICAL FITTINGS, Electro, HOME&OFFICE LIGHTING, LED LIGHTS, LIGHTING, OUTDOOR FITTINGS, OUTDOOR LIGHTS, SOLAR POWEREDLED Win Win 50w Solar Flood Light with Panel
Remote control
Auto mode
3 hours
6 hours
12 hours
Item : WW-SY-SFL-50W815
Power : 50W
Solar Power: 8W
Battery: 15A
Charging time : 5H
Lighting time : 13H
Lumen: 564LM
Beam Angel : 120 Degree
Dimension: 277*225*75
SKU: n/a -
Electro, SOCKETS & SWITCHES, SWITCHES
BG 2GANG DIMMER SWITCH – FBS82
200W Rated (100W LED)
Easy to install supplied with fixing screws and installation instructions
Adjust your light level for mood setting as well as energy saving with 2 way on/off
Trailing (lagging) edge dimmer suitable for dimming LED, dimmable CFL’s and traditional lighting
Intelligent electronic circuit monitors the connected load and provides a soft-start with protection against thermal, current and voltage overload
Suitable for use with good quality electronic or wire wound transformers. Can also be used with good quality mains voltage halogen lamps incorporating GU10 bases
2 way switching allows for a second switch position in a circuit
Screwless front plate clips on and off easily and has a sleek flat profile
Moisture control gasket prevents tarnishing from new plaster
SKU: n/a -
LIGHT SWITCHES & ELECTRICAL SOCKETS
10A 250V 2 Gang Bell Press Switch KB32BP
Main range Vivaceproduct or component type Switchdevice short name KB32device presentation Complete mechanismComplementary switch function 1-wayactuator Push-buttonnumber of gangs 2 gangscolour tint Whitematerial Polycarbonate: grid plate
Polycarbonate: surround
Nylon: baseprojecting depth 8 mmdevice mounting Flushmounting support Wall mountedfixing mode By screw M3.5fixing center 60.3 mmembedding depth 35 mmrated current 10 A at 250 V AC, inductive[Ue] rated operational voltage 250 V ACnetwork frequency 50 Hzcontacts material Brass and phosphor bronzeconnections – terminals pillar terminalterminal identifier COM
L2tightening torque 0.4 N.mclamping connection capacity <= 1.5 mm²width 86 mmheight 86 mmSKU: n/a -
Schneider Mureva Floodlight, SCHNEIDER SECTIONS
Mureva lights, Floodlight 50W 6500K, IP65 230V IMT47213
Schneider Mureva Floodlight, SCHNEIDER SECTIONSMureva lights, Floodlight 50W 6500K, IP65 230V IMT47213
Main range Murevarange of product Mureva lightsproduct name Floodlightproduct or component type Lampdevice application Ware-houses and parking garages
Residential
Media device support
Public areas
Secure lighting
Stadiums and arenasComplementary type of installation OutdoorTotal system power 50 Wlight source LED[Ue] rated operational voltage 230 V ACpower factor 0.9colour rendering index Ra=80luminous flux 5000 lmbulb lifespan 50000 hcolour temperature 6500 Kcolour Blackbeam angle 110 °shape Rectangularheight 215.4 mmwidth 161.4 mmdepth 31.0 mmnet weight 1.02 kgSKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Miniature circuit-breaker, Acti9 iC60H, 1P, 6 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84106
Schneider Circuit Breakers, SCHNEIDER SECTIONSMiniature circuit-breaker, Acti9 iC60H, 1P, 6 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84106
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Hpoles description 1Pnumber of protected poles 1[In] rated current 6 Anetwork type AC
DCtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
15 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
42 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
30 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at 60…72 V DC conforming to EN/IEC 60947-2
20 kA Icu at 12…60 V DC conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards EN 60898-1
IEC 60947-2
IEC 60898-1
EN 60947-2Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 21 kA 50 % conforming to EN 60947-2 – 12…60 V AC 50/60 Hz
7.5 kA 50 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
21 kA 50 % conforming to IEC 60947-2 – 12…60 V AC 50/60 Hz
7.5 kA 50 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7500 A 75 % conforming to EN 60898-1 – 230 V AC 50/60 Hz
7500 A 75 % conforming to IEC 60898-1 – 230 V AC 50/60 Hz
15 kA 50 % conforming to IEC 60947-2 – 100…133 V AC 50/60 Hz
15 kA 50 % conforming to EN 60947-2 – 100…133 V AC 50/60 Hz
15 kA 100 % conforming to EN 60947-2 – 72 V DC
15 kA 100 % conforming to IEC 60947-2 – 72 V DC
20 kA 100 % conforming to EN 60947-2 – 12…60 V DC
20 kA 100 % conforming to IEC 60947-2 – 12…60 V DClimitation class 3 conforming to EN 60898-1
3 conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 2height 85 mmwidth 18 mmdepth 78.5 mmnet weight 0.215 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection WithoutSKU: n/a
There are no reviews yet.