Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Easy9 miniature circuit breaker- 2P – 20 A – C curve – 6000 A – 230 V EZ9F56220
range |
Easy9
|
|
---|---|---|
device application |
Distribution
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
Easy9 MCB
|
|
Poles |
2P
|
|
number of protected poles |
2
|
|
[In] rated current |
20 A
|
|
network type |
AC
|
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
10000 A Icn at 220 V AC 50/60 Hz conforming to IEC 60898-1
6000 A Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1 |
|
suitability for isolation |
Yes conforming to IEC 60898-1
|
network frequency |
50/60 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
220 V AC 50/60 Hz
400 V AC 50/60 Hz |
|
magnetic tripping limit |
5…10 x In
|
|
[Ics] rated service breaking capacity |
6 kA 100 % x Icn at 230 V AC 50/60 Hz conforming to IEC 60898-1
|
|
[Ui] rated insulation voltage |
500 V AC 50/60 Hz conforming to IEC 60898-1
|
|
[Uimp] rated impulse withstand voltage |
4 kV conforming to IEC 60898-1
|
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Without
|
|
mounting mode |
Clip-on
|
|
mounting support |
DIN rail
|
|
9 mm pitches |
4
|
|
height |
81 mm
|
|
width |
36 mm
|
|
depth |
66.5 mm
|
|
colour |
Grey (RAL 7035)
|
|
mechanical durability |
10000 cycles
|
|
electrical durability |
4000 cycles
|
|
connections – terminals |
Tunnel type terminal (top or bottom) 1…25 mm² rigid
Tunnel type terminal (top or bottom) 1…16 mm² flexible |
|
tightening torque |
2 N.m top or bottom
|
|
earth-leakage protection |
Without
|
₦7,600.00
Compare-
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 2P 3A C Miniature Circuit breaker A9F44203
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 2P 3A C Miniature Circuit breaker A9F44203
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 2Pnumber of protected poles 2[In] rated current 3 Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 50 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
50 kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
50 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
25 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
6 kA Icu at 100…133 V DC conforming to EN/IEC 60947-2
6000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 440 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 50 kA 100 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
50 kA 100 % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz
50 kA 100 % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz
25 kA 100 % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz
6000 A 100 % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz
6 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 4height 85 mmwidth 36 mmdepth 78.5 mmnet weight 0.25 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockEnvironment standards EN/IEC 60947-2
EN/IEC 60898-1IP degree of protection IP20 conforming to IEC 60529pollution degree 3 conforming to EN/IEC 60947-2tropicalisation 2 conforming to IEC 60068-1relative humidity 95 % at 55 °Cambient air temperature for operation -35…70 °Cambient air temperature for storage -40…85 °CSKU: n/a -
Electro, SOCKETS & SWITCHES, SWITCHES
BG BRASS GEORGIAN LIGHT SWITCH PLATE – SINGLE 1 GANG 2 WAY
BG NBG12 Brass Georgian Light Switch Plate – Single 1 Gang 2 WayAT A GLANCE…- Top quality Brass finish – lightly lacquered to prevent finger marks
- Matching Brass rocker switch
- No visible plastic around switches
- Specification: 1 gang, 2 way, 10 amp (10AX)
- Requires a 16mm metal wall box
- Supplied with colour coded fixing screws
SKU: g7 -
Electro, SCHNEIDER SECTIONS, Schneider Thorsman Testmeters
Thorsman Compact Digital Multimeter Cat III IMT23112
Electro, SCHNEIDER SECTIONS, Schneider Thorsman TestmetersThorsman Compact Digital Multimeter Cat III IMT23112
Main range Thorsmanproduct or component type Digital multimetersupply battery 12 VComplementary type of setting Manualsignaling function Low battery by visualfunction available Handsfree operationsprotection type Fusetype of measurement Current DC: 200 mA
Voltage AC/DC: 2/20/200/300 V
Resistance: 2/20/200 kOhm/2 MOhmmeasurement category Category III 300 Vlanguage Danish
Swedish
Norwegian
English
Finnishheight 120 mmwidth 75 mmdepth 18 mmnet weight 110 g with batterySKU: n/a -
Electro, SOCKETS, SOCKETS & SWITCHES
FBN60- TELEVISION SOCKET
BG Electrical are confident in the quality of our workmanship and materials, the guarantee stated applies from the date of delivery.
Screw terminals
Easy to install supplied with fixing screws and installation instructions
Used for TV or FM coaxial aerial connection
Screwless front plate clips on and off easily and has a sleek flat profile
Moisture control gasket prevents tarnishing from new plaster
Minimum mounting box depth 25mm
SKU: n/a -
CIRCUIT BREAKERS
Circuit breaker Easypact EZC250N – TMD – 200 A – 3 poles 3d
Main range of product EasyPactproduct or component type Circuit breakerdevice short name Easypact EZC250Ncircuit breaker name Easypact EZC250Ndevice application Distributionpoles description 3Pprotected poles description 3tnetwork type DC
ACnetwork frequency 50/60 Hz[In] rated current 250 A at 40 °C[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2[Ue] rated operational voltage 550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2breaking capacity code Nbreaking capacity 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
20 kA Icu at 125 V DC 1P conforming to IEC 60947-2
20 kA Icu at 250 V DC 2P conforming to IEC 60947-2
25 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 400…415 V AC 50/60 Hz conforming to IEC 60947-2
8 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2[Ics] rated service breaking capacity 10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
25 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2
10 kA at 125 V DC conforming to IEC 60947-2
10 kA at 250 V DC conforming to IEC 60947-2
25 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2
4 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2suitability for isolation Yes conforming to IEC 60947-2utilisation category Category Atrip unit name TM-Dtrip unit technology Thermal-magnetictrip unit rating 200 A at 50 °Cprotection type Overload protection
Short-circuit protectionpollution degree 3 conforming to IEC 60664-1
3 conforming to IEC 947-1Complementary control type Togglemounting mode Fixedmounting support Backplateupside connection Frontdownside connection Frontmechanical durability 10000 cycleselectrical durability Category A: 5000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2connection pitch 35 mmlocal signalling Positive contact indicationneutral protection setting Without protectionearth-leakage protection Withoutheight 165 mmwidth 105 mmdepth 60 mmSKU: n/a