Easy9 miniature circuit breaker- 3P – 16 A – C curve – 6000 A – 400 V EZ9F56316
range |
Easy9
|
|
---|---|---|
device application |
Distribution
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
Easy9 MCB
|
|
Poles |
3P
|
|
number of protected poles |
3
|
|
[In] rated current |
16Â A
|
|
network type |
AC
|
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
10000Â A Icn at 220 V AC 50/60 Hz conforming to IEC 60898-1
6000Â A Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1 |
|
suitability for isolation |
Yes conforming to IEC 60898-1
|
network frequency |
50 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
220 V AC 50/60 Hz
400 V AC 50/60 Hz |
|
magnetic tripping limit |
5…10 x In
|
|
[Ics] rated service breaking capacity |
6Â kA 100Â % x Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1
|
|
[Ui] rated insulation voltage |
500Â V AC 50/60 Hz conforming to IEC 60898-1
|
|
[Uimp] rated impulse withstand voltage |
4Â kV conforming to IEC 60898-1
|
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Without
|
|
mounting mode |
Clip-on
|
|
mounting support |
DIN rail
|
|
9 mm pitches |
6
|
|
height |
81Â mm
|
|
width |
54Â mm
|
|
depth |
66.5Â mm
|
|
colour |
Grey (RAL 7035)
|
|
mechanical durability |
10000Â cycles
|
|
electrical durability |
4000Â cycles
|
|
connections – terminals |
Tunnel type terminal (top or bottom) 1…25 mm² rigid
Tunnel type terminal (top or bottom) 1…16 mm² flexible |
|
tightening torque |
2Â N.m top or bottom
|
₦10,800.00
Compare-
CHINT
CHINT NXB63 Miniature Circuit Breaker 2pole
Overload protection, short circuit protection and isolation. It is widely used in building power distribution, industrial power distribution, as well as control and protection for a variety of equipment with operating current not exceeding 125A.
DESCRIPTION
- Compliance standard : IEC60898-1
- Rated Current : 6~63A Rated Voltage (V~) : 240/415
- Rated Frequency : 50/60 Hz
SKU: n/a -
COMPUTING, PRINTERS
HP LASERJET ENTERPRISE M528DN MULTI-FUNCTION PRINTER
- Print, copy, scan
- Print speed letter: Up to 45 ppm (black)
- Auto duplex printing; 2 paper trays (standard); Uses toner with JetIntelligence
- FCC Class A emissions – for use in commercial environments, not residential environments
SKU: n/a -
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
IC60H – miniature circuit breaker – 1P – 20A – C curve A9F84120
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSIC60H – miniature circuit breaker – 1P – 20A – C curve A9F84120
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Hpoles description 1Pnumber of protected poles 1[In] rated current 20Â Anetwork type AC
DCtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000Â A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
15Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
42Â kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
30Â kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
15Â kA Icu at 60…72 V DC conforming to EN/IEC 60947-2
20Â kA Icu at 12…60 V DC conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards IEC 60898-1
IEC 60947-2
EN 60898-1
EN 60947-2Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 21Â kA 50Â % conforming to EN 60947-2 – 12…60 V AC 50/60 Hz
7.5Â kA 50Â % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
21Â kA 50Â % conforming to IEC 60947-2 – 12…60 V AC 50/60 Hz
7.5Â kA 50Â % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7500Â A 75Â % conforming to EN 60898-1 – 230 V AC 50/60 Hz
7500Â A 75Â % conforming to IEC 60898-1 – 230 V AC 50/60 Hz
15Â kA 50Â % conforming to IEC 60947-2 – 100…133 V AC 50/60 Hz
15Â kA 50Â % conforming to EN 60947-2 – 100…133 V AC 50/60 Hz
15Â kA 100Â % conforming to EN 60947-2 – 72 V DC
15Â kA 100Â % conforming to IEC 60947-2 – 72 V DC
20Â kA 100Â % conforming to EN 60947-2 – 12…60 V DC
20Â kA 100Â % conforming to IEC 60947-2 – 12…60 V DClimitation class 3 conforming to EN 60898-1
3 conforming to IEC 60898-1[Ui] rated insulation voltage 500Â V AC 50/60 Hz conforming to EN 60947-2
500Â V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6Â kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 2height 85 mmwidth 18 mmdepth 78.5 mmnet weight 0.215 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection WithoutSKU: n/a -
Electro, LED LIGHTS, LIGHTING, OUTDOOR LIGHTS
PHILIPS Smartbright Bulkhead 15W 1400 Lumen WL008C Philip
Electro, LED LIGHTS, LIGHTING, OUTDOOR LIGHTSPHILIPS Smartbright Bulkhead 15W 1400 Lumen WL008C Philip
Smartbright Bulkhead
Benefits
• Bright and energy efficient
• Optional knock-out, large terminal
• IP65 rated suitable for outdoor useModel   –        SmartBright Bulkhead (WL008C)
Type                  –    LED10
Equivalent of          –    1x26W CFLi
Power                –    15W
System lumen          –    1400lm
Type                  –    Fixed output (PSU)
Diffuser               –    Frosted diffuser
Power factor            –   ≥0.9
Beam Angle            –    110°
Operating Temperature   –    25ËšC (-20ËšC < ta < 40ËšC)
Lifetime (L70B50)*Â Â Â Â Â Â Â –Â Â Â 30,000 hours
IP/ IK rating            –   IP65/ IK06
Electrical Class           –   Class II
Input Voltage             –   220V-240V, 50/60Hz
Mounting Type            –   Surface mount
Housing colour           –   White
Accessory               –    Silver trim (in the box)Material
Frosted cover: Polycarbonate
Housing: Polycarbonate
Trim: ABSApplication Residential, back of house areas, walk-ways
SKU: n/a -
Electro, Schneider "Consort Dado" Trunking, SCHNEIDER SECTIONS
Mita – Cableline 50 – external corner – 180W x 52 mm DPX3W
Electro, Schneider "Consort Dado" Trunking, SCHNEIDER SECTIONSMita – Cableline 50 – external corner – 180W x 52 mm DPX3W
Main range of product Mitaproduct name Cableline 50product or component type External cornercolour tint Whitequantity per set Set of 1Complementary fixing mode By screws extra securitymaterial with surface finish UPVC (unplasticized polyvinyl chloride)Environment ambient air temperature for operation -5…60 °CPacking Units Unit Type of Package 1 PCENumber of Units in Package 1 1Package 1 Weight 187 gPackage 1 Height 7.8 cmPackage 1 width 12.8 cmPackage 1 Length 15.2 cmSKU: n/a -
Electro, Low Voltage Products and Systems, SCHNEIDER SECTIONS
EZC250N3200 Circuit breaker Easypact EZC250N – TMD – 200 A – 3 poles 3d
Electro, Low Voltage Products and Systems, SCHNEIDER SECTIONSEZC250N3200 Circuit breaker Easypact EZC250N – TMD – 200 A – 3 poles 3d
Main range of product EasyPactproduct or component type Circuit breakerdevice short name Easypact EZC250Ncircuit breaker name Easypact EZC250Ndevice application Distributionpoles description 3Pprotected poles description 3tnetwork type DC
ACnetwork frequency 50/60 Hz[In] rated current 250 A at 40 °C[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2[Ue] rated operational voltage 550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2breaking capacity code Nbreaking capacity 20Â kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
50Â kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
50Â kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
20Â kA Icu at 125 V DC 1P conforming to IEC 60947-2
20Â kA Icu at 250 V DC 2P conforming to IEC 60947-2
25Â kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2
25Â kA Icu at 400…415 V AC 50/60 Hz conforming to IEC 60947-2
8Â kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2[Ics] rated service breaking capacity 10Â kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
25Â kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2
10Â kA at 125 V DC conforming to IEC 60947-2
10Â kA at 250 V DC conforming to IEC 60947-2
25Â kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2
4Â kA at 550 V AC 50/60 Hz conforming to IEC 60947-2
12.5Â kA at 380 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2suitability for isolation Yes conforming to IEC 60947-2utilisation category Category Atrip unit name TM-Dtrip unit technology Thermal-magnetictrip unit rating 200 A at 50 °Cprotection type Overload protection
Short-circuit protectionpollution degree 3 conforming to IEC 60664-1
3 conforming to IEC 947-1Complementary control type Togglemounting mode Fixedmounting support Backplateupside connection Frontdownside connection Frontmechanical durability 10000Â cycleselectrical durability Category A: 5000Â cycles 415 V AC 50/60 Hz conforming to IEC 60947-2connection pitch 35Â mmlocal signalling Positive contact indicationneutral protection setting Without protectionearth-leakage protection Withoutheight 165Â mmwidth 105Â mmdepth 60Â mmSKU: n/a
There are no reviews yet.