Schneider Circuit Breakers, SCHNEIDER SECTIONS
Easy9 miniature circuit breaker- 4P – 20 A – C curve – 6000 A – 400 V EZ9F56420
range |
Easy9
|
|
---|---|---|
device application |
Distribution
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
Easy9 MCB
|
|
Poles |
4P
|
|
number of protected poles |
4
|
|
[In] rated current |
20 A
|
|
network type |
AC
|
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
10000 A Icn at 220 V AC 50/60 Hz conforming to IEC 60898-1
6000 A Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1 |
|
suitability for isolation |
Yes conforming to IEC 60898-1
|
network frequency |
50 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
220 V AC 50/60 Hz
400 V AC 50/60 Hz |
|
magnetic tripping limit |
5…10 x In
|
|
[Ics] rated service breaking capacity |
6 kA 100 % x Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1
|
|
[Ui] rated insulation voltage |
500 V AC 50/60 Hz conforming to IEC 60898-1
|
|
[Uimp] rated impulse withstand voltage |
4 kV conforming to IEC 60898-1
|
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Without
|
|
mounting mode |
Clip-on
|
|
mounting support |
DIN rail
|
|
9 mm pitches |
8
|
|
height |
81 mm
|
|
width |
72 mm
|
|
depth |
66.5 mm
|
|
colour |
Grey (RAL 7035)
|
|
mechanical durability |
10000 cycles
|
|
electrical durability |
4000 cycles
|
|
connections – terminals |
Tunnel type terminal (top or bottom) 1…25 mm² rigid
Tunnel type terminal (top or bottom) 1…16 mm² flexible |
|
tightening torque |
2 N.m top or bottom
|
₦5,999.00
Compare-
Schneider Circuit Breakers, SCHNEIDER SECTIONS
IC60H – miniature circuit breaker – 1P – 32A – C curve A9F84132
Schneider Circuit Breakers, SCHNEIDER SECTIONSIC60H – miniature circuit breaker – 1P – 32A – C curve A9F84132
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Hpoles description 1Pnumber of protected poles 1[In] rated current 32 Anetwork type DC
ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
15 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
42 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
30 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at 60…72 V DC conforming to EN/IEC 60947-2
20 kA Icu at 12…60 V DC conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards IEC 60947-2
IEC 60898-1
EN 60898-1
EN 60947-2Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 21 kA 50 % conforming to EN 60947-2 – 12…60 V AC 50/60 Hz
7.5 kA 50 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
21 kA 50 % conforming to IEC 60947-2 – 12…60 V AC 50/60 Hz
7.5 kA 50 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7500 A 75 % conforming to EN 60898-1 – 230 V AC 50/60 Hz
7500 A 75 % conforming to IEC 60898-1 – 230 V AC 50/60 Hz
15 kA 50 % conforming to IEC 60947-2 – 100…133 V AC 50/60 Hz
15 kA 50 % conforming to EN 60947-2 – 100…133 V AC 50/60 Hz
15 kA 100 % conforming to EN 60947-2 – 72 V DC
15 kA 100 % conforming to IEC 60947-2 – 72 V DC
20 kA 100 % conforming to EN 60947-2 – 12…60 V DC
20 kA 100 % conforming to IEC 60947-2 – 12…60 V DClimitation class 3 conforming to EN 60898-1
3 conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 2height 85 mmwidth 18 mmdepth 78.5 mmnet weight 0.215 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 3.5 N.m top or bottomearth-leakage protection WithoutSKU: n/a -
COMPUTING, PRINTERS
HP COLOUR LASERJET ENTERPRISE M652DN PRINTER
- Print only
- Print speed letter: Up to 50 ppm (black and color)
- Auto duplex printing; 2 paper trays (standard); Uses toner with JetIntelligence
- FCC Class A emissions – for use in commercial environments, not residential environments
SKU: n/a -
CHINT
Chint Sound And Light Control Time Delay 100w Switch
Chint Sound And Light Control Time Delay 100w Switch
See DetailsKey Features- High quality Energy Saving Auto Switch Controlled by Light and Sound
- Ideal Light Switch for use around bathroom,hallways, staircases and porches
- .Easy to install
250V Wall Mount Voice Light Sensor Switch Sound & Light Controlled Delay Switch Light on automatically when sound is detected in the dark,when in daytime or under strong light,circuit in the off state and the light does not turn on Features: 1.High quality Energy Saving Auto Switch Controlled by Light and Sound 2.Ideal Light Switch for use around bathroom,hallways, staircases and porches 3.Easy to installSKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Easy9 Residual Current Circuit Breaker – 2P – 63 A – 300 mA – AC type – 230 V EZ9R64263
Schneider Circuit Breakers, SCHNEIDER SECTIONSEasy9 Residual Current Circuit Breaker – 2P – 63 A – 300 mA – AC type – 230 V EZ9R64263
Main range of product Easy9product or component type Residual current circuit breaker (RCCB)device short name Easy9 RCCBPoles 2Pneutral position Left[In] rated current 63 Anetwork type ACearth-leakage sensitivity 300 mAearth-leakage protection time delay Instantaneousearth-leakage protection class Type ACrated breaking and making capacity 500 Arated conditional short-circuit current Easy9 MCB: 4500 A 63 AComplementary device location in system Outgoernetwork frequency 50 Hz[Ue] rated operational voltage 230 V AC 50 Hzresidual current tripping technology Voltage dependent[Ui] rated insulation voltage 440 V AC[Uimp] rated impulse withstand voltage 4 kVsurge current 250 Acontact position indicator Yescontrol type Togglemounting mode Clip-onmounting support DIN railcomb busbar and distribution block compatibility Top: YES9 mm pitches 4height 82 mmwidth 36 mmdepth 72 mmcolour Grey (RAL 7035)mechanical durability 5000 cycleselectrical durability AC: 2000 cycles 230 V AC 50 Hzconnections – terminals Tunnel type terminal (top or bottom) 1…25 mm² rigid
Tunnel type terminal (top or bottom) 1…16 mm² flexibletightening torque 2.5 N.m top or bottommarket segment Residential
Small commercialEnvironment standards IEC 61008-1product certifications GOST-R
CE
EACIP degree of protection IP20pollution degree 2 conforming to IEC 61008-1tropicalisation 2relative humidity 95 % at 55 °Cambient air temperature for operation -25…60 °Cambient air temperature for storage -40…85 °CSKU: n/a
There are no reviews yet.