Easy9 Residual Current Circuit Breaker – 2P – 63 A – 300 mA – AC type – 230 V EZ9R64263
range of product |
Easy9
|
|
---|---|---|
product or component type |
Residual current circuit breaker (RCCB)
|
|
device short name |
Easy9 RCCB
|
|
Poles |
2P
|
|
neutral position |
Left
|
|
[In] rated current |
63 A
|
|
network type |
AC
|
|
earth-leakage sensitivity |
300 mA
|
|
earth-leakage protection time delay |
Instantaneous
|
|
earth-leakage protection class |
Type AC
|
|
rated breaking and making capacity |
500 A
|
|
rated conditional short-circuit current |
Easy9 MCB: 4500 A 63 A
|
device location in system |
Outgoer
|
|
---|---|---|
network frequency |
50 Hz
|
|
[Ue] rated operational voltage |
230 V AC 50 Hz
|
|
residual current tripping technology |
Voltage dependent
|
|
[Ui] rated insulation voltage |
440 V AC
|
|
[Uimp] rated impulse withstand voltage |
4 kV
|
|
surge current |
250 A
|
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
mounting mode |
Clip-on
|
|
mounting support |
DIN rail
|
|
comb busbar and distribution block compatibility |
Top: YES
|
|
9 mm pitches |
4
|
|
height |
82 mm
|
|
width |
36 mm
|
|
depth |
72 mm
|
|
colour |
Grey (RAL 7035)
|
|
mechanical durability |
5000 cycles
|
|
electrical durability |
AC: 2000 cycles 230 V AC 50 Hz
|
|
connections – terminals |
Tunnel type terminal (top or bottom) 1…25 mm² rigid
Tunnel type terminal (top or bottom) 1…16 mm² flexible |
|
tightening torque |
2.5 N.m top or bottom
|
|
market segment |
Residential
Small commercial |
standards |
IEC 61008-1
|
|
---|---|---|
product certifications |
GOST-R
CE EAC |
|
IP degree of protection |
IP20
|
|
pollution degree |
2 conforming to IEC 61008-1
|
|
tropicalisation |
2
|
|
relative humidity |
95 % at 55 °C
|
|
ambient air temperature for operation |
-25…60 °C
|
|
ambient air temperature for storage |
-40…85 °C
|
₦12,999.00
Compare-
-
ACCESSORIES, ELECTRICAL INDUSTRIAL
Electronic Overload Relay – E80DU-80
The E80DU-80 is an self-supplied electronic overload relay, which means no extra external supply is needed. It offers reliable and fast protection for motors in the event of overload or phase failure. Easy to use like a thermal overload relay and compatible with standard motor applications, the electronic overload relay is convincing, above all, due to its wide setting range, high accuracy, high operational temperature range and the possibility to select a trip class (10E, 20E, 30E). Further features are the temperature compensation, trip contact (NC), signal contact (NO), automatic- or manual reset selectable, trip-free mechanism, STOP- and Test function and a trip indication. The overload relays are connected directly to the contactors. Single mounting kits are available as accessory.
General Information
-
- Extended Product Type: E80DU-80
-
- Product ID: 1SAX311001R1101
-
- EAN: 4016779666626
-
- Catalog Description: E80DU-80 Electronic Overload Relay
SKU: Overload Relay - E80DU-80 -
-
LIGHT SWITCHES & ELECTRICAL SOCKETS, SCHNEIDER SECTIONS
Ultimate Screwless flat plate – 1-pole 2-way switch – 2 gangs – stainless steel GU1422WSS
LIGHT SWITCHES & ELECTRICAL SOCKETS, SCHNEIDER SECTIONSUltimate Screwless flat plate – 1-pole 2-way switch – 2 gangs – stainless steel GU1422WSS
Main range of product Ultimaterange Ultimateaesthetic name Screwless flat plateproduct or component type Switchcontrol type Toggle switchswitch function 1-pole 2-wayrated current 16 AX at 230 V ACComplementary connections – terminals Screw terminalsmaterial Steelquantity per set Set of 1number of gangs 2 gangsdevice mounting Wall mountedheight 88 mmwidth 88 mmdepth 24 mmSKU: n/a -
CHINT
CHINT Kwh Meter Single
DDSU666 series three phase three wire electronic energy meter (DIN Rail) Summary :
DDSU666 series electronic energy meter is designed for power monitoring and energy measurement such as power system, communication industry, construction industry, etc. to be a new generation of programmable.
DDSU666 series three phase three wire electronic energy meter (DIN Rail)
Summary:
DDSU666 series electronic energy meter is designed for power monitoring and energy measurement such as power system, communication industry, construction industry, etc. to be a new generation of programmable intelligent instrument, integrated with measurement and communication function, mainly used for real-time measurement and display for the electrical parameters such as voltage, current, active power, reactive power, frequency, power factor, energy in the electrical circuit, etc.
1、Main functions and characteristics
◆DIN35mm Standard DIN-Rail, seven modulus with segment LCD display
◆Measurement function: Characterized with measurement for three phase three wire voltage, current, frequency, active power, power factor, active energy and reactive energy
◆communication function: RS485 communication interface, supporting DL/T645-2007 protocol, customizable for MODBUS-RTU protocol
◆Multi-rate function: it supports four rates including top, peak, flat, valley rate.
SKU: n/a -
CHINT
CHINT Extension Socket 6way NEA8-6103
CHINT Extension Socket 6way NEA8-6103
- Using bulletproof and flame retardant material, non-deforming and fadeless
- With high precision copper material, mechanical working life more than 10000 times
- The cable safety is good, its not abnormal heat if long time use
- The switch with silver cadmium
SKU: n/a
There are no reviews yet.