Easy9 miniature circuit breaker- 4P – 25 A – C curve – 6000 A – 400 V EZ9F56425
range |
Easy9
|
|
---|---|---|
device application |
Distribution
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
Easy9 MCB
|
|
Poles |
4P
|
|
number of protected poles |
4
|
|
[In] rated current |
25 A
|
|
network type |
AC
|
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
10000 A Icn at 220 V AC 50/60 Hz conforming to IEC 60898-1
6000 A Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1 |
|
suitability for isolation |
Yes conforming to IEC 60898-1
|
network frequency |
50 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
220 V AC 50/60 Hz
400 V AC 50/60 Hz |
|
magnetic tripping limit |
5…10 x In
|
|
[Ics] rated service breaking capacity |
6 kA 100 % x Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1
|
|
[Ui] rated insulation voltage |
500 V AC 50/60 Hz conforming to IEC 60898-1
|
|
[Uimp] rated impulse withstand voltage |
4 kV conforming to IEC 60898-1
|
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Without
|
|
mounting mode |
Clip-on
|
|
mounting support |
DIN rail
|
|
9 mm pitches |
8
|
|
height |
81 mm
|
|
width |
72 mm
|
|
depth |
66.5 mm
|
|
colour |
Grey (RAL 7035)
|
|
mechanical durability |
10000 cycles
|
|
electrical durability |
4000 cycles
|
|
connections – terminals |
Tunnel type terminal (top or bottom) 1…25 mm² rigid
Tunnel type terminal (top or bottom) 1…16 mm² flexible |
|
tightening torque |
2 N.m top or bottom
|
standards |
IEC 60898-1
|
|
---|---|---|
product certifications |
VDE
CE |
|
IP degree of protection |
IP20 conforming to IEC 60529
|
|
pollution degree |
2
|
|
tropicalisation |
2
|
|
relative humidity |
95 % at -5…60 °C
|
|
ambient air temperature for operation |
-5…60 °C
|
|
ambient air temperature for storage |
-40…85 °C
|
₦5,999.00
Compare-
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 1P 2A C Miniature Circuit breaker A9F44102
Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 1P 2A C Miniature Circuit breaker A9F44102
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 1Pnumber of protected poles 1[In] rated current 2 Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 50 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
50 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
50 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at 12…48 V DC conforming to EN/IEC 60947-2
6 kA Icu at 72 V DC conforming to EN/IEC 60947-2
6000 A Icn at 240 V AC 50/60 Hz conforming to EN/IEC 60898-1utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 240 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 50 kA 100 % conforming to EN/IEC 60947-2 – 12…60 V AC 50/60 Hz
50 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V AC 50/60 Hz
50 kA 100 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
6000 A 100 % conforming to EN/IEC 60898-1 – 240 V AC 50/60 Hz
15 kA 100 % conforming to EN/IEC 60947-2 – 12…48 V DC
6 kA 100 % conforming to EN/IEC 60947-2 – 72 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 2height 85 mmwidth 18 mmdepth 78.5 mmnet weight 0.125 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
ELECTRICAL FITTINGS, Electro, HOME&OFFICE LIGHTING, INDOOR LIGHTS, INTERIOR LIGHTING, LED LIGHTS, LIGHTING, OUTDOOR FITTINGS
PHILIPS BULKHEAD WT045C LED20/CW PSU CFW L1665 (Cool White) Essential Smartbright Bulkhead
ELECTRICAL FITTINGS, Electro, HOME&OFFICE LIGHTING, INDOOR LIGHTS, INTERIOR LIGHTING, LED LIGHTS, LIGHTING, OUTDOOR FITTINGSPHILIPS BULKHEAD WT045C LED20/CW PSU CFW L1665 (Cool White) Essential Smartbright Bulkhead
Light Technical
- Luminous Flux – 1,600 lm
- Correlated Color Temperature (Nom) – 6500 K
- Luminous Efficacy (rated) (Nom) – 80 lm/W
- Color rendering index (CRI) – >70
- Beam angle of light source – 120 degree(s)
- Light source color – cool white
- Optical cover type – Polycarbonate bowl/cover
- Luminaire light beam spread – 100° x 120°
Mechanical and Housing
- Housing Material – Polypropylene
- Reflector material – Polycarbonate
- Optic material – Polycarbonate
- Optical cover material – Polycarbonate
- Fixation material – Polypropylene
- Housing Color – White
- Optical cover finish – Opal
- Overall height – 88 mm
- Overall diameter – 220 mm
SKU: n/a -
ELECTRICAL INDUSTRIAL, Electro, Schneider, SCHNEIDER ELECTRIC BRANDS, TRANSFORMER
Schneider 100kVA 11/400 CuCu Transformer
ELECTRICAL INDUSTRIAL, Electro, Schneider, SCHNEIDER ELECTRIC BRANDS, TRANSFORMERSchneider 100kVA 11/400 CuCu Transformer
Features
Distribution transformers from Schneider Electric are available in ratings from 100kVA upto 4000kVA at voltages upto 36kV. They can be supplied in many types and styles, with standard industry fittings or bespoke design to the customers specific requirements. Choices available include:
- Type – Free Breathing (with or without conservator) or Hermetically sealed
- Style – Ground Mounted Cable Connected, Unit Substation or Bespoke to customer requirements
- Insulating Fluids – Mineral Oil or Midel 7131 Transformer Fluid
- Eco losses
- In addition, transformers can be supplied with directly mounted MV or LV switchgear to form an assembled package substation
Benefits
- Large choice of ratings, types and styles
- Bespoke or Standard Design
- Manufactured to specific customer requirements
- Available with MV & LV Switchgear
- Direct to Site Deliveries
- Ease of Installation
Applications
- Energy
- Infrastructure
- Commercial
SKU: n/a -
DISTRIBUTION BOARDS, DISTRIBUTION BOARDS, Electro
ABB 12 Way Three Phase Distribution Board
Available in kit form for over-the counter-supply, the latest generation sub-distribution solution from ABB has been tailored to meet the needs of all segments of the building industry.
Main construction features:
• Structure in epoxy coated metal sheets, 1mm thickness
• Wall installation for indoor environments
• Degree of protection – IP43 with door / Mechanical resistance IK 07
• Busbar rating: 250A
• Number of ways: 4, 8, 12, 16, 20, 24
• Compliance with IEC BS EN 61439 1-2
• Simple wiring of all cabinets, both horizontally and vertically
• Easy internal accessibility for wiring operations and maintenance
• Pre-packaged kits for specific applications (e.g. surge protection, metering)SKU: n/a -
CIRCUIT BREAKERS
Circuit breaker Easypact EZC250N – TMD – 200 A – 3 poles 3d
Main range of product EasyPactproduct or component type Circuit breakerdevice short name Easypact EZC250Ncircuit breaker name Easypact EZC250Ndevice application Distributionpoles description 3Pprotected poles description 3tnetwork type DC
ACnetwork frequency 50/60 Hz[In] rated current 250 A at 40 °C[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2[Ue] rated operational voltage 550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2breaking capacity code Nbreaking capacity 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
20 kA Icu at 125 V DC 1P conforming to IEC 60947-2
20 kA Icu at 250 V DC 2P conforming to IEC 60947-2
25 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 400…415 V AC 50/60 Hz conforming to IEC 60947-2
8 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2[Ics] rated service breaking capacity 10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
25 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2
10 kA at 125 V DC conforming to IEC 60947-2
10 kA at 250 V DC conforming to IEC 60947-2
25 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2
4 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2suitability for isolation Yes conforming to IEC 60947-2utilisation category Category Atrip unit name TM-Dtrip unit technology Thermal-magnetictrip unit rating 200 A at 50 °Cprotection type Overload protection
Short-circuit protectionpollution degree 3 conforming to IEC 60664-1
3 conforming to IEC 947-1Complementary control type Togglemounting mode Fixedmounting support Backplateupside connection Frontdownside connection Frontmechanical durability 10000 cycleselectrical durability Category A: 5000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2connection pitch 35 mmlocal signalling Positive contact indicationneutral protection setting Without protectionearth-leakage protection Withoutheight 165 mmwidth 105 mmdepth 60 mmSKU: n/a -
Electro, Low Voltage Products and Systems, SCHNEIDER SECTIONS
EZC250N4250 Circuit breaker Easypact EZC250N – TMD – 250 A – 4 poles 3d
Electro, Low Voltage Products and Systems, SCHNEIDER SECTIONSEZC250N4250 Circuit breaker Easypact EZC250N – TMD – 250 A – 4 poles 3d
Main
Range of product EasyPact
Product or component type Circuit breaker
Device short name Easypact EZC250N
Circuit breaker name Easypact EZC250N
Device application Distribution
Poles description 4P
Protected poles description 3t
Network type AC
DC
Network frequency 50/60 Hz
[In] rated current 250 A at 40 °C
[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2
[Ue] rated operational voltage 550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2
Breaking capacity code N
Breaking capacity 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
20 kA Icu at 125 V DC 1P conforming to IEC 60947-2
20 kA Icu at 250 V DC 2P conforming to IEC 60947-2
8 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 380…415 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity 10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
25 kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
10 kA at 125 V DC conforming to IEC 60947-2
10 kA at 250 V DC conforming to IEC 60947-2
4 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 380…415 V AC 50/60 Hz conforming to IEC 60947-2
Suitability for isolation Yes conforming to IEC 60947-2
Utilisation category Category ASKU: n/a
There are no reviews yet.