Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Easy9 miniature circuit breaker- 4P – 6 A – C curve – 6000 A – 400 V EZ9F56406
range |
Easy9
|
|
---|---|---|
device application |
Distribution
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
Easy9 MCB
|
|
Poles |
4P
|
|
number of protected poles |
4
|
|
[In] rated current |
6Â A
|
|
network type |
AC
|
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
10000Â A Icn at 220 V AC 50/60 Hz conforming to IEC 60898-1
6000Â A Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1 |
|
suitability for isolation |
Yes conforming to IEC 60898-1
|
network frequency |
50 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
220 V AC 50/60 Hz
400 V AC 50/60 Hz |
|
magnetic tripping limit |
5…10 x In
|
|
[Ics] rated service breaking capacity |
6Â kA 100Â % x Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1
|
|
[Ui] rated insulation voltage |
500Â V AC 50/60 Hz conforming to IEC 60898-1
|
|
[Uimp] rated impulse withstand voltage |
4Â kV conforming to IEC 60898-1
|
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Without
|
|
mounting mode |
Clip-on
|
|
mounting support |
DIN rail
|
|
9 mm pitches |
8
|
|
height |
81Â mm
|
|
width |
72Â mm
|
|
depth |
66.5Â mm
|
|
colour |
Grey (RAL 7035)
|
|
mechanical durability |
10000Â cycles
|
|
electrical durability |
4000Â cycles
|
|
connections – terminals |
Tunnel type terminal (top or bottom) 1…25 mm² rigid
Tunnel type terminal (top or bottom) 1…16 mm² flexible |
|
tightening torque |
2Â N.m top or bottom
|
₦14,500.00
Compare-
Electro, SCHNEIDER SECTIONS, Schneider Thorsman Testmeters
Thorsman Digital Multimeter Cat III 300V IMT23102
Electro, SCHNEIDER SECTIONS, Schneider Thorsman TestmetersThorsman Digital Multimeter Cat III 300V IMT23102
Main range Thorsmanproduct or component type Digital multimetersupply battery 9 VComplementary display type Backlit monochrome STN LCDtype of setting Manualsignaling function Low battery by visualfunction available Live AC wire detection
Stand alone equipment control
Data hold function
Non-contact AC voltage detectionprotection type Fusetype of measurement Resistance: 200 Ohm/2/20/200 kOhm/20 MOhm
Battery voltage: 1.5/9 V/12 V
Continuity: < 100 Ohm
Voltage DC: 0.2/2/20/200/300 V
Voltage AC: 0.2/2/20/200/300 V
Current DC: 20 mA/200 mA/10 A
Temperature: 0…1000 °Cmeasurement category Category III 300 Vlanguage Swedish
Finnish
Danish
Norwegian
Englishheight 165Â mmwidth 85Â mmdepth 39Â mmnet weight 290Â g with batterySKU: n/a -
EARTH LEAKAGE PROTECTION DEVICES, ELECTRICAL INDUSTRIAL, Electro
Lutron Gu-3001 Precision Milli Gauss Meter
EARTH LEAKAGE PROTECTION DEVICES, ELECTRICAL INDUSTRIAL, ElectroLutron Gu-3001 Precision Milli Gauss Meter
Lutron GU-3001 is a precision milli gauss meter.
Resolution:
– 199.9 mG to 199.9 mG.
200 mG, -200 mG
– 19.99 uT to 19.99 uT.
20.0 uT, -20.0 uT.Accuracy ± ( 2 % + 2 mG )
DC/AC miligauss Magnetometer
DC and AC magnetic field measurement
Wide measure range: 3,000 milligauss
N pole/S pole indicator
RS232/USB computer interface
The meter can detect the magnetic fields as small as 0.1 milligaus
Auto shut off is available to save battery life
Power supply from batteries or DC 9V adapter inSKU: n/a -
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Easy9 miniature circuit breaker- 4P – 16 A – C curve – 6000 A – 400 V EZ9F56416
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSEasy9 miniature circuit breaker- 4P – 16 A – C curve – 6000 A – 400 V EZ9F56416
Main range Easy9device application Distributionproduct or component type Miniature circuit-breakerdevice short name Easy9 MCBPoles 4Pnumber of protected poles 4[In] rated current 16Â Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000Â A Icn at 220 V AC 50/60 Hz conforming to IEC 60898-1
6000Â A Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1suitability for isolation Yes conforming to IEC 60898-1Complementary network frequency 50 Hz[Ue] rated operational voltage 220 V AC 50/60 Hz
400 V AC 50/60 Hzmagnetic tripping limit 5…10 x In[Ics] rated service breaking capacity 6 kA 100 % x Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to IEC 60898-1[Uimp] rated impulse withstand voltage 4 kV conforming to IEC 60898-1contact position indicator Yescontrol type Togglelocal signalling Withoutmounting mode Clip-onmounting support DIN rail9 mm pitches 8height 81 mmwidth 72 mmdepth 66.5 mmcolour Grey (RAL 7035)mechanical durability 10000 cycleselectrical durability 4000 cyclesconnections – terminals Tunnel type terminal (top or bottom) 1…25 mm² rigid
Tunnel type terminal (top or bottom) 1…16 mm² flexibletightening torque 2 N.m top or bottomEnvironment standards IEC 60898-1product certifications VDE
CEIP degree of protection IP20 conforming to IEC 60529pollution degree 2tropicalisation 2relative humidity 95 % at -5…60 °Cambient air temperature for operation -5…60 °Cambient air temperature for storage -40…85 °CSKU: n/a -
Electro, LIGHT SWITCHES & ELECTRICAL SOCKETS
Schneider 10A 250V Bell Press Switch with Bell Icon KB31BPB
Electro, LIGHT SWITCHES & ELECTRICAL SOCKETSSchneider 10A 250V Bell Press Switch with Bell Icon KB31BPB
Main range Vivaceproduct or component type Switchdevice short name KB31device presentation Complete mechanismAdditional switch application Bell switchComplementary switch function 1-wayactuator Rockernumber of gangs 1 gangcolour tint Whitematerial Polycarbonate: grid plate
Polycarbonate: surround
Polycarbonate: baseprojecting depth 8Â mmdevice mounting Flushmounting support Wall mountedfixing mode By screw M3.5fixing center 60.3 mmembedding depth 35Â mmrated current 10 A at 250 V AC, inductive[Ue] rated operational voltage 250 V ACnetwork frequency 50 Hzcontacts material Brass and phosphor bronzeconnections – terminals pillar terminalterminal identifier L1
L2
COMtightening torque 0.4 N.mclamping connection capacity 1.5 mm²width 87 mmheight 87 mmSKU: n/a
There are no reviews yet.