Schneider Circuit Breakers, SCHNEIDER SECTIONS
Easy9 switch disconnector – 2P – 125 A – 400 V EZ9S16292
range |
Easy9
|
|
---|---|---|
product or component type |
Switch
|
|
device short name |
Easy9 switch
|
|
switch application |
Distribution
|
|
Poles |
2P
|
|
utilisation category |
AC-22A
|
|
suitability for isolation |
Yes
|
[Ie] rated operational current |
125 A at 400 V 50/60 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
400 V AC 50/60 Hz
|
|
[Icm] rated short-circuit making capacity |
1.875 kA
|
|
[Icw] rated short-time withstand current |
1.5 kA during 1 s
|
|
[Ui] rated insulation voltage |
500 V AC 50/60 Hz
|
|
[Uimp] rated impulse withstand voltage |
4 kV
|
|
control type |
Toggle
|
|
local signalling |
ON/OFF indication
|
|
contact position indicator |
Yes
|
|
mounting mode |
Clip-on
|
|
mounting support |
DIN rail
|
|
9 mm pitches |
4
|
|
height |
81 mm
|
|
width |
36 mm
|
|
depth |
66.5 mm
|
|
colour |
Grey
|
|
mechanical durability |
7000 cycles
|
|
electrical durability |
1000 cycles
|
|
connections – terminals |
Tunnel type terminal (top or bottom) 1…50 mm² rigid
Tunnel type terminal (top or bottom) 1…35 mm² flexible |
|
tightening torque |
3.5 N.m
|
₦4,999.00
Compare-
-
LIGHT SWITCHES & ELECTRICAL SOCKETS
1 Gang Cable TVF Connector KB31TVF
Main range of product Vivacedevice short name KB31product or component type TVF socketdevice presentation Complete mechanismComplementary number of gangs 1 gangnumber of outputs 1Colour tint Whitematerial Polycarbonate: surround
Polycarbonate: grid plate
Polycarbonate: baseprojecting depth 8 mmdevice mounting Flushmounting support Wall mountedfixing mode By screw M3.5fixing center 60.3 mmembedding depth 35 mmconnections – terminals Clamp terminaltightening torque 0.4 N.mwidth 87 mmheight 87 mmSKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 2P 1A C Miniature Circuit breaker A9F44201
Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 2P 1A C Miniature Circuit breaker A9F44201
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 2Pnumber of protected poles 2[In] rated current 1 Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 50 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
50 kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
50 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
25 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
6 kA Icu at 100…133 V DC conforming to EN/IEC 60947-2
6000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 440 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 50 kA 100 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
50 kA 100 % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz
50 kA 100 % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz
25 kA 100 % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz
6000 A 100 % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz
6 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 4height 85 mmwidth 36 mmdepth 78.5 mmnet weight 0.25 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockEnvironment standards EN/IEC 60947-2
EN/IEC 60898-1IP degree of protection IP20 conforming to IEC 60529pollution degree 3 conforming to EN/IEC 60947-2tropicalisation 2 conforming to IEC 60068-1relative humidity 95 % at 55 °Cambient air temperature for operation -35…70 °Cambient air temperature for storage -40…85 °CSKU: n/a -
LIGHT SWITCHES & ELECTRICAL SOCKETS, SCHNEIDER SECTIONS
AvatarOn, switched socket, 3P, 13 A, 250 V, Dark Grey E8315_DG
LIGHT SWITCHES & ELECTRICAL SOCKETS, SCHNEIDER SECTIONSAvatarOn, switched socket, 3P, 13 A, 250 V, Dark Grey E8315_DG
Main product or component type Switched socketdevice application Power supplydevice presentation Complete producttype of packing Flow-packComplementary socket number 1outlet standard description With earthing contactoutlet standard British BS 1363Anumber of gangs 1 gangservice life in cycles 20000 cycleselectrical durability 5000 cyclesconnections – terminals Screw terminalsurface finish Glossydevice mounting Surfacefixing mode Screwheight 86 mmwidth 86 mmdepth 31.7 mmSKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 2P 6A C Miniature Circuit breaker
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 2Pnumber of protected poles 2[In] rated current 6 Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 6 kA Icu at 100…133 V DC conforming to EN/IEC 60947-2
6000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1
36 kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
20 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 440 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 27 kA 75 % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz
15 kA 75 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 75 % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz
4.5 kA 75 % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz
6000 A 100 % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz
6 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 4height 85 mmwidth 36 mmdepth 78.5 mmnet weight 0.25 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
LIGHT SWITCHES & ELECTRICAL SOCKETS
Lisse – Fuse connection unit – 1 gang – 13 A – white moulded GGBL5000
LIGHT SWITCHES & ELECTRICAL SOCKETSLisse – Fuse connection unit – 1 gang – 13 A – white moulded GGBL5000
Main range Lisseaesthetic name White mouldedproduct or component type Fuse connection unitdevice presentation Complete productcolour tint white mouldedquantity per set Set of 10Complementary pilot light without LEDnumber of gangs 1 gangmaterial Urea (carbamide)device mounting Wall mountedfixing mode By screwsrated current 13 A at 250 V ACconnections – terminals Screw terminalstype of packing Cartonwidth 87 mmheight 87 mmdepth 25 mmnet weight 0.091 kgSKU: n/a