Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Easy9 switch disconnector – 3P – 63 A – 400 V EZ9S16363
range |
Easy9
|
|
---|---|---|
product or component type |
Switch
|
|
device short name |
Easy9 switch
|
|
switch application |
Distribution
|
|
Poles |
3P
|
|
utilisation category |
AC-22A
|
|
suitability for isolation |
Yes
|
[Ie] rated operational current |
63 A at 400 V 50/60 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
400 V AC 50/60 Hz
|
|
[Icm] rated short-circuit making capacity |
0.945 kA
|
|
[Icw] rated short-time withstand current |
0.756 kA during 1 s
|
|
[Ui] rated insulation voltage |
500 V AC 50/60 Hz
|
|
[Uimp] rated impulse withstand voltage |
4 kV
|
|
control type |
Toggle
|
|
local signalling |
ON/OFF indication
|
|
contact position indicator |
Yes
|
|
mounting mode |
Clip-on
|
|
mounting support |
DIN rail
|
|
9 mm pitches |
6
|
|
height |
81 mm
|
|
width |
54 mm
|
|
depth |
66.5 mm
|
|
colour |
Grey
|
|
mechanical durability |
8500 cycles
|
|
electrical durability |
1500 cycles
|
|
connections – terminals |
Tunnel type terminal (top or bottom) 1…35 mm² rigid
Tunnel type terminal (top or bottom) 1…25 mm² flexible |
|
tightening torque |
3.5 N.m
|
₦15,000.00
Compare-
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Miniature circuit-breaker, Acti9 iC60H, 2P, 63 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84263
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSMiniature circuit-breaker, Acti9 iC60H, 2P, 63 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84263
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Hpoles description 2Pnumber of protected poles 2[In] rated current 63 Anetwork type DC
ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
42 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
30 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at <= 125 V DC conforming to EN/IEC 60947-2
42 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards IEC 60947-2
IEC 60898-1
EN 60947-2
EN 60898-1Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 15 kA 50 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 50 % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz
5 kA 50 % conforming to EN 60947-2 – 440 V AC 50/60 Hz
15 kA 50 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 50 % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz
5 kA 50 % conforming to IEC 60947-2 – 440 V AC 50/60 Hz
7500 A 75 % conforming to EN 60898-1 – 400 V AC 50/60 Hz
7500 A 75 % conforming to IEC 60898-1 – 400 V AC 50/60 Hz
21 kA 50 % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz
21 kA 50 % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz
15 kA 100 % conforming to IEC 60947-2 – 72…125 V DC
15 kA 100 % conforming to EN 60947-2 – 72…125 V DC[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 4height 85 mmwidth 36 mmdepth 78.5 mmnet weight 0.25 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 3.5 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
DISTRIBUTION BOARDS, DISTRIBUTION BOARDS, Electro
Easy9 distribution board – 1P – 100A – 8 ways – fixed
DISTRIBUTION BOARDS, DISTRIBUTION BOARDS, ElectroEasy9 distribution board – 1P – 100A – 8 ways – fixed
Main range Easy9product or component type Enclosureenclosure type Distribution enclosureprovided equipment 1 x washer
Identification label
4 x screws
Removable front coverComplementary enclosure mounting Surface
FlushNb of horizontal rows 1number of plates 3 for plain platenetwork number of phases Single phasenumber of ways 8 waystype of rail DINcable entry 6 knock-outsType of door Plain door[In] rated current 100 Aenclosure material Powder coated steelwidth 362 mm outside:height 232 mm outside:depth 90 mm outside:colour Grey (RAL 7035)SKU: n/a -
-
ELECTRICAL FITTINGS, Electro, HOME&OFFICE LIGHTING, INDOOR LIGHTS, INTERIOR LIGHTING, LED LIGHTS, LIGHTING, OUTDOOR FITTINGS
PHILIPS BULKHEAD WT045C LED20/CW PSU CFW L1665 (Cool White) Essential Smartbright Bulkhead
ELECTRICAL FITTINGS, Electro, HOME&OFFICE LIGHTING, INDOOR LIGHTS, INTERIOR LIGHTING, LED LIGHTS, LIGHTING, OUTDOOR FITTINGSPHILIPS BULKHEAD WT045C LED20/CW PSU CFW L1665 (Cool White) Essential Smartbright Bulkhead
Light Technical
- Luminous Flux – 1,600 lm
- Correlated Color Temperature (Nom) – 6500 K
- Luminous Efficacy (rated) (Nom) – 80 lm/W
- Color rendering index (CRI) – >70
- Beam angle of light source – 120 degree(s)
- Light source color – cool white
- Optical cover type – Polycarbonate bowl/cover
- Luminaire light beam spread – 100° x 120°
Mechanical and Housing
- Housing Material – Polypropylene
- Reflector material – Polycarbonate
- Optic material – Polycarbonate
- Optical cover material – Polycarbonate
- Fixation material – Polypropylene
- Housing Color – White
- Optical cover finish – Opal
- Overall height – 88 mm
- Overall diameter – 220 mm
SKU: n/a -
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Easy9 miniature circuit breaker- 3P – 6 A – C curve – 6000 A – 400 V EZ9F56306
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSEasy9 miniature circuit breaker- 3P – 6 A – C curve – 6000 A – 400 V EZ9F56306
Main range Easy9device application Distributionproduct or component type Miniature circuit-breakerdevice short name Easy9 MCBPoles 3Pnumber of protected poles 3[In] rated current 6 Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000 A Icn at 220 V AC 50/60 Hz conforming to IEC 60898-1
6000 A Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1suitability for isolation Yes conforming to IEC 60898-1Complementary network frequency 50 Hz[Ue] rated operational voltage 220 V AC 50/60 Hz
400 V AC 50/60 Hzmagnetic tripping limit 5…10 x In[Ics] rated service breaking capacity 6 kA 100 % x Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to IEC 60898-1[Uimp] rated impulse withstand voltage 4 kV conforming to IEC 60898-1contact position indicator Yescontrol type Togglelocal signalling Withoutmounting mode Clip-onmounting support DIN rail9 mm pitches 6height 81 mmwidth 54 mmdepth 66.5 mmcolour Grey (RAL 7035)mechanical durability 10000 cycleselectrical durability 4000 cyclesconnections – terminals Tunnel type terminal (top or bottom) 1…25 mm² rigid
Tunnel type terminal (top or bottom) 1…16 mm² flexibletightening torque 2 N.m top or bottomSKU: n/a -
Electro, Schneider, SCHNEIDER SECTIONS
Easy9 distribution board – 1P – 100A – 6 ways – fixed EZ9ES6L
Main range Easy9product or component type Enclosureenclosure type Distribution enclosureprovided equipment 1 x washer
Identification label
4 x screws
Removable front coverComplementary enclosure mounting Surface
FlushNb of horizontal rows 1number of plates 2 for plain platenetwork number of phases Single phasenumber of ways 6 waystype of rail DINcable entry 4 knock-outsType of door Plain door[In] rated current 100 Aenclosure material Powder coated steelwidth 290 mm outside:height 232 mm outside:depth 90 mm outside:colour Grey (RAL 7035)Environment standards IEC 61439-3
IEC 61439-1product certifications ASTAIP degree of protection IP40 conforming to IEC 60529 (closed door)IK degree of protection IK08 conforming to IEC 62262ambient air temperature for operation 50 °CPacking Units Package 1 Weight 3150.000 kgPackage 1 Height 95.000 mmPackage 1 width 232.000 mmPackage 1 Length 290.000 mmSKU: n/a
There are no reviews yet.