Easy9 switch disconnector – 4P – 100 A – 400 V EZ9S16491
range |
Easy9
|
|
---|---|---|
product or component type |
Switch
|
|
device short name |
Easy9 switch
|
|
switch application |
Distribution
|
|
Poles |
4P
|
|
utilisation category |
AC-22A
|
|
suitability for isolation |
Yes
|
[Ie] rated operational current |
100 A at 400 V 50/60 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
400 V AC 50/60 Hz
|
|
[Icm] rated short-circuit making capacity |
1.5 kA
|
|
[Icw] rated short-time withstand current |
1.2 kA during 1 s
|
|
[Ui] rated insulation voltage |
500 V AC 50/60 Hz
|
|
[Uimp] rated impulse withstand voltage |
4 kV
|
|
control type |
Toggle
|
|
local signalling |
ON/OFF indication
|
|
contact position indicator |
Yes
|
|
mounting mode |
Clip-on
|
|
mounting support |
DIN rail
|
|
9 mm pitches |
8
|
|
height |
81 mm
|
|
width |
72 mm
|
|
depth |
66.5 mm
|
|
colour |
Grey
|
|
mechanical durability |
8500 cycles
|
|
electrical durability |
1500 cycles
|
|
connections – terminals |
Tunnel type terminal (top or bottom) 1…50 mm² rigid
Tunnel type terminal (top or bottom) 1…35 mm² flexible |
|
tightening torque |
3.5 N.m
|
₦10,399.00
Compare-
Electro, SOLAR POWERED
Solar Homaya Hybrid Home System 1500 – Schneider Electric
Features
Recommended Solar Panel Wattage – 1000 Wp, 24V with OCV of 36V to 45V
AC Input – 230V AC, 50 Hz
AC output – 1500VA – 230V AC, 50 Hz
DC output – 12V, 5A
Recommended Battery Size – 24V, 100Ah to 200Ah
Recommended Battery type – Supports Tubular, Flat plate, GEL/VRLA battery
Product dimensions in mm (LxWxH) – 375 x 315 x 150
Safety and reliability – Protected against short-circuit, High temperature and Internal fault protectionBenefits
- Secure Power- Serves both unreliable and off-grid geographies
- Supports household energy requirement- Powers the common AC appliances in homes and shops
SKU: n/a -
-
ELECTRICAL INDUSTRIAL, TRANSFORMER
ABB Transformer 800kVA 400/11 ABB Cu/Cu Oil Filled Ground-mounting
ELECTRICAL INDUSTRIAL, TRANSFORMERABB Transformer 800kVA 400/11 ABB Cu/Cu Oil Filled Ground-mounting
Distribution transformers are typically oil-immersed and suitable for pole-, pad- or ground-mounting. They represent an economical option for certain networks, particularly those with low population densities. Depending upon requirements, transformers may be connected between two phases of a three-phase system (two high voltage bushings) or from one phase to ground (single high voltage bushing). The units are suitable for residential overhead distribution loads, as well as light commercial or industrial loads and diversified power applications. Product scope Primary voltage: up to 36 kV Typical fluid: mineral oil.
Technical Specification
Product Name: Liquid-Filled Groundmount Transformer; 800 kVA
Rated Power 800[kVA]
Insulation Liquid: Mineral Oil
Low Voltage at no Load: 415[V]
Number of phases 3
Max. average temperature rise (Oil/Winding): 60 / 65[C/C]
Location Indoor/Outdoor
Rate Voltage: 11-0,415KV
Total Weight: 2100[kg]
SKU: dts80033-1 -
LIGHT SWITCHES & ELECTRICAL SOCKETS, SCHNEIDER SECTIONS
Ultimate Screwless flat plate – switched socket – 1 gang – stainless steel GU3410BSS
LIGHT SWITCHES & ELECTRICAL SOCKETS, SCHNEIDER SECTIONSUltimate Screwless flat plate – switched socket – 1 gang – stainless steel GU3410BSS
Main aesthetic name Screwless flat plateproduct or component type Switched socketrated current 13 A at 230 V AC 50 Hzfixing mode By screws M3.5 x 30 mmcolour tint Stainless steelComplementary device presentation Complete productoutlet poles configuration 1Poutlet standard description 3 pinsoutlet standard Britishactuator Rockernumber of gangs 1 gangearth circuit Standard earthpilot light Without neon indicatordevice mounting Wall mountedconnections – terminals Screw terminalmaterial Steelquantity per set Set of 1height 88 mmwidth 88 mmdepth 30 mmsocket number 2SKU: n/a -
-
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 1P 2A C Miniature Circuit breaker A9F44102
Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 1P 2A C Miniature Circuit breaker A9F44102
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 1Pnumber of protected poles 1[In] rated current 2 Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 50 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
50 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
50 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at 12…48 V DC conforming to EN/IEC 60947-2
6 kA Icu at 72 V DC conforming to EN/IEC 60947-2
6000 A Icn at 240 V AC 50/60 Hz conforming to EN/IEC 60898-1utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 240 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 50 kA 100 % conforming to EN/IEC 60947-2 – 12…60 V AC 50/60 Hz
50 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V AC 50/60 Hz
50 kA 100 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
6000 A 100 % conforming to EN/IEC 60898-1 – 240 V AC 50/60 Hz
15 kA 100 % conforming to EN/IEC 60947-2 – 12…48 V DC
6 kA 100 % conforming to EN/IEC 60947-2 – 72 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 2height 85 mmwidth 18 mmdepth 78.5 mmnet weight 0.125 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockSKU: n/a