EZC100F3060 – Circuit breaker Easypact EZC100F – TMD – 60 A – 3 poles 3d
range of product |
EasyPact
|
|
---|---|---|
product or component type |
Circuit breaker
|
|
device short name |
Easypact EZC100F
|
|
circuit breaker name |
Easypact EZC100F
|
|
device application |
Distribution
|
|
poles description |
3P
|
|
protected poles description |
3t
|
|
network type |
DC
AC |
|
network frequency |
50/60 Hz
|
|
[In] rated current |
100 A at 40 °C
|
|
[Ui] rated insulation voltage |
690 V AC 50/60 Hz conforming to IEC 60947-2
|
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to IEC 60947-2
|
|
[Ue] rated operational voltage |
550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2 |
|
breaking capacity code |
F
|
|
breaking capacity |
25 kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 125 V DC 1P conforming to IEC 60947-2 5 kA Icu at 250 V DC 2P conforming to IEC 60947-2 5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 400…415 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Ics] rated service breaking capacity |
12.5 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 125 V DC conforming to IEC 60947-2 2.5 kA at 250 V DC conforming to IEC 60947-2 2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 5 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 3.75 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to IEC 60947-2
|
|
utilisation category |
Category A
|
|
trip unit name |
TM-D
|
|
trip unit technology |
Thermal-magnetic
|
|
trip unit rating |
60 A at 50 °C
|
|
protection type |
Overload protection
Short-circuit protection |
|
pollution degree |
3 conforming to IEC 60664-1
3 conforming to IEC 947-1 |
control type |
Toggle
|
|
---|---|---|
mounting mode |
Fixed
|
|
mounting support |
Backplate
|
|
upside connection |
Front
|
|
downside connection |
Front
|
|
mechanical durability |
8500 cycles
|
|
electrical durability |
Category A: 1500 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
|
|
connection pitch |
25 mm
|
|
local signalling |
Positive contact indication
|
|
neutral protection setting |
Without protection
|
|
earth-leakage protection |
Without
|
|
height |
130 mm
|
|
width |
75 mm
|
|
depth |
60 mm
|
₦17,999.00
Compare-
ELECTRICAL INDUSTRIAL, TRANSFORMER
BETA 750KVA/33/0.415V COPPER/COPPER WINDING TRANSFORMER
Produced within a power range between 10 – 100.000 kVA , up to 170 kV high voltage level, three phase or single phase, oil immersed, ONAN, ONAF, OFWF, with Off-Load or On-Load Tap Changer, used both external and internal.
Dimensions of transformer conservator are determined and designed after several heat calculations of the oil stored in expansion tank and oil level changes by heat.
Being open to atmosphere, oil pressure changes continuously in Conservator Type Transformers due to thermal effects and exchange of air is dehumidified via air breather silicagel.SKU: n/a -
Electro, Low Voltage Products and Systems, SCHNEIDER SECTIONS
EZC250N4160 Circuit breaker Easypact EZC250N – TMD – 160 A – 4 poles 3d
Electro, Low Voltage Products and Systems, SCHNEIDER SECTIONSEZC250N4160 Circuit breaker Easypact EZC250N – TMD – 160 A – 4 poles 3d
Main range of product EasyPact Product or component typee Circuit breaker Device short name Easypact EZC250N circuit breaker name Easypact EZC250N Device application Distribution Poles description 4P Protected poles description 3t Network type AC
DCNetwork frequency 50/60 Hz [In] rated current 160 A at 40 °C [Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2 [Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2 [Ue] rated operational voltage 550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2Breaking capacity code N Breaking capacity 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
20 kA Icu at 125 V DC 1P conforming to IEC 60947-2
20 kA Icu at 250 V DC 2P conforming to IEC 60947-2
8 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 380…415 V AC 50/60 Hz conforming to IEC 60947-2[Ics] rated service breaking capacity 10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
25 kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
10 kA at 125 V DC conforming to IEC 60947-2
10 kA at 250 V DC conforming to IEC 60947-2
4 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 380…415 V AC 50/60 Hz conforming to IEC 60947-2Suitability for isolation Yes conforming to IEC 60947-2 utilisation category Category A Trip unit name TM-D Trip unit technology Thermal-magnetic Trip unit rating 160 A at 50 °C Protection type Short-circuit protection
Overload protectionPollution degree 3 conforming to IEC 60947 Complementary control type Toggle Mounting mode Fixed mounting support Backplate Upside connection Front downside connection Front Mechanical durability 10000 cycles Electrical durability Category A: 5000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2 Connection pitch 35 mm local signalling Positive contact indication Neutral protection setting Without protection earth-leakage protection Without height 165 mm Width 140 mm Depth 60 mm Environment Standards JIS C8201-2-2
EN/IEC 60947-2
GB/T 14048.2
EN/IEC 60947-1IP degree of protection IP20 conforming to IEC 60529 IK degree of protection IK07 conforming to EN 50102 ambient air temperature for operation -25…70 °C Ambient air temperature for storage -35…85 °C Packing Units Unit Type of Package 1 PCE Number of Units in Package 1 1 Package 1 Height 11.0 cm Package 1 Width 14.5 cm Package 1 Length 18.5 cm Package 1 Weight 2.24 kg Unit Type of Package 2 S03 Number of Units in Package 2 6 Package 2 Height 30.0 cm Package 2 Width 30.0 cm Package 2 Length 40.0 cm Package 2 Weight 13.927 kg Unit Type of Package 3 PAL Number of Units in Package 3 96 Package 3 Height 72.0 cm Package 3 Width 125.0 cm Package 3 Length 96.0 cm Package 3 Weight 215.04 kg SKU: n/a -
ELECTRICAL INDUSTRIAL, Electro, Generators, Generators & Power Solutions
YTO Diesel Engine Soundproof Diesel Generator with Stamford Alternator 12.5kVA (1year Warranty)
ELECTRICAL INDUSTRIAL, Electro, Generators, Generators & Power SolutionsYTO Diesel Engine Soundproof Diesel Generator with Stamford Alternator 12.5kVA (1year Warranty)
YTO Diesel Engine Co Ltd specializes in the design and manufacture of diesel generator engines since 1958. YTO has formed international partnerships with world leaders in their respective fields to maintain the latest technologies in their engines and produce a reliable, world-class product. The YTO engines are used internationally in offroad vehicles, tractors, construction machinery, agriculture, combine harvesters and more. The engines are high quality and reliability with a solid history in Africa. These engines include high temperature and low oil, water and fuel protection to protect against engine damage. Generator World is the sole-authorized distributor for YTO Engines in Sub Saharan Africa.
YTO engines are ideal for customers who require reliable performance and reliable power and cover a range of sizes from 10kva- 630kva whether you need prime or standby power- YTO is ready to match your power needs and provide a reliable source of power to ensure your productivity is not impacted. Whether you need a diesel generator for commercial or industrial use, these gensets are the perfect fit for the budget conscious consumer looking for standby power. By choosing one of these generators, you will still enjoy the same build quality and components youʼve come to expect from Generator World.
(2years Warranty of all the component, except the Main Alternator)
SKU: n/a -
ELECTRICAL INDUSTRIAL, Schneider, TRANSFORMER
Schneider 500kVA 33/400 CuCu Transformer
Features
Distribution transformers from Schneider Electric are available in ratings from 100kVA upto 4000kVA at voltages upto 36kV. They can be supplied in many types and styles, with standard industry fittings or bespoke design to the customers specific requirements. Choices available include:
- Type – Free Breathing (with or without conservator) or Hermetically sealed
- Style – Ground Mounted Cable Connected, Unit Substation or Bespoke to customer requirements
- Insulating Fluids – Mineral Oil or Midel 7131 Transformer Fluid
- Eco losses
- In addition, transformers can be supplied with directly mounted MV or LV switchgear to form an assembled package substation
Benefits
- Large choice of ratings, types and styles
- Bespoke or Standard Design
- Manufactured to specific customer requirements
- Available with MV & LV Switchgear
- Direct to Site Deliveries
- Ease of Installation
Applications
- Energy
- Infrastructure
- Commercial
SKU: n/a -
Low Voltage Products and Systems, SCHNEIDER SECTIONS
EZC100N4080 – Circuit breaker Easypact EZC100N – TMD – 80 A – 4 poles 3d
Low Voltage Products and Systems, SCHNEIDER SECTIONSEZC100N4080 – Circuit breaker Easypact EZC100N – TMD – 80 A – 4 poles 3d
Main range of product EasyPactproduct or component type Circuit breakerdevice short name Easypact EZC100Ncircuit breaker name Easypact EZC100Ndevice application Distributionpoles description 4Pprotected poles description 3tnetwork type DC
ACnetwork frequency 50/60 Hz[In] rated current 100 A at 40 °C[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2[Ue] rated operational voltage 550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2breaking capacity code Nbreaking capacity 10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
5 kA Icu at 125 V DC 1P conforming to IEC 60947-2
5 kA Icu at 250 V DC 2P conforming to IEC 60947-2
5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
15 kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2
18 kA Icu at 380…400 V AC 50/60 Hz conforming to IEC 60947-2[Ics] rated service breaking capacity 5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
2.5 kA at 125 V DC conforming to IEC 60947-2
2.5 kA at 250 V DC conforming to IEC 60947-2
2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
9 kA at 380…400 V AC 50/60 Hz conforming to IEC 60947-2
7.5 kA at 415 V AC 50/60 Hz conforming to IEC 60947-2suitability for isolation Yes conforming to IEC 60947-2utilisation category Category Atrip unit name TM-Dtrip unit technology Thermal-magnetictrip unit rating 80 A at 50 °Cprotection type Short-circuit protection
Overload protectionpollution degree 3 conforming to IEC 60947Complementary control type Togglemounting mode Fixedmounting support Backplateupside connection Frontdownside connection Frontmechanical durability 8500 cycleselectrical durability Category A: 1500 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2connection pitch 25 mmlocal signalling Positive contact indicationneutral protection setting Without protectionearth-leakage protection Withoutheight 130 mmwidth 100 mmdepth 60 mmSKU: n/a