EZC100F3100 – Circuit breaker Easypact EZC100F – TMD – 100 A – 3 poles 3d
range of product |
EasyPact
|
|
---|---|---|
product or component type |
Circuit breaker
|
|
device short name |
Easypact EZC100F
|
|
circuit breaker name |
Easypact EZC100F
|
|
device application |
Distribution
|
|
poles description |
3P
|
|
protected poles description |
3t
|
|
network type |
DC
AC |
|
network frequency |
50/60 Hz
|
|
[In] rated current |
100 A at 40 °C
|
|
[Ui] rated insulation voltage |
690Â V AC 50/60 Hz conforming to IEC 60947-2
|
|
[Uimp] rated impulse withstand voltage |
6Â kV conforming to IEC 60947-2
|
|
[Ue] rated operational voltage |
550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2 |
|
breaking capacity code |
F
|
|
breaking capacity |
25Â kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
25Â kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2 5Â kA Icu at 125 V DC 1P conforming to IEC 60947-2 5Â kA Icu at 250 V DC 2P conforming to IEC 60947-2 5Â kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 10Â kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 10Â kA Icu at 400…415 V AC 50/60 Hz conforming to IEC 60947-2 7.5Â kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Ics] rated service breaking capacity |
12.5Â kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2
12.5Â kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 2.5Â kA at 125 V DC conforming to IEC 60947-2 2.5Â kA at 250 V DC conforming to IEC 60947-2 2.5Â kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 5Â kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 5Â kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 3.75Â kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to IEC 60947-2
|
|
utilisation category |
Category A
|
|
trip unit name |
TM-D
|
|
trip unit technology |
Thermal-magnetic
|
|
trip unit rating |
100 A at 50 °C
|
|
protection type |
Short-circuit protection
Overload protection |
|
pollution degree |
3 conforming to IEC 60664-1
3 conforming to IEC 947-1 |
control type |
Toggle
|
|
---|---|---|
mounting mode |
Fixed
|
|
mounting support |
Backplate
|
|
upside connection |
Front
|
|
downside connection |
Front
|
|
mechanical durability |
8500Â cycles
|
|
electrical durability |
Category A: 1500Â cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
|
|
connection pitch |
25Â mm
|
|
local signalling |
Positive contact indication
|
|
neutral protection setting |
Without protection
|
|
earth-leakage protection |
Without
|
|
height |
130Â mm
|
|
width |
75Â mm
|
|
depth |
60Â mm
|
standards |
EN/IEC 60947-1
JIS C8201-2-2 GB/T 14048.2 EN/IEC 60947-2 |
|
---|---|---|
IP degree of protection |
IP20 conforming to IEC 60529
|
|
IK degree of protection |
IK07 conforming to IEC 62262
|
|
ambient air temperature for operation |
-25…70 °C
|
|
ambient air temperature for storage |
-35…85 °C
|
Unit Type of Package 1 |
PCE
|
|
---|---|---|
Number of Units in Package 1 |
1
|
|
Package 1 Weight |
786Â g
|
|
Package 1 Height |
9.5Â cm
|
|
Package 1 width |
8.5Â cm
|
|
Package 1 Length |
14Â cm
|
|
Unit Type of Package 2 |
S02
|
|
Number of Units in Package 2 |
12
|
|
Package 2 Weight |
9.887Â kg
|
|
Package 2 Height |
15Â cm
|
|
Package 2 width |
30Â cm
|
|
Package 2 Length |
40Â cm
|
|
Unit Type of Package 3 |
P06
|
|
Number of Units in Package 3 |
192
|
|
Package 3 Weight |
166.692Â kg
|
|
Package 3 Height |
80Â cm
|
|
Package 3 width |
80Â cm
|
|
Package 3 Length |
60Â cm
|
₦70,500.00
Compare-
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Easy9 miniature circuit breaker- 4P – 6 A – C curve – 6000 A – 400 V EZ9F56406
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSEasy9 miniature circuit breaker- 4P – 6 A – C curve – 6000 A – 400 V EZ9F56406
Main range Easy9device application Distributionproduct or component type Miniature circuit-breakerdevice short name Easy9 MCBPoles 4Pnumber of protected poles 4[In] rated current 6Â Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000Â A Icn at 220 V AC 50/60 Hz conforming to IEC 60898-1
6000Â A Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1suitability for isolation Yes conforming to IEC 60898-1Complementary network frequency 50 Hz[Ue] rated operational voltage 220 V AC 50/60 Hz
400 V AC 50/60 Hzmagnetic tripping limit 5…10 x In[Ics] rated service breaking capacity 6 kA 100 % x Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to IEC 60898-1[Uimp] rated impulse withstand voltage 4 kV conforming to IEC 60898-1contact position indicator Yescontrol type Togglelocal signalling Withoutmounting mode Clip-onmounting support DIN rail9 mm pitches 8height 81 mmwidth 72 mmdepth 66.5 mmcolour Grey (RAL 7035)mechanical durability 10000 cycleselectrical durability 4000 cyclesconnections – terminals Tunnel type terminal (top or bottom) 1…25 mm² rigid
Tunnel type terminal (top or bottom) 1…16 mm² flexibletightening torque 2 N.m top or bottomSKU: n/a -
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Switch disconnector iSW – 2P – 100 A – 415 V A9S65291 ISOLATOR SWITCH
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSSwitch disconnector iSW – 2P – 100 A – 415 V A9S65291 ISOLATOR SWITCH
Main range Acti 9product name Acti 9 iSWproduct or component type Switch disconnectordevice short name ISWdevice application Isolation
Controlpoles description 2Putilisation category AC-22Asuitability for isolation YesComplementary [Ie] rated operational current 100 A at 415 V AC 50/60 Hz[Ue] rated operational voltage 415 V AC 50/60 Hz[Icm] rated short-circuit making capacity 5 kA switch-disconnector alone[Icw] rated short-time withstand current 1500 A[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kVcontrol type Togglelocal signalling ON/OFF indicationcontact position indicator Yesmounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 4height 85 mmwidth 36 mmdepth 73 mmcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Tunnel type terminals (top or bottom) – <= 1 x 50 mm² – rigid
Tunnel type terminals (top or bottom) – <= 1 x 35 mm² – flexible
Tunnel type terminals (top or bottom) – <= 1 x 35 mm² – flexible with ferrulewire stripping length 9 mmtightening torque 3.5 N.mSKU: n/a -
Electro, SOCKETS, SOCKETS & SWITCHES
13AMP DOUBLE SOCKET WITH LIGHT – BG826
13A Rated
Easy to install, supplied with fixing screws and installation instructions
Angled in-line terminals with captive screws provide easy access for quick installation
Screw covers for sleek appearance
Twin earth fitted as standard to allow a double earth facility for installations requiring high integrity protective connection Ref. BS 7671:2008
LED power Indicator, reliable and low power
Minimum mounting box depth 25mm
Manufactured using high grade thermoset Urea which effectively inhibits the growth of infectious diseases, including MRSA, E-Coli, Salmonella and Klebsiella Pneumonia bacteria
SKU: n/a -
ACCESSORIES, ACCESSORIES, ELECTRICAL FITTINGS, Electro
Masterplug SURGE Extension Leads 6 Sockets
Perfect for the family home, this four or six socket, lead allows you to plug four or six items safely into one socket. With two or four metres of cable, this product protects valuable electrical equipment from surges and spikes. Power and surge indicators help to show that you are connected and protected.
- Wall fixing capability
- Non-rewireable
- Surge protected
- LED power indicator
- LED surge indicator
SKU: n/a -
There are no reviews yet.