Low Voltage Products and Systems, SCHNEIDER SECTIONS
EZC250N3125 Circuit breaker Easypact EZC250N – TMD – 125 A – 3 poles 3d
range of product |
EasyPact
|
|
---|---|---|
product or component type |
Circuit breaker
|
|
device short name |
Easypact EZC250N
|
|
circuit breaker name |
Easypact EZC250N
|
|
device application |
Distribution
|
|
poles description |
3P
|
|
protected poles description |
3t
|
|
network type |
AC
DC |
|
network frequency |
50/60 Hz
|
|
[In] rated current |
250 A at 40 °C
|
|
[Ui] rated insulation voltage |
690 V AC 50/60 Hz conforming to IEC 60947-2
|
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to IEC 60947-2
|
|
[Ue] rated operational voltage |
550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2 |
|
breaking capacity code |
N
|
|
breaking capacity |
20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 125 V DC 1P conforming to IEC 60947-2 20 kA Icu at 250 V DC 2P conforming to IEC 60947-2 25 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 400…415 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Ics] rated service breaking capacity |
10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
25 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 125 V DC conforming to IEC 60947-2 10 kA at 250 V DC conforming to IEC 60947-2 25 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 4 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to IEC 60947-2
|
|
utilisation category |
Category A
|
|
trip unit name |
TM-D
|
|
trip unit technology |
Thermal-magnetic
|
|
trip unit rating |
125 A at 50 °C
|
|
protection type |
Short-circuit protection
Overload protection |
|
pollution degree |
3 conforming to IEC 60664-1
3 conforming to IEC 947-1 |
control type |
Toggle
|
|
---|---|---|
mounting mode |
Fixed
|
|
mounting support |
Backplate
|
|
upside connection |
Front
|
|
downside connection |
Front
|
|
mechanical durability |
10000 cycles
|
|
electrical durability |
Category A: 5000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
|
|
connection pitch |
35 mm
|
|
local signalling |
Positive contact indication
|
|
neutral protection setting |
Without protection
|
|
earth-leakage protection |
Without
|
|
height |
165 mm
|
|
width |
105 mm
|
|
depth |
60 mm
|
₦56,000.00
Compare-
-
LIGHT SWITCHES & ELECTRICAL SOCKETS, SCHNEIDER SECTIONS
AvatarOn, 2 switches, 16AX, 250V, 2 way, White E8332L2_WE_G2
LIGHT SWITCHES & ELECTRICAL SOCKETS, SCHNEIDER SECTIONSAvatarOn, 2 switches, 16AX, 250V, 2 way, White E8332L2_WE_G2
Main product or component type Switchdevice application Controlload type Fluorescent lamp
Inductive
Resistive
Incandescent lampComplementary device presentation Complete productswitch function 1-pole 2-waynumber of gangs 2 gangsnumber of rocker 2connections – terminals Brass terminaldevice mounting Flush
Surfacewidth 86 mmheight 86 mmdepth 34.2 mmSKU: n/a -
-
CHANGEOVER SWITCHES, Electro, GEAR SWITCHES & CHANGEOVER
ABB CHANGEOVER SWITCH 800A with Enclosure
-
-
-
- Long Description:
- Including a black plastic IP65 I-0-II pistol type handle (see the table below), shaft and bolt set for the cable connection. Handle not padlockable and no door interlocking. Operating angle 90° to achieve fast switching. Minimum OFF-time between transfer from I-II or II-I is 20 ms.
Categories
- Products » Low Voltage Products and Systems » Switches » Change-over and Transfer Switches » Manual Change-over Switches
-
-
Technical
-
- Rated Operational Current AC-21A (Ie):
- (380 … 415 V) 800 A
(500 V) 800 A
(690 V) 800 A
-
- Rated Operational Current AC-22A (Ie):
- (380 … 415 V) 800 A
(500 V) 800 A
(690 V) 800 A
-
- Rated Operational Current AC-23A (Ie):
- (380 … 415 V) 800 A
(500 V) 800 A
(690 V) 800 A
-
- Rated Operational Current AC-31B (Ie):
- (380 … 415 V) 800 A
-
- Rated Operational Current AC-33B (Ie):
- (380 … 415 V) 800 A
-
- Rated Operational Power AC-23A (Pe):
- (380 … 415 V) 450 kW
(500 V) 560 kW
(690 V) 800 kW
-
- Conventional Free-air Thermal Current (Ith):
- q = 40 °C 800 A
-
- Conventional Thermal Current (Ithe):
- Fully Enclosed 800 A
-
- Rated Impulse Withstand Voltage (Uimp):
- 12 kV
-
- Rated Insulation Voltage (Ui):
- 1000 V
-
- Rated Operational Voltage:
- 1000 V
-
- Rated Short-time Withstand Current (Icw):
- for 1 s 20 kiloampere rms
-
- Power Loss:
- 40 W
SKU: n/a -
-
Low Voltage Products and Systems, SCHNEIDER SECTIONS
EZC100N4060 Circuit breaker Easypact EZC100N – TMD – 60 A – 4 poles 3d
Low Voltage Products and Systems, SCHNEIDER SECTIONSEZC100N4060 Circuit breaker Easypact EZC100N – TMD – 60 A – 4 poles 3d
Main range of product EasyPactproduct or component type Circuit breakerdevice short name Easypact EZC100Ncircuit breaker name Easypact EZC100Ndevice application Distributionpoles description 4Pprotected poles description 3tnetwork type DC
ACnetwork frequency 50/60 Hz[In] rated current 100 A at 40 °C[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2[Ue] rated operational voltage 550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2breaking capacity code Nbreaking capacity 10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
5 kA Icu at 125 V DC 1P conforming to IEC 60947-2
5 kA Icu at 250 V DC 2P conforming to IEC 60947-2
5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
15 kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2
18 kA Icu at 380…400 V AC 50/60 Hz conforming to IEC 60947-2[Ics] rated service breaking capacity 5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
2.5 kA at 125 V DC conforming to IEC 60947-2
2.5 kA at 250 V DC conforming to IEC 60947-2
2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
9 kA at 380…400 V AC 50/60 Hz conforming to IEC 60947-2
7.5 kA at 415 V AC 50/60 Hz conforming to IEC 60947-2suitability for isolation Yes conforming to IEC 60947-2utilisation category Category Atrip unit name TM-Dtrip unit technology Thermal-magnetictrip unit rating 60 A at 50 °Cprotection type Short-circuit protection
Overload protectionpollution degree 3 conforming to IEC 60947Complementary control type Togglemounting mode Fixedmounting support Backplateupside connection Frontdownside connection Frontmechanical durability 8500 cycleselectrical durability Category A: 1500 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2connection pitch 25 mmlocal signalling Positive contact indicationneutral protection setting Without protectionearth-leakage protection Withoutheight 130 mmwidth 100 mmdepth 60 mmSKU: n/a -
EARTH LEAKAGE PROTECTION DEVICES, ELECTRICAL INDUSTRIAL, Electro
Magnetic field meter LUTRON MG-3002
Lutron MG-3002 is an AC/DC magnetic meter.
Features:
Wide range, general purpose magnetic measurement for industrial, mechanical, electrical, laboratory field usage
Unit: G (Gauss), mT (milli Tesla)
DC range: 300.00 mT / 3000.0 mT
AC range: 150.00 mT / 1500.0 mT
N pole / S pole indicator
Use Hall sensor with automatic temp. compensation
RS232/USB computer interface
Auto shut off is available to save battery life
Power supply from batteries or DC 9V adapter inSKU: n/a