Electro, Low Voltage Products and Systems, SCHNEIDER SECTIONS
EZC250N3160 Circuit breaker Easypact EZC250N – TMD – 160 A – 3 poles 3d
range of product |
EasyPact
|
|
---|---|---|
product or component type |
Circuit breaker
|
|
device short name |
Easypact EZC250N
|
|
circuit breaker name |
Easypact EZC250N
|
|
device application |
Distribution
|
|
poles description |
3P
|
|
protected poles description |
3t
|
|
network type |
DC
AC |
|
network frequency |
50/60 Hz
|
|
[In] rated current |
250 A at 40 °C
|
|
[Ui] rated insulation voltage |
690Â V AC 50/60 Hz conforming to IEC 60947-2
|
|
[Uimp] rated impulse withstand voltage |
6Â kV conforming to IEC 60947-2
|
|
[Ue] rated operational voltage |
550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2 |
|
breaking capacity code |
N
|
|
breaking capacity |
20Â kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
50Â kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2 50Â kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2 20Â kA Icu at 125 V DC 1P conforming to IEC 60947-2 20Â kA Icu at 250 V DC 2P conforming to IEC 60947-2 25Â kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 25Â kA Icu at 400…415 V AC 50/60 Hz conforming to IEC 60947-2 8Â kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Ics] rated service breaking capacity |
10Â kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
25Â kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 10Â kA at 125 V DC conforming to IEC 60947-2 10Â kA at 250 V DC conforming to IEC 60947-2 25Â kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 4Â kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 12.5Â kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 12.5Â kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to IEC 60947-2
|
|
utilisation category |
Category A
|
|
trip unit name |
TM-D
|
|
trip unit technology |
Thermal-magnetic
|
|
trip unit rating |
160 A at 50 °C
|
|
protection type |
Overload protection
Short-circuit protection |
|
pollution degree |
3 conforming to IEC 60664-1
3 conforming to IEC 947-1 |
control type |
Toggle
|
|
---|---|---|
mounting mode |
Fixed
|
|
mounting support |
Backplate
|
|
upside connection |
Front
|
|
downside connection |
Front
|
|
mechanical durability |
10000Â cycles
|
|
electrical durability |
Category A: 5000Â cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
|
|
connection pitch |
35Â mm
|
|
local signalling |
Positive contact indication
|
|
neutral protection setting |
Without protection
|
|
earth-leakage protection |
Without
|
|
height |
165Â mm
|
|
width |
105Â mm
|
|
depth |
60Â mm
|
₦206,000.00
Compare-
Electro, SOCKETS & SWITCHES, SWITCHES
BG BRASS GEORGIAN LIGHT SWITCH PLATE – SINGLE 1 GANG 2 WAY
BG NBG12 Brass Georgian Light Switch Plate – Single 1 Gang 2 WayAT A GLANCE…- Top quality Brass finish – lightly lacquered to prevent finger marks
- Matching Brass rocker switch
- No visible plastic around switches
- Specification: 1 gang, 2 way, 10 amp (10AX)
- Requires a 16mm metal wall box
- Supplied with colour coded fixing screws
SKU: g7 -
-
Electro, SOCKETS, SOCKETS & SWITCHES
BG 2WAY DATA OUT LET – FBSRJ452
IDC Terminal connection
Easy to install, supplied with fixing screws and installation instructions
RJ45 Ethernet Socket
Screwless front plate clips on and off easily and has a sleek, flat profile
Moisture control gasket, prevents tarnishing from new plaster
Shuttered socket
ID window and colour matched shutter for each outlet
Supplied as a kit of Euro module components
Anti-fingerprint lacquer reduces unsightly fingerprints
Minimum mounting box depth 35mm
SKU: n/a -
-
Electro, Low Voltage Products and Systems, SCHNEIDER SECTIONS
EZC250N4160 Circuit breaker Easypact EZC250N – TMD – 160 A – 4 poles 3d
Electro, Low Voltage Products and Systems, SCHNEIDER SECTIONSEZC250N4160 Circuit breaker Easypact EZC250N – TMD – 160 A – 4 poles 3d
Main range of product EasyPact Product or component typee Circuit breaker Device short name Easypact EZC250N circuit breaker name Easypact EZC250N Device application Distribution Poles description 4P Protected poles description 3t Network type AC
DCNetwork frequency 50/60 Hz [In] rated current 160 A at 40 °C [Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2 [Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2 [Ue] rated operational voltage 550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2Breaking capacity code N Breaking capacity 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
20 kA Icu at 125 V DC 1P conforming to IEC 60947-2
20 kA Icu at 250 V DC 2P conforming to IEC 60947-2
8 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 380…415 V AC 50/60 Hz conforming to IEC 60947-2[Ics] rated service breaking capacity 10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
25 kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
10 kA at 125 V DC conforming to IEC 60947-2
10 kA at 250 V DC conforming to IEC 60947-2
4 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 380…415 V AC 50/60 Hz conforming to IEC 60947-2Suitability for isolation Yes conforming to IEC 60947-2 utilisation category Category A Trip unit name TM-D Trip unit technology Thermal-magnetic Trip unit rating 160 A at 50 °C Protection type Short-circuit protection
Overload protectionPollution degree 3 conforming to IEC 60947 Complementary control type Toggle Mounting mode Fixed mounting support Backplate Upside connection Front downside connection Front Mechanical durability 10000 cycles Electrical durability Category A: 5000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2 Connection pitch 35 mm local signalling Positive contact indication Neutral protection setting Without protection earth-leakage protection Without height 165 mm Width 140 mm Depth 60 mm Environment Standards JIS C8201-2-2
EN/IEC 60947-2
GB/T 14048.2
EN/IEC 60947-1IP degree of protection IP20 conforming to IEC 60529 IK degree of protection IK07 conforming to EN 50102 ambient air temperature for operation -25…70 °C Ambient air temperature for storage -35…85 °C Packing Units Unit Type of Package 1 PCE Number of Units in Package 1 1 Package 1 Height 11.0 cm Package 1 Width 14.5 cm Package 1 Length 18.5 cm Package 1 Weight 2.24 kg Unit Type of Package 2 S03 Number of Units in Package 2 6 Package 2 Height 30.0 cm Package 2 Width 30.0 cm Package 2 Length 40.0 cm Package 2 Weight 13.927 kg Unit Type of Package 3 PAL Number of Units in Package 3 96 Package 3 Height 72.0 cm Package 3 Width 125.0 cm Package 3 Length 96.0 cm Package 3 Weight 215.04 kg SKU: n/a -
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 1P 1A C Miniature Circuit breaker A9F44101
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 1P 1A C Miniature Circuit breaker A9F44101
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 1Pnumber of protected poles 1[In] rated current 1Â Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 50Â kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
50Â kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
50Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
15Â kA Icu at 12…48 V DC conforming to EN/IEC 60947-2
6Â kA Icu at 72 V DC conforming to EN/IEC 60947-2
6000Â A Icn at 240 V AC 50/60 Hz conforming to EN/IEC 60898-1utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 240 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 50Â kA 100Â % conforming to EN/IEC 60947-2 – 12…60 V AC 50/60 Hz
50Â kA 100Â % conforming to EN/IEC 60947-2 – 100…133 V AC 50/60 Hz
50Â kA 100Â % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
6000Â A 100Â % conforming to EN/IEC 60898-1 – 240 V AC 50/60 Hz
15Â kA 100Â % conforming to EN/IEC 60947-2 – 12…48 V DC
6 kA 100 % conforming to EN/IEC 60947-2 – 72 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 2height 85 mmwidth 18 mmdepth 78.5 mmnet weight 0.125 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockSKU: n/a
There are no reviews yet.