EZC250N4160 Circuit breaker Easypact EZC250N – TMD – 160 A – 4 poles 3d
range of product | EasyPact |
---|---|
Product or component typee | Circuit breaker |
Device short name | Easypact EZC250N |
circuit breaker name | Easypact EZC250N |
Device application | Distribution |
Poles description | 4P |
Protected poles description | 3t |
Network type | AC DC |
Network frequency | 50/60 Hz |
[In] rated current | 160 A at 40 °C |
[Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
[Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
[Ue] rated operational voltage | 550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2 |
Breaking capacity code | N |
Breaking capacity | 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 125 V DC 1P conforming to IEC 60947-2 20 kA Icu at 250 V DC 2P conforming to IEC 60947-2 8 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380…415 V AC 50/60 Hz conforming to IEC 60947-2 |
[Ics] rated service breaking capacity | 10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 125 V DC conforming to IEC 60947-2 10 kA at 250 V DC conforming to IEC 60947-2 4 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 380…415 V AC 50/60 Hz conforming to IEC 60947-2 |
Suitability for isolation | Yes conforming to IEC 60947-2 |
utilisation category | Category A |
Trip unit name | TM-D |
Trip unit technology | Thermal-magnetic |
Trip unit rating | 160 A at 50 °C |
Protection type | Short-circuit protection Overload protection |
Pollution degree | 3 conforming to IEC 60947 |
control type | Toggle |
---|---|
Mounting mode | Fixed |
mounting support | Backplate |
Upside connection | Front |
downside connection | Front |
Mechanical durability | 10000 cycles |
Electrical durability | Category A: 5000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2 |
Connection pitch | 35 mm |
local signalling | Positive contact indication |
Neutral protection setting | Without protection |
earth-leakage protection | Without |
height | 165 mm |
Width | 140 mm |
Depth | 60 mm |
Standards | JIS C8201-2-2 EN/IEC 60947-2 GB/T 14048.2 EN/IEC 60947-1 |
---|---|
IP degree of protection | IP20 conforming to IEC 60529 |
IK degree of protection | IK07 conforming to EN 50102 |
ambient air temperature for operation | -25…70 °C |
Ambient air temperature for storage | -35…85 °C |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 11.0 cm |
Package 1 Width | 14.5 cm |
Package 1 Length | 18.5 cm |
Package 1 Weight | 2.24 kg |
Unit Type of Package 2 | S03 |
Number of Units in Package 2 | 6 |
Package 2 Height | 30.0 cm |
Package 2 Width | 30.0 cm |
Package 2 Length | 40.0 cm |
Package 2 Weight | 13.927 kg |
Unit Type of Package 3 | PAL |
Number of Units in Package 3 | 96 |
Package 3 Height | 72.0 cm |
Package 3 Width | 125.0 cm |
Package 3 Length | 96.0 cm |
Package 3 Weight | 215.04 kg |
₦163,810.00
Compare-
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Miniature circuit-breaker, Acti9 iC60H, 2P, 2 A, C curve, 10000 A (IEC 60898-1), 70 kA (IEC 60947-2) A9F84202
Schneider Circuit Breakers, SCHNEIDER SECTIONSMiniature circuit-breaker, Acti9 iC60H, 2P, 2 A, C curve, 10000 A (IEC 60898-1), 70 kA (IEC 60947-2) A9F84202
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Hpoles description 2Pnumber of protected poles 2[In] rated current 2 Anetwork type AC
DCtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
15 kA Icu at <= 125 V DC conforming to EN/IEC 60947-2
70 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
70 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
70 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
70 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
70 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards IEC 60947-2
IEC 60898-1
EN 60947-2
EN 60898-1quality labels NFComplementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 70 kA 100 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
70 kA 100 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
70 kA 100 % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz
70 kA 100 % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz
7500 A 75 % conforming to EN 60898-1 – 400 V AC 50/60 Hz
7500 A 75 % conforming to IEC 60898-1 – 400 V AC 50/60 Hz
70 kA 100 % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz
70 kA 100 % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz
50 kA 100 % conforming to EN 60947-2 – 440 V AC 50/60 Hz
50 kA 100 % conforming to IEC 60947-2 – 440 V AC 50/60 Hz
15 kA 100 % conforming to IEC 60947-2 – 72…125 V DC
15 kA 100 % conforming to EN 60947-2 – 72…125 V DClimitation class 3 conforming to EN 60898-1
3 conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 4height 85 mmwidth 36 mmdepth 78.5 mmnet weight 0.25 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
CEILING LIGHTS, ELECTRICAL FITTINGS, HOME&OFFICE LIGHTING
Philip LED Down Light Surface-mounted SmartBright 23watt Philips
CEILING LIGHTS, ELECTRICAL FITTINGS, HOME&OFFICE LIGHTINGPhilip LED Down Light Surface-mounted SmartBright 23watt Philips
Benefits
• Reliability and safety: meets national and international regulation
• Energy saving: High system efficacy with lower power consumption
• Diversity: One stop shopping with multiple choices of recess round, square as well
as surface-mount to fit your dedicated applications
• Easy to install with slim designFeatures
• Long life time: 20Khrs (L70B50@25°C)
• System efficiency: up to 85lm/W
• One family offers recess round, square and surface mount options
• Slim design: 33mm housing body heightApplication
• Retail
• Office
• ResidentialSKU: n/a -
-
Electro, LED LIGHTS, LIGHTING, OUTDOOR LIGHTS
Philip SmartBright G2 LED Floodlight BVP151 LED200/CW 220-240V 200W AWB CE Philips
Electro, LED LIGHTS, LIGHTING, OUTDOOR LIGHTSPhilip SmartBright G2 LED Floodlight BVP151 LED200/CW 220-240V 200W AWB CE Philips
SmartBright G2 LED Floodlight
BVP151 LED200/CW 220-240V 200W AWB CE
SmartBright G2 LED Floodlight delivers high lumen efficacy, with long lifetime and reliable design. Asymmetric optical distribution improves light effect. The product is an ideal solution for most floodlight applications.
Initial Performance (IEC Compliant)
Initial luminous flux (system flux) – 20000 lm
Luminous flux tolerance – +/-10%
Initial LED luminaire efficacy – 100 lm/W
Init. Corr. Color Temperature – 5700 K
Init. Color Rendering Index – 80
Initial input power – 200 W
Power consumption tolerance – +/-10%SKU: n/a -
ELECTRICAL INDUSTRIAL, TRANSFORMER
MEKSAN Transformer 100kVA 11/415kV
Meksan Transformer manufacture distribution and power transformer from 50 kVA up to 50 MVA. Our products are produced in accordance with the TS 267 and the IEC60076 standards. Our production is documented with the TSE (Türkish Standard Institue) standards confortmity, ISO 9001:2000 quality system and ISO 14001 environmental management system certificates.
SKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Switch disconnector iSW – 3P – 100 A – 415 V A9S65391
Main range Acti 9product name Acti 9 iSWproduct or component type Switch disconnectordevice short name ISWdevice application Control
Isolationpoles description 3Putilisation category AC-22Asuitability for isolation YesComplementary [Ie] rated operational current 100 A at 415 V AC 50/60 Hz[Ue] rated operational voltage 415 V AC 50/60 Hz[Icm] rated short-circuit making capacity 5 kA switch-disconnector alone[Icw] rated short-time withstand current 1500 A[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kVcontrol type Togglelocal signalling ON/OFF indicationcontact position indicator Yesmounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 6height 85 mmwidth 54 mmdepth 73 mmcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Tunnel type terminals (top or bottom) – <= 1 x 50 mm² – rigid
Tunnel type terminals (top or bottom) – <= 1 x 35 mm² – flexible
Tunnel type terminals (top or bottom) – <= 1 x 35 mm² – flexible with ferrulewire stripping length 9 mmtightening torque 3.5 N.mEnvironment standards IEC 60947-3
EN 60947-3IP degree of protection IP20pollution degree 3tropicalisation 2relative humidity 95 % at 55 °Cambient air temperature for operation -25…60 °Cambient air temperature for storage -40…85 °CSKU: n/a
There are no reviews yet.