EZC250N4250 Circuit breaker Easypact EZC250N – TMD – 250 A – 4 poles 3d
Out of stock
Main
Range of product EasyPact
Product or component type Circuit breaker
Device short name Easypact EZC250N
Circuit breaker name Easypact EZC250N
Device application Distribution
Poles description 4P
Protected poles description 3t
Network type AC
DC
Network frequency 50/60 Hz
[In] rated current 250 A at 40 °C
[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2
[Ue] rated operational voltage 550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2
Breaking capacity code N
Breaking capacity 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
20 kA Icu at 125 V DC 1P conforming to IEC 60947-2
20 kA Icu at 250 V DC 2P conforming to IEC 60947-2
8 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 380…415 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity 10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
25 kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
10 kA at 125 V DC conforming to IEC 60947-2
10 kA at 250 V DC conforming to IEC 60947-2
4 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 380…415 V AC 50/60 Hz conforming to IEC 60947-2
Suitability for isolation Yes conforming to IEC 60947-2
Utilisation category Category A
₦210,000.00
Out of stock
Compare-
ELECTRICAL FITTINGS, Electro, HOME&OFFICE LIGHTING, LED LIGHTS, LIGHTING, OUTDOOR FITTINGS, OUTDOOR LIGHTS, SOLAR POWERED
LED All in One Solar Street Light 5eyes
ELECTRICAL FITTINGS, Electro, HOME&OFFICE LIGHTING, LED LIGHTS, LIGHTING, OUTDOOR FITTINGS, OUTDOOR LIGHTS, SOLAR POWEREDLED All in One Solar Street Light 5eyes
- High-efficiency monocrystalline solar panel with fast charging and longer lifespan
- Environmental friendly long-life Po4 Batteries with overcharge and over discharge protection, solar and more reliable
- Built-in battery indicator light to check the battery capacity
- High-efficiency LED chip for working over than 20,000 hours lighting
SKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Miniature circuit-breaker, Acti9 iC60H, 2P, 63 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84263
Schneider Circuit Breakers, SCHNEIDER SECTIONSMiniature circuit-breaker, Acti9 iC60H, 2P, 63 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84263
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Hpoles description 2Pnumber of protected poles 2[In] rated current 63 Anetwork type DC
ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
42 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
30 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at <= 125 V DC conforming to EN/IEC 60947-2
42 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards IEC 60947-2
IEC 60898-1
EN 60947-2
EN 60898-1Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 15 kA 50 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 50 % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz
5 kA 50 % conforming to EN 60947-2 – 440 V AC 50/60 Hz
15 kA 50 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 50 % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz
5 kA 50 % conforming to IEC 60947-2 – 440 V AC 50/60 Hz
7500 A 75 % conforming to EN 60898-1 – 400 V AC 50/60 Hz
7500 A 75 % conforming to IEC 60898-1 – 400 V AC 50/60 Hz
21 kA 50 % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz
21 kA 50 % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz
15 kA 100 % conforming to IEC 60947-2 – 72…125 V DC
15 kA 100 % conforming to EN 60947-2 – 72…125 V DC[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 4height 85 mmwidth 36 mmdepth 78.5 mmnet weight 0.25 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 3.5 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
LIGHT SWITCHES & ELECTRICAL SOCKETS
1 Gang 350VA, 50Hz Full-Flat Universal Dimmer with LED, White E8431EPD4_WE
LIGHT SWITCHES & ELECTRICAL SOCKETS1 Gang 350VA, 50Hz Full-Flat Universal Dimmer with LED, White E8431EPD4_WE
Main product or component type Dimmerlocal signalling On: indicator light, LED (amber)
Off: indicator light, LED (blue)additional information With memory push[Ue] rated operational voltage 220…240 V AC 50 Hzmaterial Brass: metal parts
Polycarbonate: plastic part
Steel: metal partscover frame colour tint WhiteComplementary wiring device mounting Flush
Surfaceclamping connection capacity 2 x 4 mm² for solid cable(s)
2 x 4 mm² for stranded cable(s)
3 x 2.5 mm² for solid cable(s)
3 x 2.5 mm² for stranded cable(s)rated operational power in VA 350 VAnumber of gangs 1 gangload type LV halogen
Incandescent lampembedding depth 6 mmwidth 87 mmheight 87 mmdepth 35 mmSKU: n/a -
CABLE AND CABLE MANAGEMENT, Electro, SINGLE CORE WIRE
Doncaster Cables 4mm Single Core – Black
Product Description
Manufactured to BS 6004:2012 Table 3
Annealed Stranded Copper Conductor / PVC Insulated / PVC Sheathed. 300/500V
Designed for use in light industrial and domestic wiring. These cables are particularly suited for installation as meter tails and are intended for fixed installation in dry or damp premises.
These cables can be installed in conduit, in cable trunking and in cable ducting. Or where there is deemed little risk of mechanical damage these cables can be clipped direct, on cable tray, embedded or in free air. These cables are not intended to be laid underground.
Product Details
Harmonisation Code Nominal Cross Sectional Area of Conductor (mm2) Nominal Stranding of Conductor (mm) Nominal Radial Thickness of insulation (mm) Nominal Radial Thickness of sheath (mm) Overall Diameter Lower Limit (mm) Overall Diameter Upper Limit (mm) Approximate Weight(kg/km) National Type 1.0 1 / 1.13 0.6 0.8 3.8 4.5 26 National Type 1.5 1 / 1.38 0.7 0.8 4.2 4.9 35 National Type 2.5 1 / 1.78 0.8 0.8 4.8 5.8 55 National Type 4.0 7 / 0.85 0.8 0.9 5.4 6.8 75 National Type 6.0 7 / 1.04 0.8 0.9 6.0 7.4 95 National Type 10.0 7 / 1.35 1.0 0.9 7.2 8.8 155 National Type 16.0 7 / 1.70 1.0 1.0 8.4 10.5 225 National Type 25.0 7 / 2.14 1.2 1.1 10.0 12.5 340 National Type 35.0 7 / 2.52 1.2 1.1 11.0 13.5 445 SKU: n/a -
There are no reviews yet.