Schneider Circuit Breakers, SCHNEIDER SECTIONS
IC60H – miniature circuit breaker – 1P – 4A – C curve A9F84104
device application |
Distribution
|
|
---|---|---|
range |
Acti 9
|
|
product name |
Acti 9 iC60
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
IC60H
|
|
poles description |
1P
|
|
number of protected poles |
1
|
|
[In] rated current |
4Â A
|
|
network type |
DC
AC |
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
10000Â A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
15Â kA Icu at 60…72 V DC conforming to EN/IEC 60947-2 20Â kA Icu at 12…60 V DC conforming to EN/IEC 60947-2 70Â kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2 70Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 70Â kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
|
utilisation category |
Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to EN 60898-1
Yes conforming to EN 60947-2 Yes conforming to IEC 60898-1 Yes conforming to IEC 60947-2 |
|
standards |
IEC 60898-1
EN 60947-2 EN 60898-1 IEC 60947-2 |
network frequency |
50/60 Hz
|
|
---|---|---|
magnetic tripping limit |
8 x In +/- 20 %
|
|
[Ics] rated service breaking capacity |
70Â kA 100Â % conforming to EN 60947-2 – 12…60 V AC 50/60 Hz
70Â kA 100Â % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz 70Â kA 100Â % conforming to IEC 60947-2 – 12…60 V AC 50/60 Hz 70Â kA 100Â % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz 7500Â A 75Â % conforming to EN 60898-1 – 230 V AC 50/60 Hz 7500Â A 75Â % conforming to IEC 60898-1 – 230 V AC 50/60 Hz 70Â kA 100Â % conforming to IEC 60947-2 – 100…133 V AC 50/60 Hz 70Â kA 100Â % conforming to EN 60947-2 – 100…133 V AC 50/60 Hz 15Â kA 100Â % conforming to EN 60947-2 – 72 V DC 15Â kA 100Â % conforming to IEC 60947-2 – 72 V DC 20Â kA 100Â % conforming to EN 60947-2 – 12…60 V DC 20Â kA 100Â % conforming to IEC 60947-2 – 12…60 V DC |
|
limitation class |
3 conforming to EN 60898-1
3 conforming to IEC 60898-1 |
|
[Ui] rated insulation voltage |
500Â V AC 50/60 Hz conforming to EN 60947-2
500Â V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Uimp] rated impulse withstand voltage |
6Â kV conforming to EN 60947-2
6Â kV conforming to IEC 60947-2 |
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Trip indicator
|
|
mounting mode |
Fixed
|
|
mounting support |
DIN rail
|
|
comb busbar and distribution block compatibility |
Top or bottom: YES
|
|
9 mm pitches |
2
|
|
height |
85Â mm
|
|
width |
18Â mm
|
|
depth |
78.5Â mm
|
|
net weight |
0.215Â kg
|
|
colour |
White
|
|
mechanical durability |
20000Â cycles
|
|
electrical durability |
10000Â cycles
|
|
connections – terminals |
Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexible |
|
wire stripping length |
14Â mm for top or bottom connection
|
|
tightening torque |
2Â N.m top or bottom
|
|
earth-leakage protection |
Without
|
₦7,999.00
Compare-
-
ELECTRICAL INDUSTRIAL, Schneider, TRANSFORMER
Schneider 1000kVA 11/400 CuCu Transformer
Features
Distribution transformers from Schneider Electric are available in ratings from 100kVA upto 4000kVA at voltages upto 36kV. They can be supplied in many types and styles, with standard industry fittings or bespoke design to the customers specific requirements. Choices available include:
- Type – Free Breathing (with or without conservator) or Hermetically sealed
- Style – Ground Mounted Cable Connected, Unit Substation or Bespoke to customer requirements
- Insulating Fluids – Mineral Oil or Midel 7131 Transformer Fluid
- Eco losses
- In addition, transformers can be supplied with directly mounted MV or LV switchgear to form an assembled package substation
Benefits
- Large choice of ratings, types and styles
- Bespoke or Standard Design
- Manufactured to specific customer requirements
- Available with MV & LV Switchgear
- Direct to Site Deliveries
- Ease of Installation
Applications
- Energy
- Infrastructure
- Commercial
SKU: n/a -
Schneider "Consort Dado" Trunking, SCHNEIDER SECTIONS
CTJ105W Mita – Consort Dado – joint cover piece – 100 x 50 mm
Schneider "Consort Dado" Trunking, SCHNEIDER SECTIONSCTJ105W Mita – Consort Dado – joint cover piece – 100 x 50 mm
CTJ105W Mita – Consort Dado – joint cover piece – 100 x 50 mm
Main range of product Mitaproduct name Consort Dadoproduct or component type Joint cover piececolour tint Whitequantity per set Set of 2Complementary fixing mode Clip-onmaterial with surface finish UPVC (unplasticized polyvinyl chloride)SKU: n/a -
LIGHT SWITCHES & ELECTRICAL SOCKETS
GGBL7051BSSS Lisse – Telephone – 1 gang RJ12 Stainless Steel with Black Interior
LIGHT SWITCHES & ELECTRICAL SOCKETSGGBL7051BSSS Lisse – Telephone – 1 gang RJ12 Stainless Steel with Black Interior
Main range Lisseaesthetic name Screwless decoproduct or component type Data/telephone socketdevice presentation Complete producttelephone socket type RJ12colour tint Interior: black
Cover plate: stainless steelquantity per set Set of 1Complementary number of gangs 1 gangfixing mode Concealed screwsmaterial Stainless steeltype of packing Bagtype of installation Indoordepth 35Â mmwidth 87Â mmheight 87Â mmnet weight 0.101Â kgSKU: n/a -
SCHNEIDER SECTIONS, Schneider Thorsman Testmeters
Thorsman Voltage Detector Pen IMT23109
Main range Thorsmanproduct or component type Voltage testersupply 2 battery 1.5 V AAAComplementary local signalling Presence of voltage: LED
Presence of voltage: alarm sound indicatormeasurement voltage 5…1000 V ACnetwork frequency 50…400 Hzmeasurement category Category IV 1000 Vlanguage Norwegian
Finnish
English
Danish
Swedishheight 152Â mmwidth 32Â mmdepth 28Â mmSKU: n/a -
Low Voltage Products and Systems, SCHNEIDER SECTIONS
EZC100F3100 – Circuit breaker Easypact EZC100F – TMD – 100 A – 3 poles 3d
Low Voltage Products and Systems, SCHNEIDER SECTIONSEZC100F3100 – Circuit breaker Easypact EZC100F – TMD – 100 A – 3 poles 3d
Main range of product EasyPactproduct or component type Circuit breakerdevice short name Easypact EZC100Fcircuit breaker name Easypact EZC100Fdevice application Distributionpoles description 3Pprotected poles description 3tnetwork type DC
ACnetwork frequency 50/60 Hz[In] rated current 100 A at 40 °C[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2[Ue] rated operational voltage 550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2breaking capacity code Fbreaking capacity 25Â kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
25Â kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
5Â kA Icu at 125 V DC 1P conforming to IEC 60947-2
5Â kA Icu at 250 V DC 2P conforming to IEC 60947-2
5Â kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
10Â kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2
10Â kA Icu at 400…415 V AC 50/60 Hz conforming to IEC 60947-2
7.5Â kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2[Ics] rated service breaking capacity 12.5Â kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2
12.5Â kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2
2.5Â kA at 125 V DC conforming to IEC 60947-2
2.5Â kA at 250 V DC conforming to IEC 60947-2
2.5Â kA at 550 V AC 50/60 Hz conforming to IEC 60947-2
5Â kA at 380 V AC 50/60 Hz conforming to IEC 60947-2
5Â kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
3.75 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2suitability for isolation Yes conforming to IEC 60947-2utilisation category Category Atrip unit name TM-Dtrip unit technology Thermal-magnetictrip unit rating 100 A at 50 °Cprotection type Short-circuit protection
Overload protectionpollution degree 3 conforming to IEC 60664-1
3 conforming to IEC 947-1Complementary control type Togglemounting mode Fixedmounting support Backplateupside connection Frontdownside connection Frontmechanical durability 8500Â cycleselectrical durability Category A: 1500Â cycles 415 V AC 50/60 Hz conforming to IEC 60947-2connection pitch 25Â mmlocal signalling Positive contact indicationneutral protection setting Without protectionearth-leakage protection Withoutheight 130Â mmwidth 75Â mmdepth 60Â mmEnvironment standards EN/IEC 60947-1
JIS C8201-2-2
GB/T 14048.2
EN/IEC 60947-2IP degree of protection IP20 conforming to IEC 60529IK degree of protection IK07 conforming to IEC 62262ambient air temperature for operation -25…70 °Cambient air temperature for storage -35…85 °CPacking Units Unit Type of Package 1 PCENumber of Units in Package 1 1Package 1 Weight 786 gPackage 1 Height 9.5 cmPackage 1 width 8.5 cmPackage 1 Length 14 cmUnit Type of Package 2 S02Number of Units in Package 2 12Package 2 Weight 9.887 kgPackage 2 Height 15 cmPackage 2 width 30 cmPackage 2 Length 40 cmUnit Type of Package 3 P06Number of Units in Package 3 192Package 3 Weight 166.692 kgPackage 3 Height 80 cmPackage 3 width 80 cmPackage 3 Length 60 cmSKU: n/a