Schneider Circuit Breakers, SCHNEIDER SECTIONS
IC60H – miniature circuit breaker – 1P – 63A – C curve A9F84163
device application |
Distribution
|
|
---|---|---|
range |
Acti 9
|
|
product name |
Acti 9 iC60
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
IC60H
|
|
poles description |
1P
|
|
number of protected poles |
1
|
|
[In] rated current |
63 A
|
|
network type |
DC
AC |
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
10000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
15 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 42 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 60…72 V DC conforming to EN/IEC 60947-2 20 kA Icu at 12…60 V DC conforming to EN/IEC 60947-2 |
|
utilisation category |
Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to EN 60898-1
Yes conforming to EN 60947-2 Yes conforming to IEC 60898-1 Yes conforming to IEC 60947-2 |
|
standards |
EN 60947-2
EN 60898-1 IEC 60898-1 IEC 60947-2 |
network frequency |
50/60 Hz
|
|
---|---|---|
magnetic tripping limit |
8 x In +/- 20 %
|
|
[Ics] rated service breaking capacity |
21 kA 50 % conforming to EN 60947-2 – 12…60 V AC 50/60 Hz
7.5 kA 50 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz 21 kA 50 % conforming to IEC 60947-2 – 12…60 V AC 50/60 Hz 7.5 kA 50 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz 7500 A 75 % conforming to EN 60898-1 – 230 V AC 50/60 Hz 7500 A 75 % conforming to IEC 60898-1 – 230 V AC 50/60 Hz 15 kA 50 % conforming to IEC 60947-2 – 100…133 V AC 50/60 Hz 15 kA 50 % conforming to EN 60947-2 – 100…133 V AC 50/60 Hz 15 kA 100 % conforming to EN 60947-2 – 72 V DC 15 kA 100 % conforming to IEC 60947-2 – 72 V DC 20 kA 100 % conforming to EN 60947-2 – 12…60 V DC 20 kA 100 % conforming to IEC 60947-2 – 12…60 V DC |
|
[Ui] rated insulation voltage |
500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2 |
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Trip indicator
|
|
mounting mode |
Fixed
|
|
mounting support |
DIN rail
|
|
comb busbar and distribution block compatibility |
Top or bottom: YES
|
|
9 mm pitches |
2
|
|
height |
85 mm
|
|
width |
18 mm
|
|
depth |
78.5 mm
|
|
net weight |
0.215 kg
|
|
colour |
White
|
|
mechanical durability |
20000 cycles
|
|
electrical durability |
10000 cycles
|
|
connections – terminals |
Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexible |
|
wire stripping length |
14 mm for top or bottom connection
|
|
tightening torque |
3.5 N.m top or bottom
|
|
earth-leakage protection |
Without
|
₦4,999.00
Compare-
CIRCUIT BREAKERS
IC60N – miniature circuit breaker – 3P – 63A – C curve
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 3Pnumber of protected poles 3[In] rated current 63 Anetwork type DC
ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
36 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
20 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
36 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at <= 180 V DC conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards EN 60898-1
EN 60947-2
IEC 60898-1
IEC 60947-2Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 15 kA 75 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 75 % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz
4.5 kA 75 % conforming to EN 60947-2 – 440 V AC 50/60 Hz
15 kA 75 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 75 % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz
4.5 kA 75 % conforming to IEC 60947-2 – 440 V AC 50/60 Hz
27 kA 75 % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz
27 kA 75 % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz
6000 A 100 % conforming to EN 60898-1 – 400 V AC 50/60 Hz
6000 A 100 % conforming to IEC 60898-1 – 400 V AC 50/60 Hz
10 kA 100 % conforming to IEC 60947-2 – 125…180 V DC
10 kA 100 % conforming to EN 60947-2 – 125…180 V DC[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 6height 85 mmwidth 54 mmdepth 78.5 mmnet weight 0.375 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 3.5 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
-
DISTRIBUTION BOARDS, DISTRIBUTION BOARDS, Electro
Easy9 distribution board – 1P – 100A – 8 ways – fixed
DISTRIBUTION BOARDS, DISTRIBUTION BOARDS, ElectroEasy9 distribution board – 1P – 100A – 8 ways – fixed
Main range Easy9product or component type Enclosureenclosure type Distribution enclosureprovided equipment 1 x washer
Identification label
4 x screws
Removable front coverComplementary enclosure mounting Surface
FlushNb of horizontal rows 1number of plates 3 for plain platenetwork number of phases Single phasenumber of ways 8 waystype of rail DINcable entry 6 knock-outsType of door Plain door[In] rated current 100 Aenclosure material Powder coated steelwidth 362 mm outside:height 232 mm outside:depth 90 mm outside:colour Grey (RAL 7035)SKU: n/a -
Electro, SOCKETS & SWITCHES, SWITCHES
BG BRASS GEORGIAN LIGHT SWITCH PLATE – SINGLE 1 GANG 2 WAY
BG NBG12 Brass Georgian Light Switch Plate – Single 1 Gang 2 WayAT A GLANCE…- Top quality Brass finish – lightly lacquered to prevent finger marks
- Matching Brass rocker switch
- No visible plastic around switches
- Specification: 1 gang, 2 way, 10 amp (10AX)
- Requires a 16mm metal wall box
- Supplied with colour coded fixing screws
SKU: g7 -
LED LIGHTS, LIGHTING, OUTDOOR LIGHTS
VTAC LED Street Light SAMSUNG Chip 150W Grey Body 6000K
Product benefits
- Perfect replacement for traditional lights
- Saves 80% Electricity cost, Better Efficiency, Longer Lifespan
- Dedicated IP65 Sealed Optical Cavities
- Optically Optimized Glass Lenses
- Uniformity in Light Distribution – Maximizes Efficiency
- Fully Operational in Extreme Weather up to -20º Celsius
- Low maintenance & Low Power consumption
- Reduced CO² emissions
Applications
- Outdoor areas – streets, cross roads, tunnels, car parks, industrial facilities etc.
SKU: n/a -
There are no reviews yet.