IC60N – miniature circuit breaker – 3P – 63A – C curve
device application |
Distribution
|
|
---|---|---|
range |
Acti 9
|
|
product name |
Acti 9 iC60
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
IC60N
|
|
poles description |
3P
|
|
number of protected poles |
3
|
|
[In] rated current |
63Â A
|
|
network type |
DC
AC |
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
6000Â A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
36Â kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2 10Â kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2 20Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 6Â kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 36Â kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2 10Â kA Icu at <= 180 V DC conforming to EN/IEC 60947-2 |
|
utilisation category |
Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to EN 60898-1
Yes conforming to EN 60947-2 Yes conforming to IEC 60898-1 Yes conforming to IEC 60947-2 |
|
standards |
EN 60898-1
EN 60947-2 IEC 60898-1 IEC 60947-2 |
network frequency |
50/60 Hz
|
|
---|---|---|
magnetic tripping limit |
8 x In +/- 20 %
|
|
[Ics] rated service breaking capacity |
15Â kA 75Â % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
7.5Â kA 75Â % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz 4.5Â kA 75Â % conforming to EN 60947-2 – 440 V AC 50/60 Hz 15Â kA 75Â % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz 7.5Â kA 75Â % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz 4.5Â kA 75Â % conforming to IEC 60947-2 – 440 V AC 50/60 Hz 27Â kA 75Â % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz 27Â kA 75Â % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz 6000Â A 100Â % conforming to EN 60898-1 – 400 V AC 50/60 Hz 6000Â A 100Â % conforming to IEC 60898-1 – 400 V AC 50/60 Hz 10Â kA 100Â % conforming to IEC 60947-2 – 125…180 V DC 10Â kA 100Â % conforming to EN 60947-2 – 125…180 V DC |
|
[Ui] rated insulation voltage |
500Â V AC 50/60 Hz conforming to EN 60947-2
500Â V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Uimp] rated impulse withstand voltage |
6Â kV conforming to EN 60947-2
6Â kV conforming to IEC 60947-2 |
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Trip indicator
|
|
mounting mode |
Fixed
|
|
mounting support |
DIN rail
|
|
comb busbar and distribution block compatibility |
Top or bottom: YES
|
|
9 mm pitches |
6
|
|
height |
85Â mm
|
|
width |
54Â mm
|
|
depth |
78.5Â mm
|
|
net weight |
0.375Â kg
|
|
colour |
White
|
|
mechanical durability |
20000Â cycles
|
|
electrical durability |
10000Â cycles
|
|
connections – terminals |
Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexible |
|
wire stripping length |
14Â mm for top or bottom connection
|
|
tightening torque |
3.5Â N.m top or bottom
|
|
earth-leakage protection |
Separate block
|
₦16,000.00
Compare-
SOCKETS & SWITCHES, SWITCHES
Lisse – Plate Switch – 2 gang 2 way – 10AX Mocha Bronze with Black interior
SOCKETS & SWITCHES, SWITCHESLisse – Plate Switch – 2 gang 2 way – 10AX Mocha Bronze with Black interior
Main range Lisseaesthetic name Screwless decoproduct or component type Plate switchdevice presentation Complete productcolour tint Cover plate: mocha bronze
Interior: blackquantity per set Set of 10Complementary switch function 2-waycontrol type Rockernumber of gangs 2 gangsdevice mounting Wall mountedrated current 10 AX at 230 V ACfixing mode Concealed screwsconnections – terminals Screw terminalsmaterial Stainless steelsurface finish Matttype of packing Boxheight 87Â mmwidth 87Â mmdepth 25Â mmnet weight 0.122Â kgEnvironment standards BS EN 60669-1IP degree of protection IP20Packing Units Unit Type of Package 1 PCENumber of Units in Package 1 1Package 1 Weight 155Â gPackage 1 Height 3.3Â cmPackage 1 width 9.2Â cmPackage 1 Length 9.3Â cmOffer Sustainability EU RoHS Directive Compliant
EU RoHS DeclarationMercury free YesRoHS exemption information China RoHS Regulation China RoHS declaration
Product out of China RoHS scope. Substance declaration for your informationSKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Miniature circuit-breaker, Acti9 iC60H, 1P, 6 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84106
Schneider Circuit Breakers, SCHNEIDER SECTIONSMiniature circuit-breaker, Acti9 iC60H, 1P, 6 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84106
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Hpoles description 1Pnumber of protected poles 1[In] rated current 6Â Anetwork type AC
DCtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000Â A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
15Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
42Â kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
30Â kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
15Â kA Icu at 60…72 V DC conforming to EN/IEC 60947-2
20Â kA Icu at 12…60 V DC conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards EN 60898-1
IEC 60947-2
IEC 60898-1
EN 60947-2Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 21Â kA 50Â % conforming to EN 60947-2 – 12…60 V AC 50/60 Hz
7.5Â kA 50Â % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
21Â kA 50Â % conforming to IEC 60947-2 – 12…60 V AC 50/60 Hz
7.5Â kA 50Â % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7500Â A 75Â % conforming to EN 60898-1 – 230 V AC 50/60 Hz
7500Â A 75Â % conforming to IEC 60898-1 – 230 V AC 50/60 Hz
15Â kA 50Â % conforming to IEC 60947-2 – 100…133 V AC 50/60 Hz
15Â kA 50Â % conforming to EN 60947-2 – 100…133 V AC 50/60 Hz
15Â kA 100Â % conforming to EN 60947-2 – 72 V DC
15Â kA 100Â % conforming to IEC 60947-2 – 72 V DC
20Â kA 100Â % conforming to EN 60947-2 – 12…60 V DC
20Â kA 100Â % conforming to IEC 60947-2 – 12…60 V DClimitation class 3 conforming to EN 60898-1
3 conforming to IEC 60898-1[Ui] rated insulation voltage 500Â V AC 50/60 Hz conforming to EN 60947-2
500Â V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6Â kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 2height 85 mmwidth 18 mmdepth 78.5 mmnet weight 0.215 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection WithoutSKU: n/a -
CHINT
CHINT NDK Control Transformer
NDK Control Transformer
Application: for control power supply of apparatus, partial illumination and indicator light of machine tool and other mechanic equipments.
Features:
The transformer is characterized by excellent performances reliable operation, compact design, safe wiring, and wide application etc
SKU: n/a -
LIGHT SWITCHES & ELECTRICAL SOCKETS, SCHNEIDER SECTIONS
ZENCELO 1 Gang Data Outlet Category 5e with Integrated Shutter,Silver Bronze E8431RJ_5_SZ
LIGHT SWITCHES & ELECTRICAL SOCKETS, SCHNEIDER SECTIONSZENCELO 1 Gang Data Outlet Category 5e with Integrated Shutter,Silver Bronze E8431RJ_5_SZ
Main range ZENceloproduct or component type Data socketdevice application Communicationcolour tint Silver bronzeComplementary rated current 1.5 Acommunication network category Data: 5einsulation resistance >= 200 MOhmcontact resistance 1 µOhmnumber of gangs 1 gangminimum return loss 23 dBAWG gauge AWG 26…AWG 22 (4 twisted pair cables)contacts material Housing: PC
Contact: phosphor bronze with gold plating
IDC contact: phosphor bronze with nickel platingmaterial Polycarbonate: plastic partdevice mounting Surface
Flushwidth 87Â mmheight 87Â mmdepth 36Â mmSKU: n/a -
Electro, Low Voltage Products and Systems, SCHNEIDER SECTIONS
EZC250N4250 Circuit breaker Easypact EZC250N – TMD – 250 A – 4 poles 3d
Electro, Low Voltage Products and Systems, SCHNEIDER SECTIONSEZC250N4250 Circuit breaker Easypact EZC250N – TMD – 250 A – 4 poles 3d
Main
Range of product EasyPact
Product or component type Circuit breaker
Device short name Easypact EZC250N
Circuit breaker name Easypact EZC250N
Device application Distribution
Poles description 4P
Protected poles description 3t
Network type AC
DC
Network frequency 50/60 Hz
[In] rated current 250 A at 40 °C
[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2
[Ue] rated operational voltage 550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2
Breaking capacity code N
Breaking capacity 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
20 kA Icu at 125 V DC 1P conforming to IEC 60947-2
20 kA Icu at 250 V DC 2P conforming to IEC 60947-2
8 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 380…415 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity 10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
25 kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
10 kA at 125 V DC conforming to IEC 60947-2
10 kA at 250 V DC conforming to IEC 60947-2
4 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 380…415 V AC 50/60 Hz conforming to IEC 60947-2
Suitability for isolation Yes conforming to IEC 60947-2
Utilisation category Category ASKU: n/a -
ELECTRICAL INDUSTRIAL, TRANSFORMER
BETA 500KVA/11/0.415V COPPER/COPPER WINDING TRANSFORMER
Produced within a power range between 10 – 100.000 kVA , up to 170 kV high voltage level, three phase or single phase, oil immersed, ONAN, ONAF, OFWF, with Off-Load or On-Load Tap Changer, used both external and internal.
Dimensions of transformer conservator are determined and designed after several heat calculations of the oil stored in expansion tank and oil level changes by heat.
Being open to atmosphere, oil pressure changes continuously in Conservator Type Transformers due to thermal effects and exchange of air is dehumidified via air breather silicagel.SKU: n/a
There are no reviews yet.