Schneider Circuit Breakers, SCHNEIDER SECTIONS
Miniature circuit-breaker, Acti9 iC60H, 1P, 10 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84110
device application |
Distribution
|
|
---|---|---|
range |
Acti 9
|
|
product name |
Acti 9 iC60
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
IC60H
|
|
poles description |
1P
|
|
number of protected poles |
1
|
|
[In] rated current |
10 A
|
|
network type |
DC
AC |
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
10000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
15 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 42 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 60…72 V DC conforming to EN/IEC 60947-2 20 kA Icu at 12…60 V DC conforming to EN/IEC 60947-2 |
|
utilisation category |
Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to EN 60898-1
Yes conforming to EN 60947-2 Yes conforming to IEC 60898-1 Yes conforming to IEC 60947-2 |
|
standards |
EN 60898-1
EN 60947-2 IEC 60898-1 IEC 60947-2 |
network frequency |
50/60 Hz
|
|
---|---|---|
magnetic tripping limit |
8 x In +/- 20 %
|
|
[Ics] rated service breaking capacity |
21 kA 50 % conforming to EN 60947-2 – 12…60 V AC 50/60 Hz
7.5 kA 50 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz 21 kA 50 % conforming to IEC 60947-2 – 12…60 V AC 50/60 Hz 7.5 kA 50 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz 7500 A 75 % conforming to EN 60898-1 – 230 V AC 50/60 Hz 7500 A 75 % conforming to IEC 60898-1 – 230 V AC 50/60 Hz 15 kA 50 % conforming to IEC 60947-2 – 100…133 V AC 50/60 Hz 15 kA 50 % conforming to EN 60947-2 – 100…133 V AC 50/60 Hz 15 kA 100 % conforming to EN 60947-2 – 72 V DC 15 kA 100 % conforming to IEC 60947-2 – 72 V DC 20 kA 100 % conforming to EN 60947-2 – 12…60 V DC 20 kA 100 % conforming to IEC 60947-2 – 12…60 V DC |
|
limitation class |
3 conforming to EN 60898-1
3 conforming to IEC 60898-1 |
|
[Ui] rated insulation voltage |
500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2 |
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Trip indicator
|
|
mounting mode |
Fixed
|
|
mounting support |
DIN rail
|
|
comb busbar and distribution block compatibility |
Top or bottom: YES
|
|
9 mm pitches |
2
|
|
height |
85 mm
|
|
width |
18 mm
|
|
depth |
78.5 mm
|
|
net weight |
0.215 kg
|
|
colour |
White
|
|
mechanical durability |
20000 cycles
|
|
electrical durability |
10000 cycles
|
|
connections – terminals |
Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexible |
|
wire stripping length |
14 mm for top or bottom connection
|
|
tightening torque |
2 N.m top or bottom
|
|
earth-leakage protection |
Without
|
IP degree of protection |
IP20 conforming to IEC 60529
IP20 conforming to EN 60529 |
|
---|---|---|
pollution degree |
3 conforming to EN 60947-2
3 conforming to IEC 60947-2 |
|
overvoltage category |
IV
|
|
tropicalisation |
2 conforming to IEC 60068-1
|
|
relative humidity |
95 % at 55 °C
|
|
operating altitude |
0…2000 m
|
|
ambient air temperature for operation |
-35…70 °C
|
|
ambient air temperature for storage |
-40…85 °C
|
₦4,999.00
Compare-
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Easy9 switch disconnector – 2P – 125 A – 400 V EZ9S16292
Schneider Circuit Breakers, SCHNEIDER SECTIONSEasy9 switch disconnector – 2P – 125 A – 400 V EZ9S16292
Main range Easy9product or component type Switchdevice short name Easy9 switchswitch application DistributionPoles 2Putilisation category AC-22Asuitability for isolation YesComplementary [Ie] rated operational current 125 A at 400 V 50/60 Hz[Ue] rated operational voltage 400 V AC 50/60 Hz[Icm] rated short-circuit making capacity 1.875 kA[Icw] rated short-time withstand current 1.5 kA during 1 s[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 4 kVcontrol type Togglelocal signalling ON/OFF indicationcontact position indicator Yesmounting mode Clip-onmounting support DIN rail9 mm pitches 4height 81 mmwidth 36 mmdepth 66.5 mmcolour Greymechanical durability 7000 cycleselectrical durability 1000 cyclesconnections – terminals Tunnel type terminal (top or bottom) 1…50 mm² rigid
Tunnel type terminal (top or bottom) 1…35 mm² flexibletightening torque 3.5 N.mSKU: n/a -
CIRCUIT BREAKERS, DISTRIBUTION BOARDS
Easy9 miniature circuit breaker- 2P – 25 A – C curve – 6000 A – 230 V
CIRCUIT BREAKERS, DISTRIBUTION BOARDSEasy9 miniature circuit breaker- 2P – 25 A – C curve – 6000 A – 230 V
Schneider Electric Easy9 Miniature Circuit Breaker- 2P – 6 A – C Curve – 6000 A – 230 V
Main range Easy9device application Distributionproduct or component type Miniature circuit-breakerdevice short name Easy9 MCBPoles 2Pnumber of protected poles 2[In] rated current 25 Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000 A Icn at 220 V AC 50/60 Hz conforming to IEC 60898-1
6000 A Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1suitability for isolation Yes conforming to IEC 60898-1Complementary network frequency 50/60 Hz[Ue] rated operational voltage 220 V AC 50/60 Hz
400 V AC 50/60 Hzmagnetic tripping limit 5…10 x In[Ics] rated service breaking capacity 6 kA 100 % x Icn at 230 V AC 50/60 Hz conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to IEC 60898-1[Uimp] rated impulse withstand voltage 4 kV conforming to IEC 60898-1contact position indicator Yescontrol type Togglelocal signalling Withoutmounting mode Clip-onmounting support DIN rail9 mm pitches 4height 81 mmwidth 36 mmdepth 66.5 mmcolour Grey (RAL 7035)mechanical durability 10000 cycleselectrical durability 4000 cyclesconnections – terminals Tunnel type terminal (top or bottom) 1…25 mm² rigid
Tunnel type terminal (top or bottom) 1…16 mm² flexibletightening torque 2 N.m top or bottomearth-leakage protection WithoutEnvironment standards IEC 60898-1product certifications CEIP degree of protection IP20 conforming to IEC 60529pollution degree 2tropicalisation 2relative humidity 95 % at -5…60 °Cambient air temperature for operation -5…60 °Cambient air temperature for storage -40…85 °CSKU: n/a -
CHINT
CHINT NXB63 Miniature Circuit Breaker 2pole
Overload protection, short circuit protection and isolation. It is widely used in building power distribution, industrial power distribution, as well as control and protection for a variety of equipment with operating current not exceeding 125A.
DESCRIPTION
- Compliance standard : IEC60898-1
- Rated Current : 6~63A Rated Voltage (V~) : 240/415
- Rated Frequency : 50/60 Hz
SKU: n/a -
CHINT
CHINT NU6-Ⅱ Low-voltage Surge Arrester 15 – 40A
NU6-Ⅱ Low-voltage Surge Arrester
- Certificates: international certificates are under proceeding;
- Number of poles: 1, 2,3, 4;
- Electric ratings: 230/400V, AC50Hz;
- Application: Protect electric system and on-loading electrical apparatus from thunder and instantaneous over-voltage;
- Standard: IEC 61643-1, EN 61643-11
SKU: n/a -
-
Electro, LIGHT SWITCHES & ELECTRICAL SOCKETS, Uncategorized
Lisse – White moulded – blank plate – 1 gang – matt white GGBL8010
Electro, LIGHT SWITCHES & ELECTRICAL SOCKETS, UncategorizedLisse – White moulded – blank plate – 1 gang – matt white GGBL8010
Main range Lisseaesthetic name White mouldedproduct or component type Blank platedevice presentation Complete productcolour tint Whitequantity per set Set of 10Complementary fixing mode By screwsnumber of gangs 1 gangmaterial Urea (carbamide)surface finish Matttype of packing Cartonheight 87 mmwidth 87 mmdepth 9 mmnet weight 0.041 kgSKU: n/a
There are no reviews yet.