Miniature circuit breaker, Easy9, 1P, 10 A, C curve, 6000 A
range |
Easy9
|
|
---|---|---|
device application |
Distribution
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
Easy9 MCB
|
|
Poles |
1P
|
|
number of protected poles |
1
|
|
[In] rated current |
10 A
|
|
network type |
AC
|
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
6000 A Icn at 230 V AC 50/60 Hz conforming to IEC 60898-1
10000 A Icn at 127 V AC 50/60 Hz conforming to IEC 60898-1 |
|
suitability for isolation |
Yes conforming to IEC 60898-1
|
network frequency |
50 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
230 V AC 50 Hz
127 V AC 50 Hz |
|
magnetic tripping limit |
5…10 x In
|
|
[Ics] rated service breaking capacity |
6 kA 100 % x Icn at 230 V AC 50/60 Hz conforming to IEC 60898-1
|
|
[Ui] rated insulation voltage |
500 V AC 50/60 Hz conforming to IEC 60898-1
|
|
[Uimp] rated impulse withstand voltage |
4 kV conforming to IEC 60898-1
|
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Without
|
|
mounting mode |
Clip-on
|
|
mounting support |
DIN rail
|
|
9 mm pitches |
2
|
|
height |
81 mm
|
|
width |
18 mm
|
|
depth |
66.5 mm
|
|
colour |
Grey (RAL 7035)
|
|
mechanical durability |
10000 cycles
|
|
electrical durability |
4000 cycles
|
|
connections – terminals |
Tunnel type terminal (top or bottom) 1…25 mm² rigid
Tunnel type terminal (top or bottom) 1…16 mm² flexible |
|
tightening torque |
2 N.m top or bottom
|
₦5,500.00
Compare-
LIGHT SWITCHES & ELECTRICAL SOCKETS
115/240V Shaver Unit KBT727V
Main product or component type Shaver socketdevice short name KBTdevice presentation Complete mechanismComplementary number of gangs 2 gangsColour tint Whitematerial Polycarbonate: grid plate
Polycarbonate: surround
Polycarbonate: baseprojecting depth 8 mmdevice mounting Flushmounting support Wall mountedfixing mode By screw M3.5fixing center 120.6 mmembedding depth 47 mminput voltage 240 V AC
ACoutput voltage 115 V ACnetwork frequency 50 Hzconnections – terminals Pillar terminalterminal identifier L
N
Etightening torque 0.4 N.mclamping connection capacity 2.5 mm²width 146 mmheight 86 mmSKU: n/a -
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Easy9 miniature circuit breaker- 3P – 16 A – C curve – 6000 A – 400 V EZ9F56316
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSEasy9 miniature circuit breaker- 3P – 16 A – C curve – 6000 A – 400 V EZ9F56316
Main range Easy9device application Distributionproduct or component type Miniature circuit-breakerdevice short name Easy9 MCBPoles 3Pnumber of protected poles 3[In] rated current 16 Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000 A Icn at 220 V AC 50/60 Hz conforming to IEC 60898-1
6000 A Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1suitability for isolation Yes conforming to IEC 60898-1Complementary network frequency 50 Hz[Ue] rated operational voltage 220 V AC 50/60 Hz
400 V AC 50/60 Hzmagnetic tripping limit 5…10 x In[Ics] rated service breaking capacity 6 kA 100 % x Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to IEC 60898-1[Uimp] rated impulse withstand voltage 4 kV conforming to IEC 60898-1contact position indicator Yescontrol type Togglelocal signalling Withoutmounting mode Clip-onmounting support DIN rail9 mm pitches 6height 81 mmwidth 54 mmdepth 66.5 mmcolour Grey (RAL 7035)mechanical durability 10000 cycleselectrical durability 4000 cyclesconnections – terminals Tunnel type terminal (top or bottom) 1…25 mm² rigid
Tunnel type terminal (top or bottom) 1…16 mm² flexibletightening torque 2 N.m top or bottomSKU: n/a -
CIRCUIT BREAKERS
Circuit breaker Easypact EZC100H – TMD – 63 A – 4 poles 3d
Main range of product EasyPactproduct or component type Circuit breakerdevice short name Easypact EZC100Hcircuit breaker name Easypact EZC100Hdevice application Distributionpoles description 4Pprotected poles description 3tnetwork type AC
DCnetwork frequency 50/60 Hz[In] rated current 100 A at 40 °C[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2[Ue] rated operational voltage 550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2breaking capacity code Hbreaking capacity 10 kA Icu at 125 V DC 1P conforming to IEC 60947-2
10 kA Icu at 250 V DC 2P conforming to IEC 60947-2
10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
30 kA Icu at 380…400 V AC 50/60 Hz conforming to IEC 60947-2
30 kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2[Ics] rated service breaking capacity 5 kA at 125 V DC conforming to IEC 60947-2
5 kA at 250 V DC conforming to IEC 60947-2
5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2
15 kA at 380…400 V AC 50/60 Hz conforming to IEC 60947-2
25 kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
7.5 kA at 415 V AC 50/60 Hz conforming to IEC 60947-2suitability for isolation Yes conforming to IEC 60947-2utilisation category Category Atrip unit name TM-Dtrip unit technology Thermal-magnetictrip unit rating 63 A at 50 °Cprotection type Overload protection
Short-circuit protectionpollution degree 3 conforming to IEC 60947Complementary control type Togglemounting mode Fixedmounting support Backplateupside connection Frontdownside connection Frontmechanical durability 8500 cycleselectrical durability Category A: 1500 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2connection pitch 25 mmlocal signalling Positive contact indicationneutral protection setting Without protectionearth-leakage protection Withoutheight 130 mmwidth 100 mmdepth 60 mmSKU: n/a -
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 2P 40A C Miniature Circuit breaker A9F44240
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 2P 40A C Miniature Circuit breaker A9F44240
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 2Pnumber of protected poles 2[In] rated current 40 Anetwork type AC/DCtrip unit technology Thermal-magneticcurve code Cbreaking capacity 6 kA Icu at 100…133 V DC conforming to EN/IEC 60947-2
6000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1
36 kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
20 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 440 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 27 kA 75 % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz
15 kA 75 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 75 % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz
4.5 kA 75 % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz
6000 A 100 % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz
6 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 4height 85 mmwidth 36 mmdepth 78.5 mmnet weight 0.25 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 3.5 N.m top or bottomearth-leakage protection Separate blockEnvironment standards EN/IEC 60898-1
EN/IEC 60947-2IP degree of protection IP20 conforming to IEC 60529pollution degree 3 conforming to EN/IEC 60947-2tropicalisation 2 conforming to IEC 60068-1relative humidity 95 % at 55 °Cambient air temperature for operation -35…70 °Cambient air temperature for storage -40…85 °CSKU: n/a -
Electro, SOCKETS & SWITCHES, SWITCHES
FBN82- BG 2 GANG DIMMER SWITCH
BG Electrical are confident in the quality of our workmanship and materials, the guarantee stated applies from the date of delivery.
200W Rated (100W LED)
Easy to install supplied with fixing screws and installation instructions
Adjust your light level for mood setting as well as energy saving with 2 way on/off
Trailing (lagging) edge dimmer suitable for dimming LED, dimmable CFL’s and traditional lighting
Intelligent electronic circuit monitors the connected load and provides a soft-start with protection against thermal, current and voltage overload
Suitable for use with good quality electronic or wire wound transformers. Can also be used with good quality mains voltage halogen lamps incorporating GU10 bases
2 way switching allows for a second switch position in a circuit
Screwless front plate clips on and off easily and has a sleek flat profile
Moisture control gasket prevents tarnishing from new plaster
SKU: n/a -
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Easy9 miniature circuit breaker- 4P – 40 A – C curve – 6000 A – 400 V EZ9F56440
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSEasy9 miniature circuit breaker- 4P – 40 A – C curve – 6000 A – 400 V EZ9F56440
Main range Easy9device application Distributionproduct or component type Miniature circuit-breakerdevice short name Easy9 MCBPoles 4Pnumber of protected poles 4[In] rated current 40 Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000 A Icn at 220 V AC 50/60 Hz conforming to IEC 60898-1
6000 A Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1suitability for isolation Yes conforming to IEC 60898-1Complementary network frequency 50/60 Hz[Ue] rated operational voltage 220 V AC 50/60 Hz
400 V AC 50/60 Hzmagnetic tripping limit 5…10 x In[Ics] rated service breaking capacity 6 kA 100 % x Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to IEC 60898-1[Uimp] rated impulse withstand voltage 4 kV conforming to IEC 60898-1contact position indicator Yescontrol type Togglelocal signalling Withoutmounting mode Clip-onmounting support DIN rail9 mm pitches 8height 81 mmwidth 72 mmdepth 66.5 mmcolour Grey (RAL 7035)mechanical durability 10000 cycleselectrical durability 4000 cyclesconnections – terminals Tunnel type terminal (top or bottom) 1…25 mm² flexible
Tunnel type terminal (top or bottom) 1…35 mm² rigidtightening torque 3.5 N.m top or bottomearth-leakage protection WithoutSKU: n/a