Philips Certaflux LED Panel 600 x 600 865 MD1 MTP
CertaFlux LED panel are designed to enable OEM to make ultra-slim LED luminaires for commercial office applications. With various combination of Philips drivers, OEM can offer very wide range of lumen package with a few panel modules which means it benefits maximum flexibility of luminaire offer to OEMs and end-user. CertaFlux LED panel offers excellent product performance and reliability, with good quality of light, meeting market needs for office lighting.
Applications
₦42,500.00
Compare-
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Miniature circuit-breaker, Acti9 iC60H, 2P, 10 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84210
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSMiniature circuit-breaker, Acti9 iC60H, 2P, 10 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84210
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Hpoles description 2Pnumber of protected poles 2[In] rated current 10 Anetwork type AC
DCtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
42 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
30 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at <= 125 V DC conforming to EN/IEC 60947-2
42 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards EN 60898-1
IEC 60947-2
IEC 60898-1
EN 60947-2Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 15 kA 50 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 50 % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz
5 kA 50 % conforming to EN 60947-2 – 440 V AC 50/60 Hz
15 kA 50 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 50 % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz
5 kA 50 % conforming to IEC 60947-2 – 440 V AC 50/60 Hz
7500 A 75 % conforming to EN 60898-1 – 400 V AC 50/60 Hz
7500 A 75 % conforming to IEC 60898-1 – 400 V AC 50/60 Hz
21 kA 50 % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz
21 kA 50 % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz
15 kA 100 % conforming to IEC 60947-2 – 72…125 V DC
15 kA 100 % conforming to EN 60947-2 – 72…125 V DClimitation class 3 conforming to EN 60898-1
3 conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 4height 85 mmwidth 36 mmdepth 78.5 mmnet weight 0.25 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
Electro, SOLAR POWERED
Mornyray SOLAR FLOOD LIGHT 100Watt
Solar Square Floodlight: Seven working modes for your convenience 1. Sensor mode 2. Half induction mode 3. 100% lighting mode 4. 50% lighting mode 5. 3 hour lighting mode 6. 5 hour lighting mode 7. 8 hour lighting mode Application: 1. Indoor use: indoor emergency lighting, home security lighting; 2. Outdoor use: courtyard lighting, landscape lighting, corridor lighting, door lighting, port lighting, container courtyard lighting, stadium lighting, courtyard lighting, plaza lighting, plant and beautification lighting, fountain waterscape lighting and other places; 3. Special event use: adventure lighting, camping lighting, fishing lighting, on-site maintenance lighting, barbecue lighting
SKU: n/a -
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 1P 10A C Miniature Circuit breaker A9F44110
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 1P 10A C Miniature Circuit breaker A9F44110
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 1Pnumber of protected poles 1[In] rated current 10 Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 15 kA Icu at 12…48 V DC conforming to EN/IEC 60947-2
6 kA Icu at 72 V DC conforming to EN/IEC 60947-2
6000 A Icn at 240 V AC 50/60 Hz conforming to EN/IEC 60898-1
36 kA Icu at 10…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
20 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 240 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 27 kA 75 % conforming to EN/IEC 60947-2 – 10…60 V AC 50/60 Hz
15 kA 75 % conforming to EN/IEC 60947-2 – 100…133 V AC 50/60 Hz
7.5 kA 75 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
6000 A 100 % conforming to EN/IEC 60898-1 – 240 V AC 50/60 Hz
15 kA 100 % conforming to EN/IEC 60947-2 – 12…48 V DC
6 kA 100 % conforming to EN/IEC 60947-2 – 72 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 2height 85 mmwidth 18 mmdepth 78.5 mmnet weight 0.125 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
Electro, SOCKETS, SOCKETS & SWITCHES
BG BG820 – SHAVER SOCKET
Features:
• White moulded round edge, sleek and slim with softly rounded edges
• Easy to install, supplied with fixing screws and installation instructions
• Colour coded terminals with backed out captive screws for fast installation
• Screw cover caps for a sleek appearance
• Anti-microbial certified – manufactured using high grade thermoset Urea which effectively inhibits the growth of infectious diseases, including MRSA, E-Coli, Salmonella and Klebsiella Pneumonia bacteria
SKU: n/a -
Electro, INDOOR LIGHTS, LED LIGHTS, LIGHTING
V-TAC LED Modular Panel Light 60W 600 X 600mm 6400K Surface
Electro, INDOOR LIGHTS, LED LIGHTS, LIGHTINGV-TAC LED Modular Panel Light 60W 600 X 600mm 6400K Surface
Product benefits
- Ultra Slim, Contemporary & Elegant Design
- Higher Light Transmission Rate
- Exterior shell, cannot be easily damaged
- No infrared, does not attract flies
- Easy to install
- No Lead or Mercury content
- Environment friendly
- Dimmable options available in selected models
Applications
-
-
- Office Lighting
- Conference Halls
- Hospitals
- Hotels
- Shopping Malls
- Showroom and lobby cabin etc.
-
Kitchen and Domestic Lighting
SKU: n/a -
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
EZ9F56132 Easy9 miniature circuit breaker- 1P – 32 A – C curve – 6000 A – 230 V
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSEZ9F56132 Easy9 miniature circuit breaker- 1P – 32 A – C curve – 6000 A – 230 V
Main range Easy9device application Distributionproduct or component type Miniature circuit-breakerdevice short name Easy9 MCBPoles 1Pnumber of protected poles 1[In] rated current 32 Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 6000 A Icn at 230 V AC 50/60 Hz conforming to IEC 60898-1
10000 A Icn at 127 V AC 50/60 Hz conforming to IEC 60898-1suitability for isolation Yes conforming to IEC 60898-1Complementary network frequency 50 Hz[Ue] rated operational voltage 230 V AC 50 Hz
127 V AC 50 Hzmagnetic tripping limit 5…10 x In[Ics] rated service breaking capacity 6 kA 100 % x Icn at 230 V AC 50/60 Hz conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to IEC 60898-1[Uimp] rated impulse withstand voltage 4 kV conforming to IEC 60898-1contact position indicator Yescontrol type Togglelocal signalling Withoutmounting mode Clip-onmounting support DIN rail9 mm pitches 2height 81 mmwidth 18 mmdepth 66.5 mmcolour Grey (RAL 7035)mechanical durability 10000 cycleselectrical durability 4000 cyclesconnections – terminals Tunnel type terminal (top or bottom) 1…25 mm² flexible
Tunnel type terminal (top or bottom) 1…35 mm² rigidtightening torque 3.5 N.m top or bottomSKU: n/a