Acti9 iC60N 1P 16A C Miniature Circuit breaker A9F44116
Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 1P 16A C Miniature Circuit breaker A9F44116
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 1Pnumber of protected poles 1[In] rated current 16Â Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 15Â kA Icu at 12…48 V DC conforming to EN/IEC 60947-2
6Â kA Icu at 72 V DC conforming to EN/IEC 60947-2
6000Â A Icn at 240 V AC 50/60 Hz conforming to EN/IEC 60898-1
36Â kA Icu at 10…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
20Â kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
10Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 240 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 27Â kA 75Â % conforming to EN/IEC 60947-2 – 10…60 V AC 50/60 Hz
15Â kA 75Â % conforming to EN/IEC 60947-2 – 100…133 V AC 50/60 Hz
7.5Â kA 75Â % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
6000Â A 100Â % conforming to EN/IEC 60898-1 – 240 V AC 50/60 Hz
15Â kA 100Â % conforming to EN/IEC 60947-2 – 12…48 V DC
6 kA 100 % conforming to EN/IEC 60947-2 – 72 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 2height 85 mmwidth 18 mmdepth 78.5 mmnet weight 0.125 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
LIGHT SWITCHES & ELECTRICAL SOCKETS
Lisse White moulded – socket-outlet – 15 A – 1 gang – matt white GGBL3090
LIGHT SWITCHES & ELECTRICAL SOCKETSLisse White moulded – socket-outlet – 15 A – 1 gang – matt white GGBL3090
Main range Lisseaesthetic name White mouldedproduct or component type Socket-outletdevice presentation Complete productoutlet standard description Round pinswitch function Switchcolour tint Matt whitequantity per set Set of 1Complementary outlet poles configuration 1Poutlet standard Britishnumber of gangs 1 gangdevice mounting Wall mountedrated current 15 Afixing mode By screws M3.5 x 25Â mmconnections – terminals Screw terminalsmaterial Urea (carbamide)type of packing Polybagtype of installation Indoorheight 87Â mmwidth 87Â mmdepth 35.86Â mmnet weight 0.092Â kgSKU: n/a -
CHANGEOVER SWITCHES, Electro, GEAR SWITCHES & CHANGEOVER
ABB CHANGEOVER SWITCH 400A with Enclosure
Including a black plastic IP65 I-0-II pistol type handle (see the table below), shaft and bolt set for the cable connection. Handle padlockable in the 0-position, door interlock in the I- and Iipositions and when padlocked.
Dimensions
-
- Product Net Width:
- 265Â mm
-
- Product Net Height:
- 185Â mm
-
- Product Net Depth / Length:
- 203Â mm
-
- Product Net Weight:
- 7.415Â kg
16.35 lb
Technical
-
- Rated Operational Current AC-21A (Ie):
- (380 … 415 V) 400 A
(500 V) 400 A
(690 V) 400 A
-
- Rated Operational Current AC-22A (Ie):
- (380 … 415 V) 400 A
(500 V) 400 A
(690 V) 400 A
-
- Rated Operational Current AC-23A (Ie):
- (380 … 415 V) 400 A
(500 V) 400 A
(690 V) 400 A
-
- Rated Operational Current AC-31B (Ie):
- (380 … 415 V) 400 A
-
- Rated Operational Current AC-33B (Ie):
- (380 … 415 V) 400 A
-
- Rated Operational Power AC-23A (Pe):
- (380 … 415 V) 220 kW
(500 V) 280 kW
(690 V) 400 kW
-
- Conventional Free-air Thermal Current (Ith):
- q = 40 °C 400 A
-
- Conventional Thermal Current (Ithe):
- Fully Enclosed 400 A
-
- Rated Impulse Withstand Voltage (Uimp):
- 12 kV
-
- Rated Insulation Voltage (Ui):
- 1000 V
-
- Rated Operational Voltage:
- 1000 V
-
- Rated Short-time Withstand Current (Icw):
- for 1 s 15 kiloampere rms
-
- Power Loss:
- 10 W
SKU: n/a -
-
Electro, SOCKETS & SWITCHES, SWITCHES
FBN74 – 45AMP WATER HEATER SWITCH
BG Electrical are confident in the quality of our workmanship and materials, the guarantee stated applies from the date of delivery.
45A Rated
Easy to install supplied with fixing screws and installation instructions
Ideal for cookers and ovens
Double Pole switching for the peace of mind of a safer installation
Twin earth fitted as standard for high integrity circuits
Captive screws prevent screw loss
Flush power indicator
Screwless front plate clips on and off easily and has a sleek flat profile, with no visible plastic around the switch.
Moisture control gasket prevents tarnishing from new plaster
Minimum mounting box depth 47mm
SKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 1P 4A C Miniature Circuit breaker A9F44104
Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 1P 4A C Miniature Circuit breaker A9F44104
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 1Pnumber of protected poles 1[In] rated current 4Â Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 50Â kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
50Â kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
50Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
15Â kA Icu at 12…48 V DC conforming to EN/IEC 60947-2
6Â kA Icu at 72 V DC conforming to EN/IEC 60947-2
6000Â A Icn at 240 V AC 50/60 Hz conforming to EN/IEC 60898-1utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 240 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 50Â kA 100Â % conforming to EN/IEC 60947-2 – 12…60 V AC 50/60 Hz
50Â kA 100Â % conforming to EN/IEC 60947-2 – 100…133 V AC 50/60 Hz
50Â kA 100Â % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
6000Â A 100Â % conforming to EN/IEC 60898-1 – 240 V AC 50/60 Hz
15Â kA 100Â % conforming to EN/IEC 60947-2 – 12…48 V DC
6 kA 100 % conforming to EN/IEC 60947-2 – 72 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 2height 85 mmwidth 18 mmdepth 78.5 mmnet weight 0.125 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -