Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Switch disconnector iSW – 3P – 100 A – 415 V A9S65391
range |
Acti 9
|
|
---|---|---|
product name |
Acti 9 iSW
|
|
product or component type |
Switch disconnector
|
|
device short name |
ISW
|
|
device application |
Control
Isolation |
|
poles description |
3P
|
|
utilisation category |
AC-22A
|
|
suitability for isolation |
Yes
|
[Ie] rated operational current |
100 A at 415 V AC 50/60 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
415 V AC 50/60 Hz
|
|
[Icm] rated short-circuit making capacity |
5 kA switch-disconnector alone
|
|
[Icw] rated short-time withstand current |
1500 A
|
|
[Ui] rated insulation voltage |
500 V AC 50/60 Hz
|
|
[Uimp] rated impulse withstand voltage |
6 kV
|
|
control type |
Toggle
|
|
local signalling |
ON/OFF indication
|
|
contact position indicator |
Yes
|
|
mounting mode |
Fixed
|
|
mounting support |
DIN rail
|
|
comb busbar and distribution block compatibility |
Top or bottom: YES
|
|
9 mm pitches |
6
|
|
height |
85 mm
|
|
width |
54 mm
|
|
depth |
73 mm
|
|
colour |
White
|
|
mechanical durability |
20000 cycles
|
|
electrical durability |
10000 cycles
|
|
connections – terminals |
Tunnel type terminals (top or bottom) – <= 1 x 50 mm² – rigid
Tunnel type terminals (top or bottom) – <= 1 x 35 mm² – flexible Tunnel type terminals (top or bottom) – <= 1 x 35 mm² – flexible with ferrule |
|
wire stripping length |
9 mm
|
|
tightening torque |
3.5 N.m
|
standards |
IEC 60947-3
EN 60947-3 |
|
---|---|---|
IP degree of protection |
IP20
|
|
pollution degree |
3
|
|
tropicalisation |
2
|
|
relative humidity |
95 % at 55 °C
|
|
ambient air temperature for operation |
-25…60 °C
|
|
ambient air temperature for storage |
-40…85 °C
|
₦38,500.00
Compare-
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 4P 25A C Miniature Circuit breaker A9F44425
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 4P 25A C Miniature Circuit breaker A9F44425
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 4Pnumber of protected poles 4[In] rated current 25 Anetwork type AC/DCtrip unit technology Thermal-magneticcurve code Cbreaking capacity 6 kA Icu at 100…133 V DC conforming to EN/IEC 60947-2
6000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1
36 kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
20 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 440 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 27 kA 75 % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz
15 kA 75 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 75 % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz
4.5 kA 75 % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz
6000 A 100 % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz
6 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 8height 85 mmwidth 72 mmdepth 78.5 mmnet weight 0.5 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Miniature circuit breaker, Easy9, 2P, 16 A, C curve, 6000 A EZ9F56216
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSMiniature circuit breaker, Easy9, 2P, 16 A, C curve, 6000 A EZ9F56216
Main range Easy9device application Distributionproduct or component type Miniature circuit-breakerdevice short name Easy9 MCBPoles 2Pnumber of protected poles 2[In] rated current 16 Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000 A Icn at 220 V AC 50/60 Hz conforming to IEC 60898-1
6000 A Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1suitability for isolation Yes conforming to IEC 60898-1Complementary network frequency 50/60 Hz[Ue] rated operational voltage 220 V AC 50/60 Hz
400 V AC 50/60 Hzmagnetic tripping limit 5…10 x In[Ics] rated service breaking capacity 6 kA 100 % x Icn at 230 V AC 50/60 Hz conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to IEC 60898-1[Uimp] rated impulse withstand voltage 4 kV conforming to IEC 60898-1contact position indicator Yescontrol type Togglelocal signalling Withoutmounting mode Clip-onmounting support DIN rail9 mm pitches 4height 81 mmwidth 36 mmdepth 66.5 mmcolour Grey (RAL 7035)mechanical durability 10000 cycleselectrical durability 4000 cyclesconnections – terminals Tunnel type terminal (top or bottom) 1…25 mm² rigid
Tunnel type terminal (top or bottom) 1…16 mm² flexibletightening torque 2 N.m top or bottomearth-leakage protection WithoutSKU: n/a -
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Easy9 Residual Current Circuit Breaker – 4P – 63 A – 300 mA – AC type – 400 V EZ9R64463
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSEasy9 Residual Current Circuit Breaker – 4P – 63 A – 300 mA – AC type – 400 V EZ9R64463
Main range of product Easy9product or component type Residual current circuit breaker (RCCB)device short name Easy9 RCCBPoles 4Pneutral position Left[In] rated current 63 Anetwork type ACearth-leakage sensitivity 300 mAearth-leakage protection time delay Instantaneousearth-leakage protection class Type ACrated breaking and making capacity 500 Arated conditional short-circuit current Easy9 MCB: 4500 A 63 AComplementary device location in system Outgoernetwork frequency 50 Hz[Ue] rated operational voltage 400 V AC 50 Hzresidual current tripping technology Voltage independent[Ui] rated insulation voltage 440 V AC[Uimp] rated impulse withstand voltage 4 kVsurge current 250 Acontact position indicator Yescontrol type Togglemounting mode Clip-onmounting support DIN railcomb busbar and distribution block compatibility Top: YES9 mm pitches 8height 82 mmwidth 72 mmdepth 72 mmcolour Grey (RAL 7035)mechanical durability 5000 cycleselectrical durability AC: 2000 cycles 400 V AC 50 Hzconnections – terminals Tunnel type terminal (top or bottom) 1…35 mm² rigid
Tunnel type terminal (top or bottom) 1…25 mm² flexibletightening torque 3.5 N.m top or bottommarket segment Residential
Small commercialSKU: n/a -
LIGHT SWITCHES & ELECTRICAL SOCKETS
1 Gang 350VA, 50Hz Full-Flat Universal Dimmer with LED, White E8431EPD4_WE
LIGHT SWITCHES & ELECTRICAL SOCKETS1 Gang 350VA, 50Hz Full-Flat Universal Dimmer with LED, White E8431EPD4_WE
Main product or component type Dimmerlocal signalling On: indicator light, LED (amber)
Off: indicator light, LED (blue)additional information With memory push[Ue] rated operational voltage 220…240 V AC 50 Hzmaterial Brass: metal parts
Polycarbonate: plastic part
Steel: metal partscover frame colour tint WhiteComplementary wiring device mounting Flush
Surfaceclamping connection capacity 2 x 4 mm² for solid cable(s)
2 x 4 mm² for stranded cable(s)
3 x 2.5 mm² for solid cable(s)
3 x 2.5 mm² for stranded cable(s)rated operational power in VA 350 VAnumber of gangs 1 gangload type LV halogen
Incandescent lampembedding depth 6 mmwidth 87 mmheight 87 mmdepth 35 mmSKU: n/a -
-
ELECTRICAL INDUSTRIAL, Electro, RECLINE CABLES
Cometstar Nigeria Cable NAY 4 X 70.0MM Per Meter
The construction and material are determined by three main factors:
• Working voltage, determining the thickness of the insulation;
• Current-carrying capacity, determining the cross-sectional size of the conductor(s);
• Environmental conditions such as temperature, water, chemical or sunlight exposure, and mechanical impact, determining the form and composition of the outer cable jacketSKU: Cometstar Nigeria Cable NAY 4 X 70.0MM-1