CHINT
Voltage Monitoring Relay XJ3-D
XJ3 series phase failure phase sequence protection relay
www.finglai.comModel number ad parameters
Model number | XJ3-G | XJ3-S | XJ3-D |
Related product | Order | Order | Visiting… |
Phase failure protection | √ | √ | √ |
Phase wrong protection | √ | √ | √ |
Overvoltage protection | Χ | Χ | 380V-460V 1.5s-4s(Adjustable) |
Undervoltage protection | Χ | Χ | 300V-380V 2s-9s (Adjustable) |
Contact form | SPST-NO and SPST-NC | SPST-NO and SPST-NC | SPDT |
Action delay time | 2s max | 2s max | 2s max |
External dimensions | 85x46x110 mm | 85x46x110 mm | 70.5×45.5×115 mm |
Mounting type | Device or din rail | Device or din rail | 35mm din rail or punch |
Model number | XJ3 series |
Supply voltage | 380VAC 50Hz |
Contact rating | Ue/le AC-15 380V/0.95A Ith 5A |
Electrical life | 1×105 |
Mechanical life | 1×106 |
Operational temperature | -5°C-40°C |
₦16,500.00
Compare-
LIGHT SWITCHES & ELECTRICAL SOCKETS
GGBL7010BSS Lisse – Data Communication – TV/FM – Single Direct Connection Stainless Steel
LIGHT SWITCHES & ELECTRICAL SOCKETSGGBL7010BSS Lisse – Data Communication – TV/FM – Single Direct Connection Stainless Steel
Main range Lisseaesthetic name Screwless decoproduct or component type TV R socketTV socket type Individual (independant)colour tint Interior: black
Cover plate: stainless steelquantity per set Set of 10Complementary device presentation Complete productTV connector 1 female IECnumber of gangs 1 gangdevice mounting Flushfixing mode Concealed screwssurface finish Brushed finishmaterial Stainless steeltype of packing Boxdepth 22 mmwidth 87 mmheight 87 mmnet weight 0.109 kgSKU: n/a -
ACCESSORIES, ELECTRICAL INDUSTRIAL, SOLAR POWERED
Solar Powered Water Pump DC 140W 50m
Product Name 140w 24v 50m dc brushless solar powered borehole water pump Model TB3IN-140/24/50/1.3/0.75 Material stainless steel Color sliver Voltage(V) DC-36 Flow(m³/h) 1.3 Head(m) 50 Solar(W) 200 Voltrange(V) 21-50 Outlet(IN) 0.75 SKU: n/a -
CHINT
Chint 1 Gang 1 Way Switch
Founded in 1984, CHINT is a leading global provider of smart energy solutions. It is actively deploying “4+1” industrial sectors including smart electrics, green energy, industrial control and automation, smart home and incubator, forming an integrated whole industry chain of “power generation, storage, transmission, substation, distribution, sales and consumption”.
Chint 1 Gang 1 Way Switch
SKU: n/a -
CHINT
CHINT NU6-Ⅱ Low-voltage Surge Arrester 40 – 100KA
NU6-Ⅱ Low-voltage Surge Arrester
- Certificates: international certificates are under proceeding;
- Number of poles: 1, 2,3, 4;
- Electric ratings: 230/400V, AC50Hz;
- Application: Protect electric system and on-loading electrical apparatus from thunder and instantaneous over-voltage;
- Standard: IEC 61643-1, EN 61643-11
SKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 3P 16A C Miniature Circuit breaker A9F44316
Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 3P 16A C Miniature Circuit breaker A9F44316
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 3Pnumber of protected poles 3[In] rated current 16 Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 6000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1
36 kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
20 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at 100…133 V DC conforming to EN/IEC 60947-2utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 440 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 27 kA 75 % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz
15 kA 75 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 75 % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz
4.5 kA 75 % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz
6000 A 100 % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz
15 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 6height 85 mmwidth 54 mmdepth 78.5 mmnet weight 0.375 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
Low Voltage Products and Systems, SCHNEIDER SECTIONS
EZC100F3040 – Circuit breaker Easypact EZC100F – TMD – 40 A – 3 poles 3d
Low Voltage Products and Systems, SCHNEIDER SECTIONSEZC100F3040 – Circuit breaker Easypact EZC100F – TMD – 40 A – 3 poles 3d
Main range of product EasyPactproduct or component type Circuit breakerdevice short name Easypact EZC100Fcircuit breaker name Easypact EZC100Fdevice application Distributionpoles description 3Pprotected poles description 3tnetwork type AC
DCnetwork frequency 50/60 Hz[In] rated current 100 A at 40 °C[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2[Ue] rated operational voltage 550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2breaking capacity code Fbreaking capacity 25 kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
5 kA Icu at 125 V DC 1P conforming to IEC 60947-2
5 kA Icu at 250 V DC 2P conforming to IEC 60947-2
5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
10 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2
10 kA Icu at 400…415 V AC 50/60 Hz conforming to IEC 60947-2
7.5 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2[Ics] rated service breaking capacity 12.5 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2
2.5 kA at 125 V DC conforming to IEC 60947-2
2.5 kA at 250 V DC conforming to IEC 60947-2
2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2
5 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2
5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
3.75 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2suitability for isolation Yes conforming to IEC 60947-2utilisation category Category Atrip unit name TM-Dtrip unit technology Thermal-magnetictrip unit rating 40 A at 50 °Cprotection type Short-circuit protection
Overload protectionpollution degree 3 conforming to IEC 60664-1
3 conforming to IEC 947-1Complementary control type Togglemounting mode Fixedmounting support Backplateupside connection Frontdownside connection Frontmechanical durability 8500 cycleselectrical durability Category A: 1500 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2connection pitch 25 mmlocal signalling Positive contact indicationneutral protection setting Without protectionearth-leakage protection Withoutheight 130 mmwidth 75 mmdepth 60 mmSKU: n/a
There are no reviews yet.