AVS13
- Protection against:
- High voltage
- Low voltage
- Spikes/surges
- Powerback surges
- Ideal for:
- All electrical and electronic equipment
- Max current: 13 amps
- Wait time: User adjustable from 10 seconds to 3 minutes
Protect against
Ideal for
Max current: 13 amps
Wait time: User adjustable from 10 seconds to 3 minutes
₦26,000.00
CompareBG Nexus White Moulded BG827L 1 Gang 13 Amp Universal Switched Socket with Neon
range of product |
EasyPact
|
|
---|---|---|
product or component type |
Circuit breaker
|
|
device short name |
Easypact EZC250N
|
|
circuit breaker name |
Easypact EZC250N
|
|
device application |
Distribution
|
|
poles description |
3P
|
|
protected poles description |
3t
|
|
network type |
DC
AC |
|
network frequency |
50/60 Hz
|
|
[In] rated current |
250 A at 40 °C
|
|
[Ui] rated insulation voltage |
690 V AC 50/60 Hz conforming to IEC 60947-2
|
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to IEC 60947-2
|
|
[Ue] rated operational voltage |
550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2 |
|
breaking capacity code |
N
|
|
breaking capacity |
20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 125 V DC 1P conforming to IEC 60947-2 20 kA Icu at 250 V DC 2P conforming to IEC 60947-2 25 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 400…415 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Ics] rated service breaking capacity |
10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
25 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 125 V DC conforming to IEC 60947-2 10 kA at 250 V DC conforming to IEC 60947-2 25 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 4 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to IEC 60947-2
|
|
utilisation category |
Category A
|
|
trip unit name |
TM-D
|
|
trip unit technology |
Thermal-magnetic
|
|
trip unit rating |
200 A at 50 °C
|
|
protection type |
Overload protection
Short-circuit protection |
|
pollution degree |
3 conforming to IEC 60664-1
3 conforming to IEC 947-1 |
control type |
Toggle
|
|
---|---|---|
mounting mode |
Fixed
|
|
mounting support |
Backplate
|
|
upside connection |
Front
|
|
downside connection |
Front
|
|
mechanical durability |
10000 cycles
|
|
electrical durability |
Category A: 5000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
|
|
connection pitch |
35 mm
|
|
local signalling |
Positive contact indication
|
|
neutral protection setting |
Without protection
|
|
earth-leakage protection |
Without
|
|
height |
165 mm
|
|
width |
105 mm
|
|
depth |
60 mm
|
range |
Acti 9
|
|
---|---|---|
product name |
Disbo iC60
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
IC60N
|
|
poles description |
4P
|
|
number of protected poles |
4
|
|
[In] rated current |
25 A
|
|
network type |
AC/DC
|
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
6 kA Icu at 100…133 V DC conforming to EN/IEC 60947-2
6000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1 36 kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
|
utilisation category |
Category A conforming to EN/IEC 60947-2
|
network frequency |
50/60 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
440 V AC 50/60 Hz
|
|
magnetic tripping limit |
8 x In +/- 20 %
|
|
[Ics] rated service breaking capacity |
27 kA 75 % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz
15 kA 75 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz 6000 A 100 % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz 6 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V DC |
|
limitation class |
3 conforming to EN/IEC 60947-2
|
|
[Ui] rated insulation voltage |
500 V AC 50/60 Hz
|
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to EN/IEC 60947-2
|
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Trip indicator
|
|
mounting mode |
Clip-on
|
|
mounting support |
Rail
|
|
9 mm pitches |
8
|
|
height |
85 mm
|
|
width |
72 mm
|
|
depth |
78.5 mm
|
|
net weight |
0.5 kg
|
|
colour |
White
|
|
mechanical durability |
20000 cycles
|
|
electrical durability |
10000 cycles
|
|
provision for padlocking |
Padlockable
|
|
connections – terminals |
Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexible |
|
wire stripping length |
14 mm for top or bottom connection
|
|
tightening torque |
2 N.m top or bottom
|
|
earth-leakage protection |
Separate block
|
range |
Acti 9
|
|
---|---|---|
product name |
Disbo iC60
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
IC60N
|
|
poles description |
4P
|
|
number of protected poles |
4
|
|
[In] rated current |
4 A
|
|
network type |
AC/DC
|
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
50 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
50 kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 100…133 V DC conforming to EN/IEC 60947-2 6000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1 |
|
utilisation category |
Category A conforming to EN/IEC 60947-2
|
network frequency |
50/60 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
440 V AC 50/60 Hz
|
|
magnetic tripping limit |
8 x In +/- 20 %
|
|
[Ics] rated service breaking capacity |
50 kA 100 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
50 kA 100 % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz 25 kA 100 % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz 6000 A 100 % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz 6 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V DC |
|
limitation class |
3 conforming to EN/IEC 60947-2
|
|
[Ui] rated insulation voltage |
500 V AC 50/60 Hz
|
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to EN/IEC 60947-2
|
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Trip indicator
|
|
mounting mode |
Clip-on
|
|
mounting support |
Rail
|
|
9 mm pitches |
8
|
|
height |
85 mm
|
|
width |
72 mm
|
|
depth |
78.5 mm
|
|
net weight |
0.5 kg
|
|
colour |
White
|
|
mechanical durability |
20000 cycles
|
|
electrical durability |
10000 cycles
|
|
provision for padlocking |
Padlockable
|
|
connections – terminals |
Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexible |
|
wire stripping length |
14 mm for top or bottom connection
|
|
tightening torque |
2 N.m top or bottom
|
|
earth-leakage protection |
Separate block
|
standards |
EN/IEC 60898-1
EN/IEC 60947-2 |
|
---|---|---|
IP degree of protection |
IP20 conforming to IEC 60529
|
|
pollution degree |
3 conforming to EN/IEC 60947-2
|
|
tropicalisation |
2 conforming to IEC 60068-1
|
|
relative humidity |
95 % at 55 °C
|
|
ambient air temperature for operation |
-35…70 °C
|
|
ambient air temperature for storage |
-40…85 °C
|
range |
Lisse
|
|
---|---|---|
aesthetic name |
White moulded
|
|
product or component type |
Unswitched socket
|
|
device presentation |
Complete product
|
|
outlet standard |
British
|
|
colour tint |
Matt white
|
|
quantity per set |
Set of 5
|
|
type of packing |
Carton
|
switch function |
1-pole
|
|
---|---|---|
rated current |
13 A at 250 V AC 50 Hz
|
|
actuator |
Rocker
|
|
number of gangs |
2 gangs
|
|
fixing mode |
By screws
|
|
connections – terminals |
Screw terminals
|
|
material |
Urea (carbamide)
|
|
type of installation |
Indoor
|
|
depth |
22 mm
|
|
width |
148 mm
|
|
height |
87 mm
|
|
net weight |
0.123 kg
|
There are no reviews yet.