Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 3P 3A C Miniature Circuit breaker A9F44303
range |
Acti 9
|
|
---|---|---|
product name |
Disbo iC60
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
IC60N
|
|
poles description |
3P
|
|
number of protected poles |
3
|
|
[In] rated current |
3 A
|
|
network type |
AC
|
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
50 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
50 kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 6000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1 15 kA Icu at 100…133 V DC conforming to EN/IEC 60947-2 |
|
utilisation category |
Category A conforming to EN/IEC 60947-2
|
network frequency |
50/60 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
440 V AC 50/60 Hz
|
|
magnetic tripping limit |
8 x In +/- 20 %
|
|
[Ics] rated service breaking capacity |
50 kA 100 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
50 kA 100 % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz 25 kA 100 % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz 6000 A 100 % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V DC |
|
limitation class |
3 conforming to EN/IEC 60947-2
|
|
[Ui] rated insulation voltage |
500 V AC 50/60 Hz
|
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to EN/IEC 60947-2
|
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Trip indicator
|
|
mounting mode |
Clip-on
|
|
mounting support |
Rail
|
|
9 mm pitches |
6
|
|
height |
85 mm
|
|
width |
54 mm
|
|
depth |
78.5 mm
|
|
net weight |
0.375 kg
|
|
colour |
White
|
|
mechanical durability |
20000 cycles
|
|
electrical durability |
10000 cycles
|
|
provision for padlocking |
Padlockable
|
|
connections – terminals |
Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexible |
|
wire stripping length |
14 mm for top or bottom connection
|
|
tightening torque |
2 N.m top or bottom
|
|
earth-leakage protection |
Separate block
|
₦39,000.00
Compare-
LIGHTING, OUTDOOR LIGHTS
BRP392 LED144/NW 120W 220-240V
Specifications
- General Information
-
Lamp family code –Light source color 740 neutral whiteLight source replaceable NoNumber of gear units 1 unitDriver/power unit/transformer Power supply unitDriver included YesOptical cover/lens type –Control interface –Connection –Cable –Protection class IEC Safety class IFlammability mark For mounting on normally flammable surfacesCE mark CE markENEC mark –Warranty period 3 yearsOptic type outdoor –Constant light output NoNumber of products on MCB of 16 A type B 11Light source engine type LED - Light Technical
-
Upward light output ratio 0Standard tilt angle posttop –Standard tilt angle side entry 0° - Operating and Electrical
-
Input Voltage 220 to 240 VInput Frequency 50 to 60 HzInrush current 46 AInrush time 0.44 msPower Factor (Min) 0.9 - Controls and Dimming
-
Dimmable No - Mechanical and Housing
-
Housing Material Aluminum die castOptic material PolycarbonateOptical cover/lens material PolycarbonateFixation material AluminumMounting device Side-entry for diameter 42 to 60 mmOptical cover/lens shape Ball, globularOptical cover/lens finish –Overall length 492 mmOverall width 295 mmOverall height 86 mmEffective projected area 0.14 m²Color Gray - Approval and Application
-
Ingress protection code IP66 [ Dust penetration-protected, jet-proof]Mech. impact protection code IK08 [ 5 J vandal-protected] - Initial Performance (IEC Compliant)
-
Initial luminous flux (system flux) 14400 lmLuminous flux tolerance +/-5%Initial LED luminaire efficacy 120 lm/WInit. Corr. Color Temperature 4000 KInit. Color Rendering Index >70Initial chromaticity (0.43, 0.40) SDCM < 5Initial input power 120 WPower consumption tolerance +/-5% - Over Time Performance (IEC Compliant)
-
Median useful life L70B50 100000 h - Application Conditions
-
Ambient temperature range -30 to +50 °CMaximum dim level Not applicable - Product Data
-
Full product code 911401816498Order product name BRP392 LED144/NW 120W 220-240V DMOrder code 911401816498Numerator – Quantity Per Pack 1Numerator – Packs per outer box 1Material Nr. (12NC) 911401816498Net Weight (Piece) 6.200 kg
SKU: n/a -
Electro, LIGHT SWITCHES & ELECTRICAL SOCKETS, SCHNEIDER SECTIONS
Ultimate – screwless flat plage RJ45 data socket – 1 gang – stainl. steel/black GU7471BSS
Electro, LIGHT SWITCHES & ELECTRICAL SOCKETS, SCHNEIDER SECTIONSUltimate – screwless flat plage RJ45 data socket – 1 gang – stainl. steel/black GU7471BSS
Main range Ultimateaesthetic name Screwless flat plateproduct or component type Data socketdata socket type RJ45colour tint Black
Stainless steel, mattquantity per set Set of 1Complementary number of gangs 1 gangcommunication network type RJ45connections – terminals Screw terminaltype of installation Indoormaterial Steelfixing mode By screwsheight 88 mmwidth 88 mmdepth 35 mmSKU: n/a -
Schneider Mureva Floodlight, SCHNEIDER SECTIONS
Mureva lights, Floodlight 20W 4000K, IP65 230V IMT47208
Schneider Mureva Floodlight, SCHNEIDER SECTIONSMureva lights, Floodlight 20W 4000K, IP65 230V IMT47208
Main range Murevarange of product Mureva lightsproduct name Floodlightproduct or component type Lampdevice application Ware-houses and parking garages
Residential
Media device support
Public areas
Secure lighting
Stadiums and arenasComplementary type of installation OutdoorTotal system power 20 Wlight source LED[Ue] rated operational voltage 230 V ACpower factor 0.9colour rendering index Ra=80luminous flux 2000 lmbulb lifespan 50000 hcolour temperature 4000 Kcolour Blackbeam angle 110 °shape Rectangularheight 163.4 mmwidth 121.4 mmdepth 26.0 mmnet weight 530 gSKU: n/a -
Electro, LIGHT SWITCHES & ELECTRICAL SOCKETS, SOCKETS & SWITCHES, SWITCHES
BG FBS82 Screwless Flat Plate Stainless Steel Double Intelligent LED 2 Way Dimmer Switch
Electro, LIGHT SWITCHES & ELECTRICAL SOCKETS, SOCKETS & SWITCHES, SWITCHESBG FBS82 Screwless Flat Plate Stainless Steel Double Intelligent LED 2 Way Dimmer Switch
Key Features
- Screwless front plate, easy clip on/off
- No visible plastic around switches
- Sleek flat profile
- Angled in-line colour coded captive terminals
- Twin earth terminals
- Available in four high quality finishes
SKU: n/a -
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Miniature circuit-breaker, Acti9 iC60H, 2P, 50 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84250
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSMiniature circuit-breaker, Acti9 iC60H, 2P, 50 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84250
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Hpoles description 2Pnumber of protected poles 2[In] rated current 50 Anetwork type AC
DCtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
42 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
30 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at <= 125 V DC conforming to EN/IEC 60947-2
42 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards IEC 60947-2
EN 60947-2
EN 60898-1
IEC 60898-1Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 15 kA 50 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 50 % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz
5 kA 50 % conforming to EN 60947-2 – 440 V AC 50/60 Hz
15 kA 50 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 50 % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz
5 kA 50 % conforming to IEC 60947-2 – 440 V AC 50/60 Hz
7500 A 75 % conforming to EN 60898-1 – 400 V AC 50/60 Hz
7500 A 75 % conforming to IEC 60898-1 – 400 V AC 50/60 Hz
21 kA 50 % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz
21 kA 50 % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz
15 kA 100 % conforming to IEC 60947-2 – 72…125 V DC
15 kA 100 % conforming to EN 60947-2 – 72…125 V DC[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 4height 85 mmwidth 36 mmdepth 78.5 mmnet weight 0.25 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 3.5 N.m top or bottomearth-leakage protection Separate blockSKU: n/a
There are no reviews yet.