Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 4P 20A C Miniature Circuit breaker A9F44420
range |
Acti 9
|
|
---|---|---|
product name |
Disbo iC60
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
IC60N
|
|
poles description |
4P
|
|
number of protected poles |
4
|
|
[In] rated current |
20Â A
|
|
network type |
AC
|
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
6Â kA Icu at 100…133 V DC conforming to EN/IEC 60947-2
6000Â A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1 36Â kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10Â kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6Â kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
|
utilisation category |
Category A conforming to EN/IEC 60947-2
|
network frequency |
50/60 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
440 V AC 50/60 Hz
|
|
magnetic tripping limit |
8 x In +/- 20 %
|
|
[Ics] rated service breaking capacity |
27Â kA 75Â % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz
15Â kA 75Â % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz 7.5Â kA 75Â % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz 4.5Â kA 75Â % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz 6000Â A 100Â % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz 6Â kA 100Â % conforming to EN/IEC 60947-2 – 100…133 V DC |
|
limitation class |
3 conforming to EN/IEC 60947-2
|
|
[Ui] rated insulation voltage |
500Â V AC 50/60 Hz
|
|
[Uimp] rated impulse withstand voltage |
6Â kV conforming to EN/IEC 60947-2
|
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Trip indicator
|
|
mounting mode |
Clip-on
|
|
mounting support |
Rail
|
|
9 mm pitches |
8
|
|
height |
85Â mm
|
|
width |
72Â mm
|
|
depth |
78.5Â mm
|
|
net weight |
0.5Â kg
|
|
colour |
White
|
|
mechanical durability |
20000Â cycles
|
|
electrical durability |
10000Â cycles
|
|
provision for padlocking |
Padlockable
|
|
connections – terminals |
Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexible |
|
wire stripping length |
14Â mm for top or bottom connection
|
|
tightening torque |
2Â N.m top or bottom
|
|
earth-leakage protection |
Separate block
|
₦29,000.00
Compare-
ELECTRICAL INDUSTRIAL, Electro, RECLINE CABLES
Cometstar Nigeria Cable NAY 4 X 70.0MM Per Meter
The construction and material are determined by three main factors:
• Working voltage, determining the thickness of the insulation;
• Current-carrying capacity, determining the cross-sectional size of the conductor(s);
• Environmental conditions such as temperature, water, chemical or sunlight exposure, and mechanical impact, determining the form and composition of the outer cable jacketSKU: Cometstar Nigeria Cable NAY 4 X 70.0MM-1 -
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Miniature circuit-breaker, Acti9 iC60H, 2P, 4 A, C curve, 10000 A (IEC 60898-1), 70 kA (IEC 60947-2) A9F84204
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSMiniature circuit-breaker, Acti9 iC60H, 2P, 4 A, C curve, 10000 A (IEC 60898-1), 70 kA (IEC 60947-2) A9F84204
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Hpoles description 2Pnumber of protected poles 2[In] rated current 4Â Anetwork type AC
DCtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000Â A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
15Â kA Icu at <= 125 V DC conforming to EN/IEC 60947-2
70Â kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
70Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
70Â kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
70Â kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
70Â kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards IEC 60947-2
IEC 60898-1
EN 60947-2
EN 60898-1quality labels NFComplementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 70Â kA 100Â % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
70Â kA 100Â % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
70Â kA 100Â % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz
70Â kA 100Â % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz
7500Â A 75Â % conforming to EN 60898-1 – 400 V AC 50/60 Hz
7500Â A 75Â % conforming to IEC 60898-1 – 400 V AC 50/60 Hz
70Â kA 100Â % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz
70Â kA 100Â % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz
50Â kA 100Â % conforming to EN 60947-2 – 440 V AC 50/60 Hz
50Â kA 100Â % conforming to IEC 60947-2 – 440 V AC 50/60 Hz
15Â kA 100Â % conforming to IEC 60947-2 – 72…125 V DC
15Â kA 100Â % conforming to EN 60947-2 – 72…125 V DClimitation class 3 conforming to EN 60898-1
3 conforming to IEC 60898-1[Ui] rated insulation voltage 500Â V AC 50/60 Hz conforming to EN 60947-2
500Â V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6Â kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 4height 85 mmwidth 36 mmdepth 78.5 mmnet weight 0.25 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 4P 32A C Miniature Circuit breaker A9F44432
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 4P 32A C Miniature Circuit breaker A9F44432
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 4Pnumber of protected poles 4[In] rated current 32Â Anetwork type AC/DCtrip unit technology Thermal-magneticcurve code Cbreaking capacity 6Â kA Icu at 100…133 V DC conforming to EN/IEC 60947-2
6000Â A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1
36Â kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
20Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
10Â kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
6Â kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 440 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 27Â kA 75Â % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz
15Â kA 75Â % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5Â kA 75Â % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz
4.5Â kA 75Â % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz
6000Â A 100Â % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz
6 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 8height 85 mmwidth 72 mmdepth 78.5 mmnet weight 0.5 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 3.5 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
Electro, SOCKETS & SWITCHES, SURGE PROTECTOR
Himel Single Phase Voltage Stabilizers 5kVA
Voltage stabilizer, HAVRL, relay type, 5 kVA, British type plug, 110/220 V output, 85..250 V input, with time delay
Main
Range of product                      – HAVRLProduct or component type             – Voltage stabilizerTechnology type                       – RelayOutlet standard                        – BritishProvided equipment                    – User manualComplementary
Rated power in VA                        – 5 kVAMinimum insulating resistance             – 5 MOhmMaximum [In] rated current                – 22.7 AEfficiency                                 – 90 %Input voltage limits                         – 85…250 VOptional feature                            – Bypass
Cooling fan                                 – Input undervoltage protectionProtection type                              – Overvoltage
Overcurrent                                 – Temperature rise protection
Time delay                                   – Display typeLED                                         – Output voltage220 V AC +/- 8 %                             – 110 V AC +/- 10 %Network frequency                            – 50/60 HzEnvironment
Ambient air temperature for operation           -5…40 °CRelative humidity                              0…90 %Humidity storage                               0…90 %Operating altitude                              0…2000 mStorage altitude                                 0…2000 mStandards                                      EN 61000-6-2
EN 61000-6-4Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â EN 61558-1Packing Units
Unit Type of Package 1Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â PCENumber of Units in Package 1Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â 1SKU: n/a -
Electro, Low Voltage Products and Systems, SCHNEIDER SECTIONS
EZC100N4025 – Circuit breaker Easypact EZC100N – TMD – 25 A – 4 poles 3d
Electro, Low Voltage Products and Systems, SCHNEIDER SECTIONSEZC100N4025 – Circuit breaker Easypact EZC100N – TMD – 25 A – 4 poles 3d
Main range of product EasyPactproduct or component type Circuit breakerdevice short name Easypact EZC100Ncircuit breaker name Easypact EZC100Ndevice application Distributionpoles description 4Pprotected poles description 3tnetwork type DC
ACnetwork frequency 50/60 Hz[In] rated current 100 A at 40 °C[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2[Ue] rated operational voltage 550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2breaking capacity code Nbreaking capacity 10Â kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
25Â kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
25Â kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
5Â kA Icu at 125 V DC 1P conforming to IEC 60947-2
5Â kA Icu at 250 V DC 2P conforming to IEC 60947-2
5Â kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
15Â kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2
18Â kA Icu at 380…400 V AC 50/60 Hz conforming to IEC 60947-2[Ics] rated service breaking capacity 5Â kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
2.5Â kA at 125 V DC conforming to IEC 60947-2
2.5Â kA at 250 V DC conforming to IEC 60947-2
2.5Â kA at 550 V AC 50/60 Hz conforming to IEC 60947-2
12.5Â kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
12.5Â kA at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
9Â kA at 380…400 V AC 50/60 Hz conforming to IEC 60947-2
7.5 kA at 415 V AC 50/60 Hz conforming to IEC 60947-2suitability for isolation Yes conforming to IEC 60947-2utilisation category Category Atrip unit name TM-Dtrip unit technology Thermal-magnetictrip unit rating 25 A at 50 °Cprotection type Overload protection
Short-circuit protectionpollution degree 3 conforming to IEC 60947Complementary control type Togglemounting mode Fixedmounting support Backplateupside connection Frontdownside connection Frontmechanical durability 8500Â cycleselectrical durability Category A: 1500Â cycles 415 V AC 50/60 Hz conforming to IEC 60947-2connection pitch 25Â mmlocal signalling Positive contact indicationneutral protection setting Without protectionearth-leakage protection Withoutheight 130Â mmwidth 100Â mmdepth 60Â mmSKU: n/a
There are no reviews yet.