Acti9 iC60N 4P 40A C Miniature Circuit breaker A9F44440
range |
Acti 9
|
|
---|---|---|
product name |
Disbo iC60
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
IC60N
|
|
poles description |
4P
|
|
number of protected poles |
4
|
|
[In] rated current |
40Â A
|
|
network type |
AC/DC
|
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
6Â kA Icu at 100…133 V DC conforming to EN/IEC 60947-2
6000Â A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1 36Â kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10Â kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6Â kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
|
utilisation category |
Category A conforming to EN/IEC 60947-2
|
network frequency |
50/60 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
440 V AC 50/60 Hz
|
|
magnetic tripping limit |
8 x In +/- 20 %
|
|
[Ics] rated service breaking capacity |
27Â kA 75Â % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz
15Â kA 75Â % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz 7.5Â kA 75Â % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz 4.5Â kA 75Â % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz 6000Â A 100Â % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz 6Â kA 100Â % conforming to EN/IEC 60947-2 – 100…133 V DC |
|
limitation class |
3 conforming to EN/IEC 60947-2
|
|
[Ui] rated insulation voltage |
500Â V AC 50/60 Hz
|
|
[Uimp] rated impulse withstand voltage |
6Â kV conforming to EN/IEC 60947-2
|
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Trip indicator
|
|
mounting mode |
Clip-on
|
|
mounting support |
Rail
|
|
9 mm pitches |
8
|
|
height |
85Â mm
|
|
width |
72Â mm
|
|
depth |
78.5Â mm
|
|
net weight |
0.5Â kg
|
|
colour |
White
|
|
mechanical durability |
20000Â cycles
|
|
electrical durability |
10000Â cycles
|
|
provision for padlocking |
Padlockable
|
|
connections – terminals |
Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexible |
|
wire stripping length |
14Â mm for top or bottom connection
|
|
tightening torque |
3.5Â N.m top or bottom
|
|
earth-leakage protection |
Separate block
|
₦48,000.00
Compare-
ELECTRICAL INDUSTRIAL, TRANSFORMER
MEKSAN Transformer 300kVA 33/415kV
Meksan Transformer manufacture distribution and power transformer from 50 kVA up to 50 MVA.  Our products are produced in accordance with the TS 267 and the IEC60076  standards. Our production is documented with the TSE (Türkish Standard Institue) standards confortmity, ISO 9001:2000 quality system and ISO 14001 environmental management system certificates.
SKU: n/a -
CHINT
CHINT NU6-â…¡G/F Low-voltage Surge Arrester 25 – 60kA
NU6-â…¡G/F Low-voltage Surge Arrester
- Certificates: international certificates are under proceeding;
- Number of poles: 1, 2,3, 4;
- Electric ratings: 230/400V, AC50Hz;
- Application: Protect electric system and on-loading electrical apparatus from thunder and instantaneous over-voltage;
- Standard: IEC 61643-1, EN 61643-11
SKU: n/a -
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Easy9 miniature circuit breaker- 1P – 20 A – C curve – 6000 A – 230 V EZ9F56120
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSEasy9 miniature circuit breaker- 1P – 20 A – C curve – 6000 A – 230 V EZ9F56120
Main range Easy9device application Distributionproduct or component type Miniature circuit-breakerdevice short name Easy9 MCBPoles 1Pnumber of protected poles 1[In] rated current 20Â Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 6000Â A Icn at 230 V AC 50/60 Hz conforming to IEC 60898-1
10000Â A Icn at 127 V AC 50/60 Hz conforming to IEC 60898-1suitability for isolation Yes conforming to IEC 60898-1Complementary network frequency 50 Hz[Ue] rated operational voltage 230 V AC 50 Hz
127 V AC 50 Hzmagnetic tripping limit 5…10 x In[Ics] rated service breaking capacity 6 kA 100 % x Icn at 230 V AC 50/60 Hz conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to IEC 60898-1[Uimp] rated impulse withstand voltage 4 kV conforming to IEC 60898-1contact position indicator Yescontrol type Togglelocal signalling Withoutmounting mode Clip-onmounting support DIN rail9 mm pitches 2height 81 mmwidth 18 mmdepth 66.5 mmcolour Grey (RAL 7035)mechanical durability 10000 cycleselectrical durability 4000 cyclesconnections – terminals Tunnel type terminal (top or bottom) 1…25 mm² rigid
Tunnel type terminal (top or bottom) 1…16 mm² flexibletightening torque 2 N.m top or bottomSKU: n/a -
Electro, LIGHT SWITCHES & ELECTRICAL SOCKETS, SCHNEIDER SECTIONS
Ultimate Screwless dimmer switch 400W/VA, 1gang, 2way, main & LV, st.steel GU6412CSS
Electro, LIGHT SWITCHES & ELECTRICAL SOCKETS, SCHNEIDER SECTIONSUltimate Screwless dimmer switch 400W/VA, 1gang, 2way, main & LV, st.steel GU6412CSS
Main range of product Ultimaterange Ultimateaesthetic name Screwless flat plateproduct or component type Dimmerdevice application Controlload type Incandescent lamp
230 V AC halogen lamp: 400 Wcolour tint Stainless steelquantity per set Set of 1Complementary switch function 2-waydevice mounting Wall mounteddimmer application Resistive load
Inductive load[Ue] rated operational voltage 230 V AC 50 Hznumber of gangs 1 gangconnections – terminals Screwless terminalsfixing mode By screws M3.5 x 25Â mmheight 88Â mmwidth 88Â mmdepth 25Â mmSKU: n/a -
CABLE AND CABLE MANAGEMENT, Electro, SINGLE CORE WIRE
KABLEMETAL 25mm Single Core – Red
We offer other range of products across various categories and sub categories and our services are Procurement, installation and Management etc of electrical products, should you have any inquiry we are always here to do our best to promptly answer you.
SKU: n/a -
CHINT
N266 series digital clamp meter
N266 and N266F are kind of trinity half digital pincer-like meter with stable performance, safety and reliability. Adopting A/D converter with large-scaled collected circuit and equipped with overload protecting circuit for overall instrument, it is characterized with all range overload protection, low voltage indication, data hold, inductive indication and fast measurement, becoming the first choice for the electrical measurement.
SKU: n/a