Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 4P 50A C Miniature Circuit breaker A9F44450
range |
Acti 9
|
|
---|---|---|
product name |
Disbo iC60
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
IC60N
|
|
poles description |
4P
|
|
number of protected poles |
4
|
|
[In] rated current |
50 A
|
|
network type |
AC/DC
|
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
6 kA Icu at 100…133 V DC conforming to EN/IEC 60947-2
6000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1 36 kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
|
utilisation category |
Category A conforming to EN/IEC 60947-2
|
network frequency |
50/60 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
440 V AC 50/60 Hz
|
|
magnetic tripping limit |
8 x In +/- 20 %
|
|
[Ics] rated service breaking capacity |
27 kA 75 % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz
15 kA 75 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz 6000 A 100 % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz 6 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V DC |
|
limitation class |
3 conforming to EN/IEC 60947-2
|
|
[Ui] rated insulation voltage |
500 V AC 50/60 Hz
|
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to EN/IEC 60947-2
|
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Trip indicator
|
|
mounting mode |
Clip-on
|
|
mounting support |
Rail
|
|
9 mm pitches |
8
|
|
height |
85 mm
|
|
width |
72 mm
|
|
depth |
78.5 mm
|
|
net weight |
0.5 kg
|
|
colour |
White
|
|
mechanical durability |
20000 cycles
|
|
electrical durability |
10000 cycles
|
|
provision for padlocking |
Padlockable
|
|
connections – terminals |
Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexible |
|
wire stripping length |
14 mm for top or bottom connection
|
|
tightening torque |
3.5 N.m top or bottom
|
|
earth-leakage protection |
Separate block
|
₦48,000.00
Compare-
Electro, LIGHT SWITCHES & ELECTRICAL SOCKETS
Lisse – Plate Switch – 3 gang 2 way – 10AX Polished Chrome with White Interior GGBL1032WPC
Electro, LIGHT SWITCHES & ELECTRICAL SOCKETSLisse – Plate Switch – 3 gang 2 way – 10AX Polished Chrome with White Interior GGBL1032WPC
Main range Lisseaesthetic name Screwless decoproduct or component type Plate switchdevice presentation Complete productquantity per set Set of 10Complementary switch function 2-waycontrol type Rockernumber of gangs 3 gangsdevice mounting Wall mountedfixing mode Concealed screwsconnections – terminals Screw terminalsmaterial Stainless steelsurface finish Polishedtype of packing Boxheight 87 mmwidth 87 mmdepth 25 mmnet weight 0.136 kgSKU: n/a -
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Miniature circuit-breaker, Acti9 iC60H, 2P, 16 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84216
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSMiniature circuit-breaker, Acti9 iC60H, 2P, 16 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84216
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Hpoles description 2Pnumber of protected poles 2[In] rated current 16 Anetwork type DC
ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
42 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
30 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at <= 125 V DC conforming to EN/IEC 60947-2
42 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards EN 60898-1
IEC 60898-1
EN 60947-2
IEC 60947-2Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 15 kA 50 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 50 % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz
5 kA 50 % conforming to EN 60947-2 – 440 V AC 50/60 Hz
15 kA 50 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 50 % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz
5 kA 50 % conforming to IEC 60947-2 – 440 V AC 50/60 Hz
7500 A 75 % conforming to EN 60898-1 – 400 V AC 50/60 Hz
7500 A 75 % conforming to IEC 60898-1 – 400 V AC 50/60 Hz
21 kA 50 % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz
21 kA 50 % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz
15 kA 100 % conforming to IEC 60947-2 – 72…125 V DC
15 kA 100 % conforming to EN 60947-2 – 72…125 V DClimitation class 3 conforming to EN 60898-1
3 conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 4height 85 mmwidth 36 mmdepth 78.5 mmnet weight 0.25 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
Electro, SCHNEIDER SECTIONS, Schneider Thorsman Testmeters
Thorsman BS Socket Tester IMT23103
Main product or component type Socket-outlet testeroutlet standard BritishComplementary local signalling Ground error by LCD displayfunction available RCD test functionrated voltage 220 V 50…60 Hz +/- 10 %measurement category Category III 300 Vresidual test current 30 mA +/- 15 %RCD test time 60…300 mscontact voltage threshold < 35 V ACheight 77 mmwidth 67 mmdepth 66 mmnet weight 70 gSKU: n/a -
Electro, SOCKETS, SOCKETS & SWITCHES
Lisse – Switched Socket – 1 gang – 13A SP 2USB Mocha Bronze with Black Interior
Electro, SOCKETS, SOCKETS & SWITCHESLisse – Switched Socket – 1 gang – 13A SP 2USB Mocha Bronze with Black Interior
Main range Lisseaesthetic name Screwless decoproduct or component type Switched socketdevice presentation Complete productoutlet standard Britishcolour tint Cover plate: mocha bronze
Interior: blacktype of packing BagComplementary switch function 1-polerated current 13 A at 250 V AC 50/60 Hzintegrated connection type 2 USB port 5 V DC 2.1 Aactuator Rockernumber of gangs 1 gangpilot light without LEDfixing mode Concealed screwsconnections – terminals Screw terminalsmaterial Stainless steeltype of installation Indoordepth 32 mmwidth 87 mmheight 87 mmnet weight 0.149 kgEnvironment standards BS 1363-2IP degree of protection IP20Packing Units Unit Type of Package 1 PCENumber of Units in Package 1 1Package 1 Weight 187 gPackage 1 Height 3.5 cmPackage 1 width 8.7 cmPackage 1 Length 8.7 cmSKU: n/a -
CHANGEOVER SWITCHES, Electro, GEAR SWITCHES & CHANGEOVER
ABB CHANGEOVER SWITCH 400A with Enclosure
Including a black plastic IP65 I-0-II pistol type handle (see the table below), shaft and bolt set for the cable connection. Handle padlockable in the 0-position, door interlock in the I- and Iipositions and when padlocked.
Dimensions
-
- Product Net Width:
- 265 mm
-
- Product Net Height:
- 185 mm
-
- Product Net Depth / Length:
- 203 mm
-
- Product Net Weight:
- 7.415 kg
16.35 lb
Technical
-
- Rated Operational Current AC-21A (Ie):
- (380 … 415 V) 400 A
(500 V) 400 A
(690 V) 400 A
-
- Rated Operational Current AC-22A (Ie):
- (380 … 415 V) 400 A
(500 V) 400 A
(690 V) 400 A
-
- Rated Operational Current AC-23A (Ie):
- (380 … 415 V) 400 A
(500 V) 400 A
(690 V) 400 A
-
- Rated Operational Current AC-31B (Ie):
- (380 … 415 V) 400 A
-
- Rated Operational Current AC-33B (Ie):
- (380 … 415 V) 400 A
-
- Rated Operational Power AC-23A (Pe):
- (380 … 415 V) 220 kW
(500 V) 280 kW
(690 V) 400 kW
-
- Conventional Free-air Thermal Current (Ith):
- q = 40 °C 400 A
-
- Conventional Thermal Current (Ithe):
- Fully Enclosed 400 A
-
- Rated Impulse Withstand Voltage (Uimp):
- 12 kV
-
- Rated Insulation Voltage (Ui):
- 1000 V
-
- Rated Operational Voltage:
- 1000 V
-
- Rated Short-time Withstand Current (Icw):
- for 1 s 15 kiloampere rms
-
- Power Loss:
- 10 W
SKU: n/a -
There are no reviews yet.