C120H – circuit breaker – 3P – 100A – C curve
range of product |
C120
|
|
---|---|---|
range |
Acti 9
|
|
product name |
C120
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
C120H
|
|
device application |
Distribution
|
|
poles description |
3P
|
|
number of protected poles |
3
|
|
[In] rated current |
100Â A
|
|
network type |
AC
|
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
15Â kA Icu at <= 375 V DC conforming to EN/IEC 60947-2
15Â kA Icu at 230…400 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
network frequency |
50/60 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
<= 375 V DC
230…400 V AC 50/60 Hz |
|
magnetic tripping limit |
8 x In +/- 20 %
|
|
[Ics] rated service breaking capacity |
15Â kA 100Â % conforming to EN/IEC 60947-2 – <= 375 V DC
7.5Â kA 50Â % conforming to EN/IEC 60947-2 – 230…400 V AC 50/60 Hz |
|
limitation class |
3 conforming to EN/IEC 60947-2
|
|
[Ui] rated insulation voltage |
500Â V AC 50/60 Hz conforming to EN/IEC 60947-2
|
|
[Uimp] rated impulse withstand voltage |
6Â kV conforming to EN/IEC 60947-2
|
|
control type |
Toggle
|
|
local signalling |
ON/OFF indication
|
|
mounting mode |
Clip-on
|
|
mounting support |
35 mm symmetrical DIN rail
|
|
9 mm pitches |
9
|
|
height |
81Â mm
|
|
width |
81Â mm
|
|
depth |
73Â mm
|
|
net weight |
0.615Â kg
|
|
colour |
White
|
|
mechanical durability |
20000Â cycles
|
|
electrical durability |
5000Â cycles
|
|
connections – terminals |
Tunnel type terminals1…50 mm² rigid
Tunnel type terminals1.5…35 mm² flexible |
|
wire stripping length |
15Â mm
|
|
tightening torque |
3.5Â N.m
|
|
earth-leakage protection |
Separate block
|
standards |
EN/IEC 60947-2
|
|
---|---|---|
IP degree of protection |
IP20 conforming to IEC 60529
|
|
pollution degree |
3 conforming to IEC 60947-2
|
|
overvoltage category |
III
|
|
tropicalisation |
2 conforming to IEC 60068-1
|
|
relative humidity |
95 % at 55 °C
|
|
ambient air temperature for operation |
-30…70 °C
|
|
ambient air temperature for storage |
-40…80 °C
|
₦53,000.00
Compare-
CHANGEOVER SWITCHES, Electro, GEAR SWITCHES & CHANGEOVER
ABB CHANGEOVER SWITCH 800A with Enclosure
-
-
-
- Long Description:
- Including a black plastic IP65 I-0-II pistol type handle (see the table below), shaft and bolt set for the cable connection. Handle not padlockable and no door interlocking. Operating angle 90° to achieve fast switching. Minimum OFF-time between transfer from I-II or II-I is 20 ms.
Categories
- Products » Low Voltage Products and Systems » Switches » Change-over and Transfer Switches » Manual Change-over Switches
-
-
Technical
-
- Rated Operational Current AC-21A (Ie):
- (380 … 415 V) 800 A
(500 V) 800 A
(690 V) 800 A
-
- Rated Operational Current AC-22A (Ie):
- (380 … 415 V) 800 A
(500 V) 800 A
(690 V) 800 A
-
- Rated Operational Current AC-23A (Ie):
- (380 … 415 V) 800 A
(500 V) 800 A
(690 V) 800 A
-
- Rated Operational Current AC-31B (Ie):
- (380 … 415 V) 800 A
-
- Rated Operational Current AC-33B (Ie):
- (380 … 415 V) 800 A
-
- Rated Operational Power AC-23A (Pe):
- (380 … 415 V) 450 kW
(500 V) 560 kW
(690 V) 800 kW
-
- Conventional Free-air Thermal Current (Ith):
- q = 40 °C 800 A
-
- Conventional Thermal Current (Ithe):
- Fully Enclosed 800 A
-
- Rated Impulse Withstand Voltage (Uimp):
- 12 kV
-
- Rated Insulation Voltage (Ui):
- 1000 V
-
- Rated Operational Voltage:
- 1000 V
-
- Rated Short-time Withstand Current (Icw):
- for 1 s 20 kiloampere rms
-
- Power Loss:
- 40 W
SKU: n/a -
-
ELECTRICAL INDUSTRIAL, TRANSFORMER
MEKSAN Transformer 750kVA 33/415kV
Meksan Transformer manufacture distribution and power transformer from 50 kVA up to 50 MVA.  Our products are produced in accordance with the TS 267 and the IEC60076  standards. Our production is documented with the TSE (Türkish Standard Institue) standards confortmity, ISO 9001:2000 quality system and ISO 14001 environmental management system certificates.
SKU: n/a -
ELECTRICAL INDUSTRIAL, TRANSFORMER
MEKSAN Transformer 500kVA 11/415kV
Meksan Transformer manufacture distribution and power transformer from 50 kVA up to 50 MVA.  Our products are produced in accordance with the TS 267 and the IEC60076  standards. Our production is documented with the TSE (Türkish Standard Institue) standards confortmity, ISO 9001:2000 quality system and ISO 14001 environmental management system certificates.
SKU: n/a -
Electro, LED LIGHTS, LIGHTING, OUTDOOR LIGHTS
PHILIP LED FLOODLIGHT BVP175 LED142/CW 150W WB GREY CE Philips
Electro, LED LIGHTS, LIGHTING, OUTDOOR LIGHTSPHILIP LED FLOODLIGHT BVP175 LED142/CW 150W WB GREY CE Philips
SmartBright LED
FloodlightBVP175 LED142/CW 150W WB GREY CE
LED module 14250 lm
The SmartBright LED Floodlight is a versatile floodlight engineered to deliver
significant energy savings, an ideal solution for diverse floodlighting applications.
The product is also designed to meet relevant performance and safety
standards,offering you reliable and long-lasting performance.SKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
IC60H – miniature circuit breaker – 1P – 63A – C curve A9F84163
Schneider Circuit Breakers, SCHNEIDER SECTIONSIC60H – miniature circuit breaker – 1P – 63A – C curve A9F84163
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Hpoles description 1Pnumber of protected poles 1[In] rated current 63Â Anetwork type DC
ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000Â A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
15Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
42Â kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
30Â kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
15Â kA Icu at 60…72 V DC conforming to EN/IEC 60947-2
20Â kA Icu at 12…60 V DC conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards EN 60947-2
EN 60898-1
IEC 60898-1
IEC 60947-2Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 21Â kA 50Â % conforming to EN 60947-2 – 12…60 V AC 50/60 Hz
7.5Â kA 50Â % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
21Â kA 50Â % conforming to IEC 60947-2 – 12…60 V AC 50/60 Hz
7.5Â kA 50Â % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7500Â A 75Â % conforming to EN 60898-1 – 230 V AC 50/60 Hz
7500Â A 75Â % conforming to IEC 60898-1 – 230 V AC 50/60 Hz
15Â kA 50Â % conforming to IEC 60947-2 – 100…133 V AC 50/60 Hz
15Â kA 50Â % conforming to EN 60947-2 – 100…133 V AC 50/60 Hz
15Â kA 100Â % conforming to EN 60947-2 – 72 V DC
15Â kA 100Â % conforming to IEC 60947-2 – 72 V DC
20Â kA 100Â % conforming to EN 60947-2 – 12…60 V DC
20Â kA 100Â % conforming to IEC 60947-2 – 12…60 V DC[Ui] rated insulation voltage 500Â V AC 50/60 Hz conforming to EN 60947-2
500Â V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6Â kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 2height 85 mmwidth 18 mmdepth 78.5 mmnet weight 0.215 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 3.5 N.m top or bottomearth-leakage protection WithoutSKU: n/a
There are no reviews yet.