C120H – circuit breaker – 3P – 100A – C curve
range of product |
C120
|
|
---|---|---|
range |
Acti 9
|
|
product name |
C120
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
C120H
|
|
device application |
Distribution
|
|
poles description |
3P
|
|
number of protected poles |
3
|
|
[In] rated current |
100 A
|
|
network type |
AC
|
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
15 kA Icu at <= 375 V DC conforming to EN/IEC 60947-2
15 kA Icu at 230…400 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
network frequency |
50/60 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
<= 375 V DC
230…400 V AC 50/60 Hz |
|
magnetic tripping limit |
8 x In +/- 20 %
|
|
[Ics] rated service breaking capacity |
15 kA 100 % conforming to EN/IEC 60947-2 – <= 375 V DC
7.5 kA 50 % conforming to EN/IEC 60947-2 – 230…400 V AC 50/60 Hz |
|
limitation class |
3 conforming to EN/IEC 60947-2
|
|
[Ui] rated insulation voltage |
500 V AC 50/60 Hz conforming to EN/IEC 60947-2
|
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to EN/IEC 60947-2
|
|
control type |
Toggle
|
|
local signalling |
ON/OFF indication
|
|
mounting mode |
Clip-on
|
|
mounting support |
35 mm symmetrical DIN rail
|
|
9 mm pitches |
9
|
|
height |
81 mm
|
|
width |
81 mm
|
|
depth |
73 mm
|
|
net weight |
0.615 kg
|
|
colour |
White
|
|
mechanical durability |
20000 cycles
|
|
electrical durability |
5000 cycles
|
|
connections – terminals |
Tunnel type terminals1…50 mm² rigid
Tunnel type terminals1.5…35 mm² flexible |
|
wire stripping length |
15 mm
|
|
tightening torque |
3.5 N.m
|
|
earth-leakage protection |
Separate block
|
standards |
EN/IEC 60947-2
|
|
---|---|---|
IP degree of protection |
IP20 conforming to IEC 60529
|
|
pollution degree |
3 conforming to IEC 60947-2
|
|
overvoltage category |
III
|
|
tropicalisation |
2 conforming to IEC 60068-1
|
|
relative humidity |
95 % at 55 °C
|
|
ambient air temperature for operation |
-30…70 °C
|
|
ambient air temperature for storage |
-40…80 °C
|
₦53,000.00
Compare-
ELECTRICAL INDUSTRIAL, TRANSFORMER
BETA 1000KVA/11/0.415V COPPER/COPPER WINDING TRANSFORMER
Produced within a power range between 10 – 100.000 kVA , up to 170 kV high voltage level, three phase or single phase, oil immersed, ONAN, ONAF, OFWF, with Off-Load or On-Load Tap Changer, used both external and internal.
Dimensions of transformer conservator are determined and designed after several heat calculations of the oil stored in expansion tank and oil level changes by heat.
Being open to atmosphere, oil pressure changes continuously in Conservator Type Transformers due to thermal effects and exchange of air is dehumidified via air breather silicagel.SKU: n/a -
LIGHT SWITCHES & ELECTRICAL SOCKETS
15A 250V 1 Gang Switched Socket KB15_15
Main range Vivaceproduct or component type Socket-outlet with switchdevice short name KB15device presentation Complete mechanismComplementary outlet poles configuration 2P + Enumber of gangs 1 gangColour tint Whitematerial Polycarbonate: grid plate
Polycarbonate: surround
Polycarbonate: baseprojecting depth 8 mmdevice mounting Flushmounting support Wall mountedfixing mode By screw M3.5fixing center 60.3 mmembedding depth 35 mmrated current 15 A at 250 V AC, resistivenetwork frequency 50 Hzcontacts material Brass and phosphor bronzeconnections – terminals Pillar terminalterminal identifier N
Earth
Ltightening torque 0.4 N.mclamping connection capacity 2.5 mm²width 87 mmheight 87 mmSKU: n/a -
Low Voltage Products and Systems, SCHNEIDER SECTIONS
EZC100N4050 Circuit breaker Easypact EZC100N – TMD – 50 A – 4 poles 3d
Low Voltage Products and Systems, SCHNEIDER SECTIONSEZC100N4050 Circuit breaker Easypact EZC100N – TMD – 50 A – 4 poles 3d
Main range of product EasyPactproduct or component type Circuit breakerdevice short name Easypact EZC100Ncircuit breaker name Easypact EZC100Ndevice application Distributionpoles description 4Pprotected poles description 3tnetwork type DC
ACnetwork frequency 50/60 Hz[In] rated current 100 A at 40 °C[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2[Ue] rated operational voltage 550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2breaking capacity code Nbreaking capacity 10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
5 kA Icu at 125 V DC 1P conforming to IEC 60947-2
5 kA Icu at 250 V DC 2P conforming to IEC 60947-2
5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
15 kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2
18 kA Icu at 380…400 V AC 50/60 Hz conforming to IEC 60947-2[Ics] rated service breaking capacity 5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
2.5 kA at 125 V DC conforming to IEC 60947-2
2.5 kA at 250 V DC conforming to IEC 60947-2
2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
9 kA at 380…400 V AC 50/60 Hz conforming to IEC 60947-2
7.5 kA at 415 V AC 50/60 Hz conforming to IEC 60947-2suitability for isolation Yes conforming to IEC 60947-2utilisation category Category Atrip unit name TM-Dtrip unit technology Thermal-magnetictrip unit rating 50 A at 50 °Cprotection type Overload protection
Short-circuit protectionpollution degree 3 conforming to IEC 60947Complementary control type Togglemounting mode Fixedmounting support Backplateupside connection Frontdownside connection Frontmechanical durability 8500 cycleselectrical durability Category A: 1500 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2connection pitch 25 mmlocal signalling Positive contact indicationneutral protection setting Without protectionearth-leakage protection Withoutheight 130 mmwidth 100 mmdepth 60 mmSKU: n/a -
Electro, SOCKETS & SWITCHES, SWITCHES
BG 1GANG DIMMER SWITCH – FBS81
200W Rated (100W LED)
Easy to install supplied with fixing screws and installation instructions
Adjust your light level for mood setting as well as energy saving with 2 way on/off
Trailing (lagging) edge dimmer suitable for dimming LED, dimmable CFL’s and traditional lighting
Intelligent electronic circuit monitors the connected load and provides a soft-start with protection against thermal, current and voltage overload
Suitable for use with good quality electronic or wire wound transformers. Can also be used with good quality mains voltage halogen lamps incorporating GU10 bases
2 way switching allows for a second switch position in a circuit
Screwless front plate clips on and off easily and has a sleek flat profile
Moisture control gasket prevents tarnishing from new plaster
SKU: n/a -
CHINT
Chint 2 Gang Switch
Founded in 1984, CHINT is a leading global provider of smart energy solutions. It is actively deploying “4+1” industrial sectors including smart electrics, green energy, industrial control and automation, smart home and incubator, forming an integrated whole industry chain of “power generation, storage, transmission, substation, distribution, sales and consumption”.
Chint 2 Gang Switch
SKU: n/a -
LIGHT SWITCHES & ELECTRICAL SOCKETS, SCHNEIDER SECTIONS
Ultimate Screwless flat plate – switched socket – 1 gang – stainless steel GU3410BSS
LIGHT SWITCHES & ELECTRICAL SOCKETS, SCHNEIDER SECTIONSUltimate Screwless flat plate – switched socket – 1 gang – stainless steel GU3410BSS
Main aesthetic name Screwless flat plateproduct or component type Switched socketrated current 13 A at 230 V AC 50 Hzfixing mode By screws M3.5 x 30 mmcolour tint Stainless steelComplementary device presentation Complete productoutlet poles configuration 1Poutlet standard description 3 pinsoutlet standard Britishactuator Rockernumber of gangs 1 gangearth circuit Standard earthpilot light Without neon indicatordevice mounting Wall mountedconnections – terminals Screw terminalmaterial Steelquantity per set Set of 1height 88 mmwidth 88 mmdepth 30 mmsocket number 2SKU: n/a
There are no reviews yet.