C120N – circuit breaker – 4P – 100A – C curve
range of product |
C120
|
|
---|---|---|
range |
Acti 9
|
|
product name |
C120
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
C120N
|
|
device application |
Distribution
|
|
poles description |
4P
|
|
number of protected poles |
4
|
|
[In] rated current |
100 A at 30 °C
|
|
network type |
AC
|
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
10000 A Icn at 230…400 V AC 50/60 Hz conforming to EN/IEC 60898-1
6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at <= 500 V DC conforming to EN/IEC 60947-2 |
|
suitability for isolation |
Yes conforming to IEC 60947-2
|
network frequency |
50/60 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
380…415 V AC 50/60 Hz
<= 500 V DC 220…240 V AC 50/60 Hz 440 V AC 50/60 Hz 230…400 V AC 50/60 Hz |
|
magnetic tripping limit |
5…10 x In
|
|
[Ics] rated service breaking capacity |
7500 A 75 % conforming to EN/IEC 60898-1 – 230…400 V AC 50/60 Hz
4.5 kA 75 % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 – <= 500 V DC |
|
limitation class |
3 conforming to EN/IEC 60947-2
|
|
[Ui] rated insulation voltage |
500 V AC 50/60 Hz conforming to EN/IEC 60947-2
|
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to EN/IEC 60947-2
|
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
ON/OFF indication
|
|
mounting mode |
Clip-on
|
|
mounting support |
35 mm symmetrical DIN rail
|
|
comb busbar and distribution block compatibility |
NO
|
|
9 mm pitches |
12
|
|
height |
81 mm
|
|
width |
108 mm
|
|
depth |
73 mm
|
|
net weight |
0.82 kg
|
|
colour |
White
|
|
mechanical durability |
20000 cycles
|
|
electrical durability |
5000 cycles conforming to IEC 60947-2
|
|
connections – terminals |
Tunnel type terminals1…50 mm² rigid
Tunnel type terminals1.5…35 mm² flexible |
|
wire stripping length |
15 mm
|
|
tightening torque |
3.5 N.m
|
|
earth-leakage protection |
Separate block
|
₦60,000.00
Compare-
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 1P 10A C Miniature Circuit breaker A9F44110
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 1P 10A C Miniature Circuit breaker A9F44110
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 1Pnumber of protected poles 1[In] rated current 10 Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 15 kA Icu at 12…48 V DC conforming to EN/IEC 60947-2
6 kA Icu at 72 V DC conforming to EN/IEC 60947-2
6000 A Icn at 240 V AC 50/60 Hz conforming to EN/IEC 60898-1
36 kA Icu at 10…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
20 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 240 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 27 kA 75 % conforming to EN/IEC 60947-2 – 10…60 V AC 50/60 Hz
15 kA 75 % conforming to EN/IEC 60947-2 – 100…133 V AC 50/60 Hz
7.5 kA 75 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
6000 A 100 % conforming to EN/IEC 60898-1 – 240 V AC 50/60 Hz
15 kA 100 % conforming to EN/IEC 60947-2 – 12…48 V DC
6 kA 100 % conforming to EN/IEC 60947-2 – 72 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 2height 85 mmwidth 18 mmdepth 78.5 mmnet weight 0.125 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Miniature circuit-breaker, Acti9 iC60H, 2P, 16 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84216
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSMiniature circuit-breaker, Acti9 iC60H, 2P, 16 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84216
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Hpoles description 2Pnumber of protected poles 2[In] rated current 16 Anetwork type DC
ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
42 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
30 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at <= 125 V DC conforming to EN/IEC 60947-2
42 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards EN 60898-1
IEC 60898-1
EN 60947-2
IEC 60947-2Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 15 kA 50 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 50 % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz
5 kA 50 % conforming to EN 60947-2 – 440 V AC 50/60 Hz
15 kA 50 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 50 % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz
5 kA 50 % conforming to IEC 60947-2 – 440 V AC 50/60 Hz
7500 A 75 % conforming to EN 60898-1 – 400 V AC 50/60 Hz
7500 A 75 % conforming to IEC 60898-1 – 400 V AC 50/60 Hz
21 kA 50 % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz
21 kA 50 % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz
15 kA 100 % conforming to IEC 60947-2 – 72…125 V DC
15 kA 100 % conforming to EN 60947-2 – 72…125 V DClimitation class 3 conforming to EN 60898-1
3 conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 4height 85 mmwidth 36 mmdepth 78.5 mmnet weight 0.25 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
LIGHT SWITCHES & ELECTRICAL SOCKETS
16 A X/20 A 2 gang 2wfull – flat switch White E8432_2_WE
Main range ZENceloproduct or component type Switchdevice application Controlload type Inductive
Incandescent lamp
Fluorescent lamp
ResistiveComplementary device mounting Surface
Flushswitch function 2-wayrated current 20 A/16 AX at 250 V AC 50 Hznumber of gangs 2 gangsmaterial Polycarbonate + GF 20 %: grid plate
Polycarbonate: base
Polycarbonate: cover
Polycarbonate: surroundSKU: n/a -
ACCESSORIES, ELECTRICAL INDUSTRIAL, SOLAR POWERED
Ritar 100AH 12V AGM Deep Cycle Battery
Ritar Power Valve Regulated Lead Acid (VRLA) battery is a premium quality battery with wide application is critical power installations and offers long design life in float service. Ritar Power prides its RA series batteries as being designed with up-dated AGM valve regulated technology and made of high purity raw materials for high consistency and better performance battery.
Long design life
Low self-discharge rate
Good high rate discharge performance
Wide operation temperature range
Application: telecom systems, fire & alarm systems, emergency systems, power tools, medical equipment, UPS/EPS, solar inverters/controllers, etc.
SKU: n/a -
Electro, FLUORESENT TUBES, LIGHT BULBS, LIGHTING
PHILIPS CENTURA 2 TCS160 4xTL-D18W HF C3 Philip
PHILIPS CENTURA 2 TCS160 4xTL-D18W HF C3 – Electronic highfrequency – High-gloss mirror matt aluminum louver – Push-in
connector 3-poleCENTURA 2 TBS160 is a functional recessed luminaire for 2, 3 or 4 TL-D fluorescent lamps. It offers a wide range of optics as well as a prismatic plate. The optics/plate are fitted to the housing by means of a clip for easy installation and maintenance.
An external connection system enables the mains connection to be made without opening the luminaire. The luminaire fits in visible profile ceilings as standard and, using accessories, in concealed and plaster ceilings.
SKU: n/a
There are no reviews yet.