C120N – circuit breaker – 4P – 100A – C curve
range of product |
C120
|
|
---|---|---|
range |
Acti 9
|
|
product name |
C120
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
C120N
|
|
device application |
Distribution
|
|
poles description |
4P
|
|
number of protected poles |
4
|
|
[In] rated current |
100 A at 30 °C
|
|
network type |
AC
|
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
10000 A Icn at 230…400 V AC 50/60 Hz conforming to EN/IEC 60898-1
6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at <= 500 V DC conforming to EN/IEC 60947-2 |
|
suitability for isolation |
Yes conforming to IEC 60947-2
|
network frequency |
50/60 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
380…415 V AC 50/60 Hz
<= 500 V DC 220…240 V AC 50/60 Hz 440 V AC 50/60 Hz 230…400 V AC 50/60 Hz |
|
magnetic tripping limit |
5…10 x In
|
|
[Ics] rated service breaking capacity |
7500 A 75 % conforming to EN/IEC 60898-1 – 230…400 V AC 50/60 Hz
4.5 kA 75 % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 – <= 500 V DC |
|
limitation class |
3 conforming to EN/IEC 60947-2
|
|
[Ui] rated insulation voltage |
500 V AC 50/60 Hz conforming to EN/IEC 60947-2
|
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to EN/IEC 60947-2
|
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
ON/OFF indication
|
|
mounting mode |
Clip-on
|
|
mounting support |
35 mm symmetrical DIN rail
|
|
comb busbar and distribution block compatibility |
NO
|
|
9 mm pitches |
12
|
|
height |
81 mm
|
|
width |
108 mm
|
|
depth |
73 mm
|
|
net weight |
0.82 kg
|
|
colour |
White
|
|
mechanical durability |
20000 cycles
|
|
electrical durability |
5000 cycles conforming to IEC 60947-2
|
|
connections – terminals |
Tunnel type terminals1…50 mm² rigid
Tunnel type terminals1.5…35 mm² flexible |
|
wire stripping length |
15 mm
|
|
tightening torque |
3.5 N.m
|
|
earth-leakage protection |
Separate block
|
₦60,000.00
Compare-
Electro, LIGHT SWITCHES & ELECTRICAL SOCKETS, SOCKETS, SOCKETS & SWITCHES, SWITCHES
BG FBN65 TELEVISION SOCKET BLACK NICKEL
Electro, LIGHT SWITCHES & ELECTRICAL SOCKETS, SOCKETS, SOCKETS & SWITCHES, SWITCHESBG FBN65 TELEVISION SOCKET BLACK NICKEL
The BG Nexus Screwless range has a variety of stunning slimline clip-on screwless flat plates complimenting any interior space with their sleek profile. They are suitable for both domestic and commercial installations.
Range: BG Nexus Screwless
Type: TV & Satellite Socket
Finish: Black Nickel
Inserts: Black
Part: FBN65
Dimensions: 88mm x 88mm x 3mm
Minimum Box Depth: 25mm
SKU: n/a -
CHINT
Chint 2 Gang Switch
Founded in 1984, CHINT is a leading global provider of smart energy solutions. It is actively deploying “4+1” industrial sectors including smart electrics, green energy, industrial control and automation, smart home and incubator, forming an integrated whole industry chain of “power generation, storage, transmission, substation, distribution, sales and consumption”.
Chint 2 Gang Switch
SKU: n/a -
LIGHT SWITCHES & ELECTRICAL SOCKETS, SCHNEIDER SECTIONS
AvatarOn, switch, 16AX, 250V, 1 way, LED, Wood E8331L1LED_WD
LIGHT SWITCHES & ELECTRICAL SOCKETS, SCHNEIDER SECTIONSAvatarOn, switch, 16AX, 250V, 1 way, LED, Wood E8331L1LED_WD
Main product or component type Switchdevice application Controlload type Resistive
Fluorescent lamp
Inductive
Incandescent lampcolour tint WoodComplementary device presentation Complete productrated current 16 AX at 250 V AC 50/60 Hzswitch function 1-pole 1-waynumber of gangs 1 gangnumber of rocker 1clamping connection capacity 3 x 2.5 mm² for solid cable(s)
3 x 2.5 mm² for stranded cable(s)
4 x 1.5 mm² for solid cable(s)
4 x 1.5 mm² for stranded cable(s)connections – terminals Brass terminallocal signalling Off: LED indicator, LED (amber)Material Polycarbonate: grid plate
Polycarbonate: base
Polycarbonate: dolly
Polycarbonate: frame
Polycarbonate + GF 20 %: actuatordevice mounting Flush
Surfacewidth 86 mmheight 86 mmdepth 34.2 mmSKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
IC60H – miniature circuit breaker – 2P – 25A – C curve A9F84225
Schneider Circuit Breakers, SCHNEIDER SECTIONSIC60H – miniature circuit breaker – 2P – 25A – C curve A9F84225
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Hpoles description 2Pnumber of protected poles 2[In] rated current 25 Anetwork type AC
DCtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
42 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
30 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at <= 125 V DC conforming to EN/IEC 60947-2
42 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards EN 60898-1
EN 60947-2
IEC 60898-1
IEC 60947-2Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 15 kA 50 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 50 % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz
5 kA 50 % conforming to EN 60947-2 – 440 V AC 50/60 Hz
15 kA 50 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 50 % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz
5 kA 50 % conforming to IEC 60947-2 – 440 V AC 50/60 Hz
7500 A 75 % conforming to EN 60898-1 – 400 V AC 50/60 Hz
7500 A 75 % conforming to IEC 60898-1 – 400 V AC 50/60 Hz
21 kA 50 % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz
21 kA 50 % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz
15 kA 100 % conforming to IEC 60947-2 – 72…125 V DC
15 kA 100 % conforming to EN 60947-2 – 72…125 V DClimitation class 3 conforming to EN 60898-1
3 conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 4height 85 mmwidth 36 mmdepth 78.5 mmnet weight 0.25 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockSKU: n/a