Electro, Schneider, SCHNEIDER SECTIONS
Easy9 distribution board – 1P – 100A – 12 ways – fixed EZ9ES12L
range |
Easy9
|
|
---|---|---|
product or component type |
Enclosure
|
|
enclosure type |
Distribution enclosure
|
|
provided equipment |
1 x washer
Identification label 4 x screws Removable front cover |
enclosure mounting |
Surface
Flush |
|
---|---|---|
Nb of horizontal rows |
1
|
|
number of plates |
5 for plain plate
|
|
network number of phases |
Single phase
|
|
number of ways |
12 ways
|
|
type of rail |
DIN
|
|
cable entry |
8 knock-outs
|
|
Type of door |
Plain door
|
|
[In] rated current |
100 A
|
|
enclosure material |
Powder coated steel
|
|
width |
470 mm outside:
|
|
height |
232 mm outside:
|
|
depth |
90 mm outside:
|
|
colour |
Grey (RAL 7035)
|
standards |
IEC 61439-1
IEC 61439-3 |
|
---|---|---|
product certifications |
ASTA
|
|
IP degree of protection |
IP40 conforming to IEC 60529 (closed door)
|
|
IK degree of protection |
IK08 conforming to IEC 62262
|
|
ambient air temperature for operation |
50 °C
|
Package 1 Weight |
5250.000 kg
|
|
---|---|---|
Package 1 Height |
95.000 mm
|
|
Package 1 width |
232.000 mm
|
|
Package 1 Length |
470.000 mm
|
₦123,000.00
Compare-
-
Electro, SOLAR POWERED
Solar Panel MR300W Mono
330W Monocrystalline solar panel has cells built in for efficiency and durability. It is waterproof and can withstand a wide range of environmental conditions.
Features
● Bypass diode minimizes the power drop by shade.● White tempered glass, EVA resin,weather proof film and anodized aluminum frame to provide efficient protection from the severest environmental conditions.● Waterproof● Perfect for grid applications.● Product guarantee 10 years.SKU: n/a -
CIRCUIT BREAKERS
IC60N – miniature circuit breaker – 3P – 63A – C curve
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 3Pnumber of protected poles 3[In] rated current 63 Anetwork type DC
ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
36 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
20 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
36 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at <= 180 V DC conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards EN 60898-1
EN 60947-2
IEC 60898-1
IEC 60947-2Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 15 kA 75 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 75 % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz
4.5 kA 75 % conforming to EN 60947-2 – 440 V AC 50/60 Hz
15 kA 75 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 75 % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz
4.5 kA 75 % conforming to IEC 60947-2 – 440 V AC 50/60 Hz
27 kA 75 % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz
27 kA 75 % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz
6000 A 100 % conforming to EN 60898-1 – 400 V AC 50/60 Hz
6000 A 100 % conforming to IEC 60898-1 – 400 V AC 50/60 Hz
10 kA 100 % conforming to IEC 60947-2 – 125…180 V DC
10 kA 100 % conforming to EN 60947-2 – 125…180 V DC[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 6height 85 mmwidth 54 mmdepth 78.5 mmnet weight 0.375 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 3.5 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
Electro, SOCKETS & SWITCHES, SWITCHES
BG FBSRJ451 -1 WAY DATA OUT LET
IDC Terminal connection
Easy to install, supplied with fixing screws and installation instructions
RJ45 Ethernet Socket
Screwless front plate clips on and off easily and has a sleek, flat profile
Moisture control gasket, prevents tarnishing from new plaster
Shuttered socket
ID window and colour matched shutter for each outlet
Supplied as a kit of Euro module components
Anti-fingerprint lacquer reduces unsightly fingerprints
Minimum mounting box depth 35mm
SKU: n/a