DISTRIBUTION BOARDS, DISTRIBUTION BOARDS, Electro
Easy9 distribution board – 1P – 100A – 8 ways – fixed
range |
Easy9
|
|
---|---|---|
product or component type |
Enclosure
|
|
enclosure type |
Distribution enclosure
|
|
provided equipment |
1 x washer
Identification label 4 x screws Removable front cover |
enclosure mounting |
Surface
Flush |
|
---|---|---|
Nb of horizontal rows |
1
|
|
number of plates |
3 for plain plate
|
|
network number of phases |
Single phase
|
|
number of ways |
8 ways
|
|
type of rail |
DIN
|
|
cable entry |
6 knock-outs
|
|
Type of door |
Plain door
|
|
[In] rated current |
100 A
|
|
enclosure material |
Powder coated steel
|
|
width |
362 mm outside:
|
|
height |
232 mm outside:
|
|
depth |
90 mm outside:
|
|
colour |
Grey (RAL 7035)
|
₦157,800.00
Compare-
Electro, SOCKETS, SOCKETS & SWITCHES
BG Electrical Fast Charging 2.1 A USB Charger and Wi-Fi Range Extender Electrical Socket, Brushed Steel
Electro, SOCKETS, SOCKETS & SWITCHESBG Electrical Fast Charging 2.1 A USB Charger and Wi-Fi Range Extender Electrical Socket, Brushed Steel
- Improved Wi-Fi coverage throughout your home
- Works with all wireless broadband routers
- Easy to install and setup with one-touch WPS (Wi-Fi Protected Setup)
- Perfect for streaming music and videos or playing online games
- Suitable for computers, tablets, mobile phones, games consoles, TVs
- No plug-in adapters – keep your sockets free for use
- Wireless 2.4GHz single band
- Retrofits a standard 25mm wall box
- N300 – 300Mbps speed 802.11b/g/n wireless
- Terminal capacity; 3 x 2.5mm², 3 x 4.0mm² or 2 x 6mm²
- Twin earth fitted as standard to allow a double earth facility for installations requiring high integrity protective connection Ref. BS 7671:2008
- Manufactured to BS 1363-2
- Supplied with 2 x 32mm screws and screw covers
- 86mm x 146mm x 10mm (front plate) (H x W x D)
SKU: SMJ CTH5013 CABLE REEL HEAVY DUTY -
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 2P 10A C Miniature Circuit breaker A9F44210
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 2P 10A C Miniature Circuit breaker A9F44210
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 2Pnumber of protected poles 2[In] rated current 10 Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 6 kA Icu at 100…133 V DC conforming to EN/IEC 60947-2
6000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1
36 kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
20 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 440 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 27 kA 75 % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz
15 kA 75 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 75 % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz
4.5 kA 75 % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz
6000 A 100 % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz
6 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 4height 85 mmwidth 36 mmdepth 78.5 mmnet weight 0.25 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockEnvironment standards EN/IEC 60947-2
EN/IEC 60898-1IP degree of protection IP20 conforming to IEC 60529pollution degree 3 conforming to EN/IEC 60947-2tropicalisation 2 conforming to IEC 60068-1relative humidity 95 % at 55 °Cambient air temperature for operation -35…70 °Cambient air temperature for storage -40…85 °CSKU: n/a -
Electro, Schneider, SCHNEIDER SECTIONS
Easy9 distribution board – 1P – 100A – 8 ways – fixed EZ9ES8L
Main range Easy9product or component type Enclosureenclosure type Distribution enclosureprovided equipment 1 x washer
Identification label
4 x screws
Removable front coverComplementary enclosure mounting Surface
FlushNb of horizontal rows 1number of plates 3 for plain platenetwork number of phases Single phasenumber of ways 8 waystype of rail DINcable entry 6 knock-outsType of door Plain door[In] rated current 100 Aenclosure material Powder coated steelwidth 362 mm outside:height 232 mm outside:depth 90 mm outside:colour Grey (RAL 7035)Environment standards IEC 61439-1
IEC 61439-3product certifications ASTAIP degree of protection IP40 conforming to IEC 60529 (closed door)IK degree of protection IK08 conforming to IEC 62262ambient air temperature for operation 50 °CPacking Units Package 1 Weight 4500.000 kgPackage 1 Height 95.000 mmPackage 1 width 232.000 mmPackage 1 Length 362.000 mmSKU: n/a -
Electro, SOCKETS & SWITCHES, SWITCHES
FBN44 – BG 4GANG 2WAY SWITCH BLACK NICKEL
20A 16AX Rated
Easy to install supplied with fixing screws and installation instructions
2 way switching allows for a second switch position in a circuit
Captive backed out terminal screws for fast installation and to prevent screw loss
Screwless front plate clips on and off easily and has a sleek flat profile
No visible plastic around switches
Moisture control gasket prevents tarnishing from new plaster
Minimum mounting box depth 25mm
SKU: n/a -
CHINT
CHINT NU6-Ⅱ Low-voltage Surge Arrester 15 – 40A
NU6-Ⅱ Low-voltage Surge Arrester
- Certificates: international certificates are under proceeding;
- Number of poles: 1, 2,3, 4;
- Electric ratings: 230/400V, AC50Hz;
- Application: Protect electric system and on-loading electrical apparatus from thunder and instantaneous over-voltage;
- Standard: IEC 61643-1, EN 61643-11
SKU: n/a