Easy9 distribution board – 3P – 125A – 24 ways- straight with fixlink
range |
Easy9
|
|
---|---|---|
product or component type |
Enclosure
|
|
enclosure type |
Distribution enclosure
|
|
provided equipment |
1 x washer
4 x screws Removable front cover Prefabricated flexible connection Insulated fishbone Adjustable pan assembly Provision for incomer |
enclosure mounting |
Flush
Surface |
|
---|---|---|
number of plates |
6 for plain plate
|
|
network number of phases |
Three phase
|
|
number of ways |
24 ways
|
|
type of rail |
DIN
|
|
cable entry |
11 knock-outs
|
|
Type of door |
Plain door
|
|
[In] rated current |
125 A
|
|
enclosure material |
Powder coated steel
|
|
width |
470 mm outside:
|
|
height |
633 mm outside:
|
|
depth |
105 mm outside:
|
|
colour |
Grey (RAL 7035)
|
standards |
IEC 61439-3
IEC 61439-1 |
|
---|---|---|
product certifications |
ASTA
|
|
IP degree of protection |
IP40 conforming to IEC 60529 (closed door)
|
|
IK degree of protection |
IK08 conforming to IEC 62262
|
|
ambient air temperature for operation |
50 °C
|
₦483,000.00
Compare-
LIGHT SWITCHES & ELECTRICAL SOCKETS
Lisse Square edge white moulded – TV-R/DAB socket GGBL7020
Main range Lisseaesthetic name White mouldedproduct or component type TV R DAB socketTV socket type Intermediatecolour tint Whitequantity per set Set of 10Complementary device presentation Complete productTV connector 1 male IECradio connector Female IEC 1number of gangs 1 gangdevice mounting Flushfixing mode By screwssurface finish Semi-mattmaterial Urea (carbamide)type of packing Cartondepth 31.8 mmwidth 87 mmheight 87 mmnet weight 0.12 kgSKU: n/a -
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 1P 2A C Miniature Circuit breaker A9F44102
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 1P 2A C Miniature Circuit breaker A9F44102
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 1Pnumber of protected poles 1[In] rated current 2 Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 50 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
50 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
50 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at 12…48 V DC conforming to EN/IEC 60947-2
6 kA Icu at 72 V DC conforming to EN/IEC 60947-2
6000 A Icn at 240 V AC 50/60 Hz conforming to EN/IEC 60898-1utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 240 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 50 kA 100 % conforming to EN/IEC 60947-2 – 12…60 V AC 50/60 Hz
50 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V AC 50/60 Hz
50 kA 100 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
6000 A 100 % conforming to EN/IEC 60898-1 – 240 V AC 50/60 Hz
15 kA 100 % conforming to EN/IEC 60947-2 – 12…48 V DC
6 kA 100 % conforming to EN/IEC 60947-2 – 72 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 2height 85 mmwidth 18 mmdepth 78.5 mmnet weight 0.125 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
INDOOR LIGHTS, LED LIGHTS
TM En-Light LED Panel 600 x 600 40W 6500K
LED Panel Light Features:
1. Wide input voltage design: Universal Use
2. Long life: Over 35,000H
3. Safe & reliable & pollution-free & non-toxic & harmless
4. Advanced PC material: anti-extrusion &non-friable
5. High end quality
6. Super emitting angle: 120°
7. EMI anti-interference design
8. Constant current design
9. No Harmful Mercury, No UltraViolet or InfraRed Radiation
10. Safety design for overload .SKU: n/a -
LIGHT SWITCHES & ELECTRICAL SOCKETS
2 Gang TV and FM Outlet KB32TVFM
Main range of product Vivacerange Vivacedevice short name KB32product or component type TV/FM socketdevice presentation Complete mechanismComplementary number of gangs 1 gangnumber of outputs 2Colour tint Whitematerial Polycarbonate: surround
Polycarbonate: grid plate
Polycarbonate: baseprojecting depth 8 mmdevice mounting Flushmounting support Wall mountedfixing mode By screw M3.5fixing center 60.3 mmembedding depth 35 mmtightening torque 0.4 N.mwidth 86 mmheight 86 mmSKU: n/a -
LIGHT SWITCHES & ELECTRICAL SOCKETS
16 A X/20 A 2 Gang 1 way full – flat switch with ON indicator White E8432_1_WE
LIGHT SWITCHES & ELECTRICAL SOCKETS16 A X/20 A 2 Gang 1 way full – flat switch with ON indicator White E8432_1_WE
Main range ZENceloproduct or component type Switchdevice application Controlload type Incandescent lamp
Resistive
Fluorescent lamp
InductiveComplementary device mounting Surface
Flushswitch function 1-wayrated current 20 A/16 AX at 250 V AC 50 Hzlocal signalling Mechanical indicator, neon (amber)number of gangs 2 gangsmaterial Polycarbonate + GF 20 %: grid plate
Polycarbonate: base
Polycarbonate: cover
Polycarbonate: surroundPacking Units Package 1 Weight 71.840 gSKU: n/a -
CABLE AND CABLE MANAGEMENT, Electro, SINGLE CORE WIRE
Doncaster Cables 6mm Single Core – Red
Product Description
Manufactured to BS 6004:2012 Table 3
Annealed Stranded Copper Conductor / PVC Insulated / PVC Sheathed. 300/500V
Designed for use in light industrial and domestic wiring. These cables are particularly suited for installation as meter tails and are intended for fixed installation in dry or damp premises.
These cables can be installed in conduit, in cable trunking and in cable ducting. Or where there is deemed little risk of mechanical damage these cables can be clipped direct, on cable tray, embedded or in free air. These cables are not intended to be laid underground.
Product Details
Harmonisation Code Nominal Cross Sectional Area of Conductor (mm2) Nominal Stranding of Conductor (mm) Nominal Radial Thickness of insulation (mm) Nominal Radial Thickness of sheath (mm) Overall Diameter Lower Limit (mm) Overall Diameter Upper Limit (mm) Approximate Weight(kg/km) National Type 1.0 1 / 1.13 0.6 0.8 3.8 4.5 26 National Type 1.5 1 / 1.38 0.7 0.8 4.2 4.9 35 National Type 2.5 1 / 1.78 0.8 0.8 4.8 5.8 55 National Type 4.0 7 / 0.85 0.8 0.9 5.4 6.8 75 National Type 6.0 7 / 1.04 0.8 0.9 6.0 7.4 95 National Type 10.0 7 / 1.35 1.0 0.9 7.2 8.8 155 National Type 16.0 7 / 1.70 1.0 1.0 8.4 10.5 225 National Type 25.0 7 / 2.14 1.2 1.1 10.0 12.5 340 National Type 35.0 7 / 2.52 1.2 1.1 11.0 13.5 445 SKU: n/a
There are no reviews yet.