Easy9 miniature circuit breaker- 2P – 40 A – C curve – 6000 A – 230 V EZ9F56240
range |
Easy9
|
|
---|---|---|
device application |
Distribution
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
Easy9 MCB
|
|
Poles |
2P
|
|
number of protected poles |
2
|
|
[In] rated current |
40 A
|
|
network type |
AC
|
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
10000 A Icn at 220 V AC 50/60 Hz conforming to IEC 60898-1
6000 A Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1 |
|
suitability for isolation |
Yes conforming to IEC 60898-1
|
network frequency |
50/60 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
220 V AC 50/60 Hz
400 V AC 50/60 Hz |
|
magnetic tripping limit |
5…10 x In
|
|
[Ics] rated service breaking capacity |
6 kA 100 % x Icn at 230 V AC 50/60 Hz conforming to IEC 60898-1
|
|
[Ui] rated insulation voltage |
500 V AC 50/60 Hz conforming to IEC 60898-1
|
|
[Uimp] rated impulse withstand voltage |
4 kV conforming to IEC 60898-1
|
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Without
|
|
mounting mode |
Clip-on
|
|
mounting support |
DIN rail
|
|
9 mm pitches |
4
|
|
height |
81 mm
|
|
width |
36 mm
|
|
depth |
66.5 mm
|
|
colour |
Grey (RAL 7035)
|
|
mechanical durability |
10000 cycles
|
|
electrical durability |
4000 cycles
|
|
connections – terminals |
Tunnel type terminal (top or bottom) 1…25 mm² flexible
Tunnel type terminal (top or bottom) 1…35 mm² rigid |
|
tightening torque |
3.5 N.m top or bottom
|
|
earth-leakage protection |
Without
|
₦15,928.00
Compare-
COMPUTING, PRINTERS
HP COLOUR LASERJET ENTERPRISE M776DN MULTIFUNCTION PRINTER
- Print, copy, scan, digital send
- Print speed letter: Up to 45 ppm (black and color)
- Prints up to 11×17″; 1×550 paper tray (standard); Auto duplex printing; 200-sheet ADF
- FCC Class A emissions – for use in commercial environments, not residential environments
SKU: n/a -
CHANGEOVER SWITCHES
Santon 600Amps Changeover Switch
Santon produce 3 ranges of manual changeover switches, the Packet, Cam and Flat pack types. The Packet and Cam can be provided with or without off position and are available enclosed or as an open type for mounting in customers equipment, i.e. contol panels etc.
SKU: PT600 -
Electro, LED LIGHTS, LIGHTING, OUTDOOR LIGHTS
Philips Lighting LED Streetlight BRP492 LED215/NW 150W 220-240V DM GM (21500 lm)- 4000K Philip
Electro, LED LIGHTS, LIGHTING, OUTDOOR LIGHTSPhilips Lighting LED Streetlight BRP492 LED215/NW 150W 220-240V DM GM (21500 lm)- 4000K Philip
RoadFlair Gen2
BRP492 LED215/NW 150W 220-240V DM GM
RoadFlair Gen2 – 21500 lm – 150 W – 4000 K
RoadFlair Gen2 is brand new design road lighting product family, set to meet customers’ all-round requirements, including high lumen efficacy for energy saving and sustainability, aesthetic design for nice shape and appearance, quality material and components for product reliability and long lifetime, professional optics for various applications fulfillment, dimming and system control interface for improving municipal operations and offering future-proof features. RoadFlair Gen2 competitive price would help on the acceleration of road lighting LED transformation, to a more sustainable society and smarter city.
Product data
General Information
Light source color – 740 neutral white
Driver included – Yes
Optical cover/lens type – Polycarbonate micro lens optic
Control interface – Analog
Connection – Screw connection block 3-pole
Cable –
Protection class IEC – Safety class I
CE mark CE markOperating and Electrical
Input Voltage – 220 to 240 V
Input Frequency – 50 or 60 Hz
Power Factor (Min) – 0.95Luminous flux tolerance – +/-10%
Initial LED luminaire efficacy – 140 lm/W
Init. Corr. Color Temperature – 4000 K
Init. Color Rendering Index – >70
Initial input power – 150 W
Power consumption tolerance – +/-10%Application Conditions
Ambient temperature range – -40 to +50 °CProduct Data
Full product code – 911401673406SKU: n/a -
Electro, SCHNEIDER SECTIONS, Schneider Thorsman Testmeters
Thorsman Digital Clamp Test Meter IMT23114
Electro, SCHNEIDER SECTIONS, Schneider Thorsman TestmetersThorsman Digital Clamp Test Meter IMT23114
Main range Thorsmanproduct or component type Test metersupply 2 battery 3 VComplementary display digits 3.5type of setting Automatic resetsignaling function Low battery by visualfunction available High precision measuring
Audible continuity
Tactile barrier for safety
Data hold functiontype of measurement Voltage DC: 200mV/2/20/200/600 V
Resistance: 200 Ohm/2/20/200 kOhm/20 MOhm
Voltage AC: 2/20/200/600 V
Current AC: 2/20/200/600 A
Continuity: < 30 Ohm
Diode check: 1.5 Vmeasurement category Category III 600 Vlanguage Finnish
Swedish
Danish
Norwegian
Englishheight 190 mmwidth 76 mmdepth 36 mmnet weight 160 g with batterySKU: n/a -
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 4P 10A C Miniature Circuit breaker A9F44410
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 4P 10A C Miniature Circuit breaker A9F44410
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 4Pnumber of protected poles 4[In] rated current 10 Anetwork type AC/DCtrip unit technology Thermal-magneticcurve code Cbreaking capacity 6 kA Icu at 100…133 V DC conforming to EN/IEC 60947-2
6000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1
36 kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
20 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 440 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 27 kA 75 % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz
15 kA 75 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 75 % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz
4.5 kA 75 % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz
6000 A 100 % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz
6 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 8height 85 mmwidth 72 mmdepth 78.5 mmnet weight 0.5 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockSKU: n/a