Easy9 miniature circuit breaker- 3P – 20 A – C curve – 6000 A – 400 V EZ9F56320
range |
Easy9
|
|
---|---|---|
device application |
Distribution
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
Easy9 MCB
|
|
Poles |
3P
|
|
number of protected poles |
3
|
|
[In] rated current |
20 A
|
|
network type |
AC
|
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
10000 A Icn at 220 V AC 50/60 Hz conforming to IEC 60898-1
6000 A Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1 |
|
suitability for isolation |
Yes conforming to IEC 60898-1
|
network frequency |
50 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
220 V AC 50/60 Hz
400 V AC 50/60 Hz |
|
magnetic tripping limit |
5…10 x In
|
|
[Ics] rated service breaking capacity |
6 kA 100 % x Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1
|
|
[Ui] rated insulation voltage |
500 V AC 50/60 Hz conforming to IEC 60898-1
|
|
[Uimp] rated impulse withstand voltage |
4 kV conforming to IEC 60898-1
|
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Without
|
|
mounting mode |
Clip-on
|
|
mounting support |
DIN rail
|
|
9 mm pitches |
6
|
|
height |
81 mm
|
|
width |
54 mm
|
|
depth |
66.5 mm
|
|
colour |
Grey (RAL 7035)
|
|
mechanical durability |
10000 cycles
|
|
electrical durability |
4000 cycles
|
|
connections – terminals |
Tunnel type terminal (top or bottom) 1…25 mm² rigid
Tunnel type terminal (top or bottom) 1…16 mm² flexible |
|
tightening torque |
2 N.m top or bottom
|
₦4,399.00
Compare-
CHINT
Voltage Monitoring Relay XJ3-D
XJ3 series phase failure phase sequence protection relay
www.finglai.comModel number ad parametersModel number XJ3-G XJ3-S XJ3-D Related product Order Order Visiting… Phase failure protection √ √ √ Phase wrong protection √ √ √ Overvoltage protection Χ Χ 380V-460V 1.5s-4s(Adjustable) Undervoltage protection Χ Χ 300V-380V 2s-9s (Adjustable) Contact form SPST-NO and SPST-NC SPST-NO and SPST-NC SPDT Action delay time 2s max 2s max 2s max External dimensions 85x46x110 mm 85x46x110 mm 70.5×45.5×115 mm Mounting type Device or din rail Device or din rail 35mm din rail or punch Model number XJ3 series Supply voltage 380VAC 50Hz Contact rating Ue/le AC-15 380V/0.95A Ith 5A Electrical life 1×105 Mechanical life 1×106 Operational temperature -5°C-40°C SKU: n/a -
LIGHT SWITCHES & ELECTRICAL SOCKETS, SCHNEIDER SECTIONS
Ultimate Screwless flat plate – shaver socket – stainless steel/white GU7490WSS
LIGHT SWITCHES & ELECTRICAL SOCKETS, SCHNEIDER SECTIONSUltimate Screwless flat plate – shaver socket – stainless steel/white GU7490WSS
Main range of product Ultimateaesthetic name Screwless flat plateproduct or component type Shaver socketinput voltage 230 V AC 50 Hzcolour tint Stainless steel matt
WhiteComplementary material Steelfixing mode By screws M3.5 x 30 mmdevice mounting Flushconnections – terminals Screw terminalsquantity per set Set of 1height 148 mmwidth 88 mmdepth 47 mmSKU: n/a -
CEILING LIGHTS, ELECTRICAL FITTINGS, Electro, HOME&OFFICE LIGHTING, INTERIOR LIGHTING, LED LIGHTS, LIGHTING, MODULAR FITTING
AKT LED Edge Lit Troffer Panel Lights 600 x 600 Modular
CEILING LIGHTS, ELECTRICAL FITTINGS, Electro, HOME&OFFICE LIGHTING, INTERIOR LIGHTING, LED LIGHTS, LIGHTING, MODULAR FITTINGAKT LED Edge Lit Troffer Panel Lights 600 x 600 Modular
AKT LIGHTING led flat panel Edge Lit Troffer Light Ceiling Light 2pack
AKT LIGHTING 2 Pack LED Panel Light:
6500K – 4000lm Daylight White Flat LED Troffer Light Panel Fixture for Office DLC UL
Energy Saving Close Fixture Light:
40W/50W, save energy, more suitable for commercial offices, supermarkets, hospital, etc, easy to drop and install.
Features
1. Bright light, soft, not harsh.
2. Easy to install, can be used for integrated ceiling.
3. Constant current driver, no strobe, waterproof and heat dissipation, long service life
4. Energy saving and power saving, more than 85% power saving compared to incandescent lamps.
SKU: n/a -
CHINT
CHINT BH-0.66I Current Transformers from 100/5A to 6000/5A
General
To be used in combination with measurement instruments; ammeters, watt-hour meters, measurement units, control relays, etc
Operating Conditions
Secondary current Isn: 5A
Rated voltage Ue:660V
Frequency/L 50Hz/60Hz
Operating temperature: 5oC to +40oC, humidity C80%
Altitude: <1000m
SKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 4P 1A C Miniature Circuit breaker A9F44401
Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 4P 1A C Miniature Circuit breaker A9F44401
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 4Pnumber of protected poles 4[In] rated current 1 Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 50 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
50 kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
50 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
25 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
6 kA Icu at 100…133 V DC conforming to EN/IEC 60947-2
6000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 440 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 50 kA 100 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
50 kA 100 % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz
50 kA 100 % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz
25 kA 100 % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz
6000 A 100 % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz
6 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 8height 85 mmwidth 72 mmdepth 78.5 mmnet weight 0.5 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockEnvironment standards EN/IEC 60898-1
EN/IEC 60947-2IP degree of protection IP20 conforming to IEC 60529pollution degree 3 conforming to EN/IEC 60947-2tropicalisation 2 conforming to IEC 60068-1relative humidity 95 % at 55 °Cambient air temperature for operation -35…70 °Cambient air temperature for storage -40…85 °CSKU: n/a
There are no reviews yet.