Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Easy9 miniature circuit breaker- 4P – 6 A – C curve – 6000 A – 400 V EZ9F56406
range |
Easy9
|
|
---|---|---|
device application |
Distribution
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
Easy9 MCB
|
|
Poles |
4P
|
|
number of protected poles |
4
|
|
[In] rated current |
6Â A
|
|
network type |
AC
|
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
10000Â A Icn at 220 V AC 50/60 Hz conforming to IEC 60898-1
6000Â A Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1 |
|
suitability for isolation |
Yes conforming to IEC 60898-1
|
network frequency |
50 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
220 V AC 50/60 Hz
400 V AC 50/60 Hz |
|
magnetic tripping limit |
5…10 x In
|
|
[Ics] rated service breaking capacity |
6Â kA 100Â % x Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1
|
|
[Ui] rated insulation voltage |
500Â V AC 50/60 Hz conforming to IEC 60898-1
|
|
[Uimp] rated impulse withstand voltage |
4Â kV conforming to IEC 60898-1
|
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Without
|
|
mounting mode |
Clip-on
|
|
mounting support |
DIN rail
|
|
9 mm pitches |
8
|
|
height |
81Â mm
|
|
width |
72Â mm
|
|
depth |
66.5Â mm
|
|
colour |
Grey (RAL 7035)
|
|
mechanical durability |
10000Â cycles
|
|
electrical durability |
4000Â cycles
|
|
connections – terminals |
Tunnel type terminal (top or bottom) 1…25 mm² rigid
Tunnel type terminal (top or bottom) 1…16 mm² flexible |
|
tightening torque |
2Â N.m top or bottom
|
₦14,500.00
Compare-
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Easy9 miniature circuit breaker- 1P – 16 A – C curve – 6000 A – 230 V
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSEasy9 miniature circuit breaker- 1P – 16 A – C curve – 6000 A – 230 V
Main range Easy9device application Distributionproduct or component type Miniature circuit-breakerdevice short name Easy9 MCBPoles 1Pnumber of protected poles 1[In] rated current 16Â Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 6000Â A Icn at 230 V AC 50/60 Hz conforming to IEC 60898-1
10000Â A Icn at 127 V AC 50/60 Hz conforming to IEC 60898-1suitability for isolation Yes conforming to IEC 60898-1Complementary network frequency 50 Hz[Ue] rated operational voltage 230 V AC 50 Hz
127 V AC 50 Hzmagnetic tripping limit 5…10 x In[Ics] rated service breaking capacity 6 kA 100 % x Icn at 230 V AC 50/60 Hz conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to IEC 60898-1[Uimp] rated impulse withstand voltage 4 kV conforming to IEC 60898-1contact position indicator Yescontrol type Togglelocal signalling Withoutmounting mode Clip-onmounting support DIN rail9 mm pitches 2height 81 mmwidth 18 mmdepth 66.5 mmcolour Grey (RAL 7035)mechanical durability 10000 cycleselectrical durability 4000 cyclesconnections – terminals Tunnel type terminal (top or bottom) 1…25 mm² rigid
Tunnel type terminal (top or bottom) 1…16 mm² flexibletightening torque 2 N.m top or bottomSKU: n/a -
Schneider "Consort Dado" Trunking, SCHNEIDER SECTIONS
Mita – Consort Dado – internal corner – 100 x 50 mm CTI105W
Schneider "Consort Dado" Trunking, SCHNEIDER SECTIONSMita – Consort Dado – internal corner – 100 x 50 mm CTI105W
Main range of product Mitaproduct name Consort Dadoproduct or component type Internal cornercolour tint Whitequantity per set Set of 1Complementary fixing mode Clip-onmaterial with surface finish UPVC (unplasticized polyvinyl chloride)Environment ambient air temperature for operation -5…60 °CPacking Units Unit Type of Package 1 PCENumber of Units in Package 1 1Package 1 Weight 62 gPackage 1 Height 8.8 cmPackage 1 width 8.8 cmPackage 1 Length 10.3 cmSKU: n/a -
ELECTRICAL FITTINGS, Electro, FLUORESCENT FITTINGS, HOME&OFFICE LIGHTING, INDOOR LIGHTS, LED LIGHTS, LIGHTING, OUTDOOR FITTINGS, OUTDOOR LIGHTS
PHILIPS WATERPROOF BATTEN WT120C G2 LED60S/840 PSU L1500(Neutral White, 5FT) CoreLine Waterproof
ELECTRICAL FITTINGS, Electro, FLUORESCENT FITTINGS, HOME&OFFICE LIGHTING, INDOOR LIGHTS, LED LIGHTS, LIGHTING, OUTDOOR FITTINGS, OUTDOOR LIGHTSPHILIPS WATERPROOF BATTEN WT120C G2 LED60S/840 PSU L1500(Neutral White, 5FT) CoreLine Waterproof
Light Technical
- Luminous Flux                       –  6,000 lm
- Correlated Color Temperature (Nom)Â Â Â –Â Â 4000 K
- Luminous Efficacy (rated) (Nom)Â Â Â Â Â Â –Â Â Â 140 lm/W
- Color rendering index (CRI)Â Â Â Â Â Â Â Â Â Â Â Â Â Â >80
- Flickering value (PstLM)Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â 1
- Stroboscopic effect value (SVM)Â Â Â Â Â Â Â Â Â Â 1.6
- Light source color                       840 neutral white
- Optic type                              Wide beam
- Luminaire light beam spread             105°
- Unified glare rating CENÂ Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â 25
Mechanical and Housing
- Housing Material                  –  Polycarbonate
- Reflector material                  –  Steel
- Optic material                     –  Polycarbonate
- Optical cover material              –  Polycarbonate
- Fixation material                  –  Stainless steel
- Housing Color                     –  Gray
- Optical cover finish                –  Matte
- Overall length                     –  1,515 mm
- Overall width                      –  80 mm
- Overall height                      – 76 mm
- Dimensions (Height x Width x Depth)Â –Â 76 x 80 x 1515 mm
SKU: n/a -
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 2P 10A C Miniature Circuit breaker A9F44210
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 2P 10A C Miniature Circuit breaker A9F44210
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 2Pnumber of protected poles 2[In] rated current 10Â Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 6Â kA Icu at 100…133 V DC conforming to EN/IEC 60947-2
6000Â A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1
36Â kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
20Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
10Â kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
6Â kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 440 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 27Â kA 75Â % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz
15Â kA 75Â % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5Â kA 75Â % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz
4.5Â kA 75Â % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz
6000Â A 100Â % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz
6 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 4height 85 mmwidth 36 mmdepth 78.5 mmnet weight 0.25 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockEnvironment standards EN/IEC 60947-2
EN/IEC 60898-1IP degree of protection IP20 conforming to IEC 60529pollution degree 3 conforming to EN/IEC 60947-2tropicalisation 2 conforming to IEC 60068-1relative humidity 95 % at 55 °Cambient air temperature for operation -35…70 °Cambient air temperature for storage -40…85 °CSKU: n/a -