Schneider Circuit Breakers, SCHNEIDER SECTIONS
Easy9 Residual Current Circuit Breaker – 4P – 40A – 30 mA – AC type – 400 V EZ9R34440
range of product |
Easy9
|
|
---|---|---|
product or component type |
Residual current circuit breaker (RCCB)
|
|
device short name |
Easy9 RCCB
|
|
Poles |
4P
|
|
neutral position |
Left
|
|
[In] rated current |
40 A
|
|
network type |
AC
|
|
earth-leakage sensitivity |
30 mA
|
|
earth-leakage protection time delay |
Instantaneous
|
|
earth-leakage protection class |
Type AC
|
|
rated breaking and making capacity |
500 A
|
|
rated conditional short-circuit current |
Easy9 MCB: 4500 A 40 A
|
device location in system |
Outgoer
|
|
---|---|---|
network frequency |
50 Hz
|
|
[Ue] rated operational voltage |
400 V AC 50 Hz
|
|
residual current tripping technology |
Voltage independent
|
|
[Ui] rated insulation voltage |
440 V AC
|
|
[Uimp] rated impulse withstand voltage |
4 kV
|
|
surge current |
250 A
|
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
mounting mode |
Clip-on
|
|
mounting support |
DIN rail
|
|
comb busbar and distribution block compatibility |
Top: YES
|
|
9 mm pitches |
8
|
|
height |
82 mm
|
|
width |
72 mm
|
|
depth |
72 mm
|
|
colour |
Grey (RAL 7035)
|
|
mechanical durability |
5000 cycles
|
|
electrical durability |
AC: 2000 cycles 400 V AC 50 Hz
|
|
connections – terminals |
Tunnel type terminal (top or bottom) 1…35 mm² rigid
Tunnel type terminal (top or bottom) 1…25 mm² flexible |
|
tightening torque |
3.5 N.m top or bottom
|
|
market segment |
Small commercial
Residential |
₦19,999.00
Compare-
LIGHT SWITCHES & ELECTRICAL SOCKETS
Lisse – Plate switch – 4 gang 2 way – 10AX – white GGBL1042
Main range Lisseaesthetic name White mouldedproduct or component type Plate switchdevice presentation Complete productcolour tint Whitequantity per set Set of 5Complementary switch function 2-waycontrol type Rockernumber of gangs 4 gangsdevice mounting Wall mountedrated current 10 AX at 230 V ACconnections – terminals Screw terminalsmaterial Urea (carbamide)surface finish Matttype of packing Cartonheight 149 mmwidth 87 mmdepth 24 mmnet weight 0.015 kgSKU: n/a -
ELECTRICAL FITTINGS, Electro, HOME&OFFICE LIGHTING, INDOOR LIGHTS, INTERIOR LIGHTING
Vellmax 50W LED Modular Fitting 600 x 600
ELECTRICAL FITTINGS, Electro, HOME&OFFICE LIGHTING, INDOOR LIGHTS, INTERIOR LIGHTINGVellmax 50W LED Modular Fitting 600 x 600
- Panel Light
- Modular fitting
LED Panels are the most effective way to light large open plan areas. They are used in hotels, airports, hospitals, office buildings, supermarkets etc.Benefits for LED panel lights; Vellmax LED lighting panels are the energy-efficient alternative to fluorescent grill lights. Choosing high-performance LED panel lighting means many times greater luminosity, with far less energy wasted on heat.
SKU: n/a -
CIRCUIT BREAKERS
IC60N – miniature circuit breaker – 3P – 63A – C curve
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 3Pnumber of protected poles 3[In] rated current 63 Anetwork type DC
ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
36 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
20 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
36 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at <= 180 V DC conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards EN 60898-1
EN 60947-2
IEC 60898-1
IEC 60947-2Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 15 kA 75 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 75 % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz
4.5 kA 75 % conforming to EN 60947-2 – 440 V AC 50/60 Hz
15 kA 75 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 75 % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz
4.5 kA 75 % conforming to IEC 60947-2 – 440 V AC 50/60 Hz
27 kA 75 % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz
27 kA 75 % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz
6000 A 100 % conforming to EN 60898-1 – 400 V AC 50/60 Hz
6000 A 100 % conforming to IEC 60898-1 – 400 V AC 50/60 Hz
10 kA 100 % conforming to IEC 60947-2 – 125…180 V DC
10 kA 100 % conforming to EN 60947-2 – 125…180 V DC[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 6height 85 mmwidth 54 mmdepth 78.5 mmnet weight 0.375 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 3.5 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
ELECTRICAL FITTINGS, Electro, FLUORESCENT FITTINGS, INDOOR LIGHTS, LED LIGHTS, LIGHTING, OUTDOOR LIGHTS
PHILIPS WATERPROOF BATTEN WT120C G2 LED40S/840 PSU L1200(Neutral White, 4FT) CoreLine Waterproof
ELECTRICAL FITTINGS, Electro, FLUORESCENT FITTINGS, INDOOR LIGHTS, LED LIGHTS, LIGHTING, OUTDOOR LIGHTSPHILIPS WATERPROOF BATTEN WT120C G2 LED40S/840 PSU L1200(Neutral White, 4FT) CoreLine Waterproof
Light Technical
- Luminous Flux – 4,000 lm
- Correlated Color Temperature (Nom) – 4000 K
- Luminous Efficacy (rated) (Nom) – 140 lm/W
- Color rendering index (CRI) >80
- Flickering value (PstLM) 1
- Stroboscopic effect value (SVM) 1.6
- Light source color 840 neutral white
- Optic type Wide beam
- Luminaire light beam spread 105°
- Unified glare rating CEN 25
Mechanical and Housing
- Housing Material – Polycarbonate
- Reflector material – Steel
- Optic material – Polycarbonate
- Optical cover material – Polycarbonate
- Fixation material – Stainless steel
- Housing Color – Gray
- Optical cover finish – Matte
- Overall length – 1,215 mm
- Overall width – 80 mm
- Overall height – 76 mm
- Dimensions (Height x Width x Depth) – 76 x 80 x 1215 mm
SKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Miniature circuit-breaker, Acti9 iC60H, 1P, 6 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84106
Schneider Circuit Breakers, SCHNEIDER SECTIONSMiniature circuit-breaker, Acti9 iC60H, 1P, 6 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84106
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Hpoles description 1Pnumber of protected poles 1[In] rated current 6 Anetwork type AC
DCtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
15 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
42 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
30 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at 60…72 V DC conforming to EN/IEC 60947-2
20 kA Icu at 12…60 V DC conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards EN 60898-1
IEC 60947-2
IEC 60898-1
EN 60947-2Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 21 kA 50 % conforming to EN 60947-2 – 12…60 V AC 50/60 Hz
7.5 kA 50 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
21 kA 50 % conforming to IEC 60947-2 – 12…60 V AC 50/60 Hz
7.5 kA 50 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7500 A 75 % conforming to EN 60898-1 – 230 V AC 50/60 Hz
7500 A 75 % conforming to IEC 60898-1 – 230 V AC 50/60 Hz
15 kA 50 % conforming to IEC 60947-2 – 100…133 V AC 50/60 Hz
15 kA 50 % conforming to EN 60947-2 – 100…133 V AC 50/60 Hz
15 kA 100 % conforming to EN 60947-2 – 72 V DC
15 kA 100 % conforming to IEC 60947-2 – 72 V DC
20 kA 100 % conforming to EN 60947-2 – 12…60 V DC
20 kA 100 % conforming to IEC 60947-2 – 12…60 V DClimitation class 3 conforming to EN 60898-1
3 conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 2height 85 mmwidth 18 mmdepth 78.5 mmnet weight 0.215 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection WithoutSKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 4P 1A C Miniature Circuit breaker A9F44401
Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 4P 1A C Miniature Circuit breaker A9F44401
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 4Pnumber of protected poles 4[In] rated current 1 Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 50 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
50 kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
50 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
25 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
6 kA Icu at 100…133 V DC conforming to EN/IEC 60947-2
6000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 440 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 50 kA 100 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
50 kA 100 % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz
50 kA 100 % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz
25 kA 100 % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz
6000 A 100 % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz
6 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 8height 85 mmwidth 72 mmdepth 78.5 mmnet weight 0.5 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockEnvironment standards EN/IEC 60898-1
EN/IEC 60947-2IP degree of protection IP20 conforming to IEC 60529pollution degree 3 conforming to EN/IEC 60947-2tropicalisation 2 conforming to IEC 60068-1relative humidity 95 % at 55 °Cambient air temperature for operation -35…70 °Cambient air temperature for storage -40…85 °CSKU: n/a
There are no reviews yet.