EZC100F3080 – Circuit breaker Easypact EZC100F – TMD – 80 A – 3 poles 3d
range of product |
EasyPact
|
|
---|---|---|
product or component type |
Circuit breaker
|
|
device short name |
Easypact EZC100F
|
|
circuit breaker name |
Easypact EZC100F
|
|
device application |
Distribution
|
|
poles description |
3P
|
|
protected poles description |
3t
|
|
network type |
AC
DC |
|
network frequency |
50/60 Hz
|
|
[In] rated current |
100 A at 40 °C
|
|
[Ui] rated insulation voltage |
690 V AC 50/60 Hz conforming to IEC 60947-2
|
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to IEC 60947-2
|
|
[Ue] rated operational voltage |
550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2 |
|
breaking capacity code |
F
|
|
breaking capacity |
25 kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 125 V DC 1P conforming to IEC 60947-2 5 kA Icu at 250 V DC 2P conforming to IEC 60947-2 5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 400…415 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Ics] rated service breaking capacity |
12.5 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 125 V DC conforming to IEC 60947-2 2.5 kA at 250 V DC conforming to IEC 60947-2 2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 5 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 3.75 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to IEC 60947-2
|
|
utilisation category |
Category A
|
|
trip unit name |
TM-D
|
|
trip unit technology |
Thermal-magnetic
|
|
trip unit rating |
80 A at 50 °C
|
|
protection type |
Short-circuit protection
Overload protection |
|
pollution degree |
3 conforming to IEC 60664-1
3 conforming to IEC 947-1 |
control type |
Toggle
|
|
---|---|---|
mounting mode |
Fixed
|
|
mounting support |
Backplate
|
|
upside connection |
Front
|
|
downside connection |
Front
|
|
mechanical durability |
8500 cycles
|
|
electrical durability |
Category A: 1500 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
|
|
connection pitch |
25 mm
|
|
local signalling |
Positive contact indication
|
|
neutral protection setting |
Without protection
|
|
earth-leakage protection |
Without
|
|
height |
130 mm
|
|
width |
75 mm
|
|
depth |
60 mm
|
₦70,500.00
Compare-
Electro, Low Voltage Products and Systems, SCHNEIDER SECTIONS
EZC100N4030 – Circuit breaker Easypact EZC100N – TMD – 30 A – 4 poles 3d
Electro, Low Voltage Products and Systems, SCHNEIDER SECTIONSEZC100N4030 – Circuit breaker Easypact EZC100N – TMD – 30 A – 4 poles 3d
Main range of product EasyPactproduct or component type Circuit breakerdevice short name Easypact EZC100Ncircuit breaker name Easypact EZC100Ndevice application Distributionpoles description 4Pprotected poles description 3tnetwork type AC
DCnetwork frequency 50/60 Hz[In] rated current 100 A at 40 °C[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2[Ue] rated operational voltage 550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2breaking capacity code Nbreaking capacity 10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
5 kA Icu at 125 V DC 1P conforming to IEC 60947-2
5 kA Icu at 250 V DC 2P conforming to IEC 60947-2
5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
15 kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2
18 kA Icu at 380…400 V AC 50/60 Hz conforming to IEC 60947-2[Ics] rated service breaking capacity 5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
2.5 kA at 125 V DC conforming to IEC 60947-2
2.5 kA at 250 V DC conforming to IEC 60947-2
2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
9 kA at 380…400 V AC 50/60 Hz conforming to IEC 60947-2
7.5 kA at 415 V AC 50/60 Hz conforming to IEC 60947-2suitability for isolation Yes conforming to IEC 60947-2utilisation category Category Atrip unit name TM-Dtrip unit technology Thermal-magnetictrip unit rating 30 A at 50 °Cprotection type Overload protection
Short-circuit protectionpollution degree 3 conforming to IEC 60947Complementary control type Togglemounting mode Fixedmounting support Backplateupside connection Frontdownside connection Frontmechanical durability 8500 cycleselectrical durability Category A: 1500 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2connection pitch 25 mmlocal signalling Positive contact indicationneutral protection setting Without protectionearth-leakage protection Withoutheight 130 mmwidth 100 mmdepth 60 mmSKU: n/a -
Electro, LED LIGHTS, LIGHTING, OUTDOOR LIGHTS
12W Underground Light Lamps Outdoor Buried Recessed Floor LED Waterproof IP67
Electro, LED LIGHTS, LIGHTING, OUTDOOR LIGHTS12W Underground Light Lamps Outdoor Buried Recessed Floor LED Waterproof IP67
Applications:
square, restaurant, Private, villas, garden, meeting room, exhibition hall, District environment beautification, Stage bar, supermarket, Parking sculpture, Tourist attractions and other placesSKU: n/a -
CIRCUIT BREAKERS
Circuit breaker Easypact EZC100H – TMD – 63 A – 4 poles 3d
Main range of product EasyPactproduct or component type Circuit breakerdevice short name Easypact EZC100Hcircuit breaker name Easypact EZC100Hdevice application Distributionpoles description 4Pprotected poles description 3tnetwork type AC
DCnetwork frequency 50/60 Hz[In] rated current 100 A at 40 °C[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2[Ue] rated operational voltage 550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2breaking capacity code Hbreaking capacity 10 kA Icu at 125 V DC 1P conforming to IEC 60947-2
10 kA Icu at 250 V DC 2P conforming to IEC 60947-2
10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
30 kA Icu at 380…400 V AC 50/60 Hz conforming to IEC 60947-2
30 kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2[Ics] rated service breaking capacity 5 kA at 125 V DC conforming to IEC 60947-2
5 kA at 250 V DC conforming to IEC 60947-2
5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2
15 kA at 380…400 V AC 50/60 Hz conforming to IEC 60947-2
25 kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
7.5 kA at 415 V AC 50/60 Hz conforming to IEC 60947-2suitability for isolation Yes conforming to IEC 60947-2utilisation category Category Atrip unit name TM-Dtrip unit technology Thermal-magnetictrip unit rating 63 A at 50 °Cprotection type Overload protection
Short-circuit protectionpollution degree 3 conforming to IEC 60947Complementary control type Togglemounting mode Fixedmounting support Backplateupside connection Frontdownside connection Frontmechanical durability 8500 cycleselectrical durability Category A: 1500 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2connection pitch 25 mmlocal signalling Positive contact indicationneutral protection setting Without protectionearth-leakage protection Withoutheight 130 mmwidth 100 mmdepth 60 mmSKU: n/a -
Electro, SOLAR POWERED
Solar Panel MR300W Mono
330W Monocrystalline solar panel has cells built in for efficiency and durability. It is waterproof and can withstand a wide range of environmental conditions.
Features
● Bypass diode minimizes the power drop by shade.● White tempered glass, EVA resin,weather proof film and anodized aluminum frame to provide efficient protection from the severest environmental conditions.● Waterproof● Perfect for grid applications.● Product guarantee 10 years.SKU: n/a -
Electro, LIGHT SWITCHES & ELECTRICAL SOCKETS
Schneider 13A 250V 1 Gang Switched Socket with Neon KB15N
Electro, LIGHT SWITCHES & ELECTRICAL SOCKETSSchneider 13A 250V 1 Gang Switched Socket with Neon KB15N
Main range Vivaceproduct or component type Socket-outlet with switchdevice short name KB15device presentation Complete mechanismComplementary pilot light Red neon indicatoroutlet poles configuration 2P + Enumber of gangs 1 gangColour tint Whitematerial Polycarbonate: grid plate
Polycarbonate: surround
Polycarbonate: baseprojecting depth 8 mmdevice mounting Flushmounting support Wall mountedfixing mode By screw M3.5fixing center 60.3 mmembedding depth 35 mmrated current 13 A at 250 V AC, resistivenetwork frequency 50 Hzcontacts material Brass and phosphor bronzeconnections – terminals Pillar terminalterminal identifier N
L
Earthtightening torque 0.4 N.mclamping connection capacity 2 x 4 mm²
3 x 2.5 mm²width 87 mmheight 87 mmSKU: n/a -
CABLE AND CABLE MANAGEMENT, Electro, SINGLE CORE WIRE
Doncaster Cables 2.5mm Single Core – Black
Product Description
Manufactured to BS 6004:2012 Table 3
Annealed Stranded Copper Conductor / PVC Insulated / PVC Sheathed. 300/500V
Designed for use in light industrial and domestic wiring. These cables are particularly suited for installation as meter tails and are intended for fixed installation in dry or damp premises.
These cables can be installed in conduit, in cable trunking and in cable ducting. Or where there is deemed little risk of mechanical damage these cables can be clipped direct, on cable tray, embedded or in free air. These cables are not intended to be laid underground.
Product Details
Harmonisation Code Nominal Cross Sectional Area of Conductor (mm2) Nominal Stranding of Conductor (mm) Nominal Radial Thickness of insulation (mm) Nominal Radial Thickness of sheath (mm) Overall Diameter Lower Limit (mm) Overall Diameter Upper Limit (mm) Approximate Weight(kg/km) National Type 1.0 1 / 1.13 0.6 0.8 3.8 4.5 26 National Type 1.5 1 / 1.38 0.7 0.8 4.2 4.9 35 National Type 2.5 1 / 1.78 0.8 0.8 4.8 5.8 55 National Type 4.0 7 / 0.85 0.8 0.9 5.4 6.8 75 National Type 6.0 7 / 1.04 0.8 0.9 6.0 7.4 95 National Type 10.0 7 / 1.35 1.0 0.9 7.2 8.8 155 National Type 16.0 7 / 1.70 1.0 1.0 8.4 10.5 225 National Type 25.0 7 / 2.14 1.2 1.1 10.0 12.5 340 National Type 35.0 7 / 2.52 1.2 1.1 11.0 13.5 445 SKU: n/a
There are no reviews yet.