EZC100F3080 – Circuit breaker Easypact EZC100F – TMD – 80 A – 3 poles 3d
range of product |
EasyPact
|
|
---|---|---|
product or component type |
Circuit breaker
|
|
device short name |
Easypact EZC100F
|
|
circuit breaker name |
Easypact EZC100F
|
|
device application |
Distribution
|
|
poles description |
3P
|
|
protected poles description |
3t
|
|
network type |
AC
DC |
|
network frequency |
50/60 Hz
|
|
[In] rated current |
100 A at 40 °C
|
|
[Ui] rated insulation voltage |
690Â V AC 50/60 Hz conforming to IEC 60947-2
|
|
[Uimp] rated impulse withstand voltage |
6Â kV conforming to IEC 60947-2
|
|
[Ue] rated operational voltage |
550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2 |
|
breaking capacity code |
F
|
|
breaking capacity |
25Â kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
25Â kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2 5Â kA Icu at 125 V DC 1P conforming to IEC 60947-2 5Â kA Icu at 250 V DC 2P conforming to IEC 60947-2 5Â kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 10Â kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 10Â kA Icu at 400…415 V AC 50/60 Hz conforming to IEC 60947-2 7.5Â kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Ics] rated service breaking capacity |
12.5Â kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2
12.5Â kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 2.5Â kA at 125 V DC conforming to IEC 60947-2 2.5Â kA at 250 V DC conforming to IEC 60947-2 2.5Â kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 5Â kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 5Â kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 3.75Â kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to IEC 60947-2
|
|
utilisation category |
Category A
|
|
trip unit name |
TM-D
|
|
trip unit technology |
Thermal-magnetic
|
|
trip unit rating |
80 A at 50 °C
|
|
protection type |
Short-circuit protection
Overload protection |
|
pollution degree |
3 conforming to IEC 60664-1
3 conforming to IEC 947-1 |
control type |
Toggle
|
|
---|---|---|
mounting mode |
Fixed
|
|
mounting support |
Backplate
|
|
upside connection |
Front
|
|
downside connection |
Front
|
|
mechanical durability |
8500Â cycles
|
|
electrical durability |
Category A: 1500Â cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
|
|
connection pitch |
25Â mm
|
|
local signalling |
Positive contact indication
|
|
neutral protection setting |
Without protection
|
|
earth-leakage protection |
Without
|
|
height |
130Â mm
|
|
width |
75Â mm
|
|
depth |
60Â mm
|
₦70,500.00
Compare-
CHANGEOVER SWITCHES, Electro, GEAR SWITCHES & CHANGEOVER
ABB CHANGEOVER SWITCH 630A with Enclosure
Including a black plastic IP65 I-0-II pistol type handle (see the table below), shaft and bolt set for the cable connection. Handle padlockable in the 0-position, door interlock in the I- and Iipositions and when padlocked.
Categories
- Products » Low Voltage Products and Systems » Switches » Change-over and Transfer Switches » Manual Change-over Switches
Dimensions
-
- Product Net Width:Â 376Â mm
-
- Product Net Height:Â 250Â mm
-
- Product Net Depth / Length:Â 280Â mm
-
- Product Net Weight:Â Â 18.51 kg
- Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â 40.81 lb
Technical
-
- Rated Operational Current AC-21A (Ie):
- (380 … 415 V) 630 A
(500 V) 630 A
(690 V) 630 A
-
- Rated Operational Current AC-22A (Ie):
- (380 … 415 V) 630 A
(500 V) 630 A
(690 V) 630 A
-
- Rated Operational Current AC-23A (Ie):
- (380 … 415 V) 630 A
(500 V) 630 A
(690 V) 630 A
-
- Rated Operational Current AC-31B (Ie):
- (380 … 415 V) 630 A
-
- Rated Operational Current AC-33B (Ie):
- (380 … 415 V) 630 A
-
- Rated Operational Power AC-23A (Pe):
- (380 … 415 V) 355 kW
(500 V) 400 kW
(690 V) 630 kW
SKU: n/a -
Electro, LIGHT SWITCHES & ELECTRICAL SOCKETS
Schneider 1 Gang TV Coaxial Outlet + 1 Gang TVF Socket KB32TV_TVF
Electro, LIGHT SWITCHES & ELECTRICAL SOCKETSSchneider 1 Gang TV Coaxial Outlet + 1 Gang TVF Socket KB32TV_TVF
Main range of product Vivacerange Vivacedevice short name KB32product or component type TV/TVF socketdevice presentation Complete mechanismComplementary number of gangs 1 gangnumber of outputs 1Colour tint Whitematerial Polycarbonate: surround
Polycarbonate: grid plate
Polycarbonate: baseprojecting depth 8Â mmdevice mounting Flushmounting support Wall mountedfixing mode By screw M3.5fixing center 60.3 mmembedding depth 35Â mmtightening torque 0.4Â N.mwidth 146Â mmheight 86Â mmSKU: n/a -
ELECTRICAL INDUSTRIAL, TRANSFORMER
BETA 500KVA/33/0.415V COPPER/COPPER WINDING TRANSFORMER
Produced within a power range between 10 – 100.000 kVA , up to 170 kV high voltage level, three phase or single phase, oil immersed, ONAN, ONAF, OFWF, with Off-Load or On-Load Tap Changer, used both external and internal.
Dimensions of transformer conservator are determined and designed after several heat calculations of the oil stored in expansion tank and oil level changes by heat.
Being open to atmosphere, oil pressure changes continuously in Conservator Type Transformers due to thermal effects and exchange of air is dehumidified via air breather silicagel.SKU: n/a -
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 4P 4A C Miniature Circuit breaker A9F44404
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 4P 4A C Miniature Circuit breaker A9F44404
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 4Pnumber of protected poles 4[In] rated current 4Â Anetwork type AC/DCtrip unit technology Thermal-magneticcurve code Cbreaking capacity 50Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
50Â kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
50Â kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
25Â kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
6Â kA Icu at 100…133 V DC conforming to EN/IEC 60947-2
6000Â A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 440 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 50Â kA 100Â % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
50Â kA 100Â % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz
50Â kA 100Â % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz
25Â kA 100Â % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz
6000Â A 100Â % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz
6 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 8height 85 mmwidth 72 mmdepth 78.5 mmnet weight 0.5 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockEnvironment standards EN/IEC 60898-1
EN/IEC 60947-2IP degree of protection IP20 conforming to IEC 60529pollution degree 3 conforming to EN/IEC 60947-2tropicalisation 2 conforming to IEC 60068-1relative humidity 95 % at 55 °Cambient air temperature for operation -35…70 °Cambient air temperature for storage -40…85 °CSKU: n/a
There are no reviews yet.