Electro, Low Voltage Products and Systems, SCHNEIDER SECTIONS
EZC100N4016 Circuit breaker Easypact EZC100N – TMD – 16 A – 4 poles 3d
range of product |
EasyPact
|
|
---|---|---|
product or component type |
Circuit breaker
|
|
device short name |
Easypact EZC100N
|
|
circuit breaker name |
Easypact EZC100N
|
|
device application |
Distribution
|
|
poles description |
4P
|
|
protected poles description |
3t
|
|
network type |
DC
AC |
|
network frequency |
50/60 Hz
|
|
[In] rated current |
100 A at 40 °C
|
|
[Ui] rated insulation voltage |
690 V AC 50/60 Hz conforming to IEC 60947-2
|
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to IEC 60947-2
|
|
[Ue] rated operational voltage |
550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2 |
|
breaking capacity code |
N
|
|
breaking capacity |
10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 125 V DC 1P conforming to IEC 60947-2 5 kA Icu at 250 V DC 2P conforming to IEC 60947-2 5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2 18 kA Icu at 380…400 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Ics] rated service breaking capacity |
5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
2.5 kA at 125 V DC conforming to IEC 60947-2 2.5 kA at 250 V DC conforming to IEC 60947-2 2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 110…130 V AC 50/60 Hz conforming to IEC 60947-2 9 kA at 380…400 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA at 415 V AC 50/60 Hz conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to IEC 60947-2
|
|
utilisation category |
Category A
|
|
trip unit name |
TM-D
|
|
trip unit technology |
Thermal-magnetic
|
|
trip unit rating |
16 A at 50 °C
|
|
protection type |
Overload protection
Short-circuit protection |
|
pollution degree |
3 conforming to IEC 60947
|
control type |
Toggle
|
|
---|---|---|
mounting mode |
Fixed
|
|
mounting support |
Backplate
|
|
upside connection |
Front
|
|
downside connection |
Front
|
|
mechanical durability |
8500 cycles
|
|
electrical durability |
Category A: 1500 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
|
|
connection pitch |
25 mm
|
|
local signalling |
Positive contact indication
|
|
neutral protection setting |
Without protection
|
|
earth-leakage protection |
Without
|
|
height |
130 mm
|
|
width |
100 mm
|
|
depth |
60 mm
|
₦93,000.00
Compare-
Electro, Schneider Mureva Floodlight, SCHNEIDER SECTIONS
Thorsman, Worklight 30W, IP65 DK Plug 230V IMT47230
Electro, Schneider Mureva Floodlight, SCHNEIDER SECTIONSThorsman, Worklight 30W, IP65 DK Plug 230V IMT47230
Main range Thorsmanrange of product Thorsman Worklightsproduct name Worklightproduct or component type Lampdevice application Mobile equipment
Ware-houses and parking garages
Hospital
Residential
Sports hallComplementary type of installation Outdoor[Ue] rated operational voltage 230 Vnetwork type ACoperational power in W 30 Wplug standard Denmarkluminous flux 3000 lmbulb lifespan 50000 hcolour rendering index Ra=80colour temperature 4000 Kbeam angle 110 °power factor 0.9height 254.5 mmwidth 231.0 mmdepth 20.0 mmnet weight 1.1 kgSKU: n/a -
SOLAR POWERED
Solar Panel YL280W Poly
The 60-cell polycrystalline module is currently one of the strongest in the market with 280 Wp output power. Compliant with advanced load tests – meets the load requirement of 5400 Pa. By optimizing the design of solar cells and selecting the right materials, the module achieves high efficiency even in a weaker light. Due to high corrosion resistance due to salt (fog) and ammonia, the modules are also suitable for agricultural and coastal surfaces.
Package includes:
Connection cable (L) with a width of 4.0 mm2 and a length of 900 mm; the toughened glass front has low iron content and is resistant to high temperatures; frame made of anodized aluminum alloy.
SKU: n/a -
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Easy9 miniature circuit breaker- 4P – 25 A – C curve – 6000 A – 400 V EZ9F56425
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSEasy9 miniature circuit breaker- 4P – 25 A – C curve – 6000 A – 400 V EZ9F56425
Main range Easy9device application Distributionproduct or component type Miniature circuit-breakerdevice short name Easy9 MCBPoles 4Pnumber of protected poles 4[In] rated current 25 Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000 A Icn at 220 V AC 50/60 Hz conforming to IEC 60898-1
6000 A Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1suitability for isolation Yes conforming to IEC 60898-1Complementary network frequency 50 Hz[Ue] rated operational voltage 220 V AC 50/60 Hz
400 V AC 50/60 Hzmagnetic tripping limit 5…10 x In[Ics] rated service breaking capacity 6 kA 100 % x Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to IEC 60898-1[Uimp] rated impulse withstand voltage 4 kV conforming to IEC 60898-1contact position indicator Yescontrol type Togglelocal signalling Withoutmounting mode Clip-onmounting support DIN rail9 mm pitches 8height 81 mmwidth 72 mmdepth 66.5 mmcolour Grey (RAL 7035)mechanical durability 10000 cycleselectrical durability 4000 cyclesconnections – terminals Tunnel type terminal (top or bottom) 1…25 mm² rigid
Tunnel type terminal (top or bottom) 1…16 mm² flexibletightening torque 2 N.m top or bottomEnvironment standards IEC 60898-1product certifications VDE
CEIP degree of protection IP20 conforming to IEC 60529pollution degree 2tropicalisation 2relative humidity 95 % at -5…60 °Cambient air temperature for operation -5…60 °Cambient air temperature for storage -40…85 °CSKU: n/a -
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
IC60H – miniature circuit breaker – 1P – 32A – C curve A9F84132
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSIC60H – miniature circuit breaker – 1P – 32A – C curve A9F84132
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Hpoles description 1Pnumber of protected poles 1[In] rated current 32 Anetwork type DC
ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
15 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
42 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
30 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at 60…72 V DC conforming to EN/IEC 60947-2
20 kA Icu at 12…60 V DC conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards IEC 60947-2
IEC 60898-1
EN 60898-1
EN 60947-2Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 21 kA 50 % conforming to EN 60947-2 – 12…60 V AC 50/60 Hz
7.5 kA 50 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
21 kA 50 % conforming to IEC 60947-2 – 12…60 V AC 50/60 Hz
7.5 kA 50 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7500 A 75 % conforming to EN 60898-1 – 230 V AC 50/60 Hz
7500 A 75 % conforming to IEC 60898-1 – 230 V AC 50/60 Hz
15 kA 50 % conforming to IEC 60947-2 – 100…133 V AC 50/60 Hz
15 kA 50 % conforming to EN 60947-2 – 100…133 V AC 50/60 Hz
15 kA 100 % conforming to EN 60947-2 – 72 V DC
15 kA 100 % conforming to IEC 60947-2 – 72 V DC
20 kA 100 % conforming to EN 60947-2 – 12…60 V DC
20 kA 100 % conforming to IEC 60947-2 – 12…60 V DClimitation class 3 conforming to EN 60898-1
3 conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 2height 85 mmwidth 18 mmdepth 78.5 mmnet weight 0.215 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 3.5 N.m top or bottomearth-leakage protection WithoutSKU: n/a -
Electro, LIGHT SWITCHES & ELECTRICAL SOCKETS
Lisse – unswitched socket – 13 A – 1 gang – 230 V – white GGBL3050
Electro, LIGHT SWITCHES & ELECTRICAL SOCKETSLisse – unswitched socket – 13 A – 1 gang – 230 V – white GGBL3050
Main range Lisseaesthetic name White mouldedproduct or component type Unswitched socketdevice presentation Complete productoutlet standard Britishcolour tint Matt whitequantity per set Set of 10type of packing CartonComplementary switch function 1-polerated current 13 A at 250 V AC 50 Hzactuator Rockernumber of gangs 1 gangfixing mode By screwsconnections – terminals Screw terminalsmaterial Urea (carbamide)type of installation Indoordepth 27 mmwidth 87 mmheight 87 mmnet weight 0.08 kgSKU: n/a -
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 1P 25A C Miniature Circuit breaker A9F44125
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 1P 25A C Miniature Circuit breaker A9F44125
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 1Pnumber of protected poles 1[In] rated current 25 Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 15 kA Icu at 12…48 V DC conforming to EN/IEC 60947-2
6 kA Icu at 72 V DC conforming to EN/IEC 60947-2
6000 A Icn at 240 V AC 50/60 Hz conforming to EN/IEC 60898-1
36 kA Icu at 10…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
20 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 240 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 27 kA 75 % conforming to EN/IEC 60947-2 – 10…60 V AC 50/60 Hz
15 kA 75 % conforming to EN/IEC 60947-2 – 100…133 V AC 50/60 Hz
7.5 kA 75 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
6000 A 100 % conforming to EN/IEC 60898-1 – 240 V AC 50/60 Hz
15 kA 100 % conforming to EN/IEC 60947-2 – 12…48 V DC
6 kA 100 % conforming to EN/IEC 60947-2 – 72 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 2height 85 mmwidth 18 mmdepth 78.5 mmnet weight 0.125 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockSKU: n/a