EZC100N4025 – Circuit breaker Easypact EZC100N – TMD – 25 A – 4 poles 3d
range of product |
EasyPact
|
|
---|---|---|
product or component type |
Circuit breaker
|
|
device short name |
Easypact EZC100N
|
|
circuit breaker name |
Easypact EZC100N
|
|
device application |
Distribution
|
|
poles description |
4P
|
|
protected poles description |
3t
|
|
network type |
DC
AC |
|
network frequency |
50/60 Hz
|
|
[In] rated current |
100 A at 40 °C
|
|
[Ui] rated insulation voltage |
690Â V AC 50/60 Hz conforming to IEC 60947-2
|
|
[Uimp] rated impulse withstand voltage |
6Â kV conforming to IEC 60947-2
|
|
[Ue] rated operational voltage |
550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2 |
|
breaking capacity code |
N
|
|
breaking capacity |
10Â kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
25Â kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2 25Â kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2 5Â kA Icu at 125 V DC 1P conforming to IEC 60947-2 5Â kA Icu at 250 V DC 2P conforming to IEC 60947-2 5Â kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 15Â kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2 18Â kA Icu at 380…400 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Ics] rated service breaking capacity |
5Â kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
2.5Â kA at 125 V DC conforming to IEC 60947-2 2.5Â kA at 250 V DC conforming to IEC 60947-2 2.5Â kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 12.5Â kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2 12.5Â kA at 110…130 V AC 50/60 Hz conforming to IEC 60947-2 9Â kA at 380…400 V AC 50/60 Hz conforming to IEC 60947-2 7.5Â kA at 415 V AC 50/60 Hz conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to IEC 60947-2
|
|
utilisation category |
Category A
|
|
trip unit name |
TM-D
|
|
trip unit technology |
Thermal-magnetic
|
|
trip unit rating |
25 A at 50 °C
|
|
protection type |
Overload protection
Short-circuit protection |
|
pollution degree |
3 conforming to IEC 60947
|
control type |
Toggle
|
|
---|---|---|
mounting mode |
Fixed
|
|
mounting support |
Backplate
|
|
upside connection |
Front
|
|
downside connection |
Front
|
|
mechanical durability |
8500Â cycles
|
|
electrical durability |
Category A: 1500Â cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
|
|
connection pitch |
25Â mm
|
|
local signalling |
Positive contact indication
|
|
neutral protection setting |
Without protection
|
|
earth-leakage protection |
Without
|
|
height |
130Â mm
|
|
width |
100Â mm
|
|
depth |
60Â mm
|
₦93,000.00
Compare-
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 1P 50A C Miniature Circuit breaker A9F44150
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 1P 50A C Miniature Circuit breaker A9F44150
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 1Pnumber of protected poles 1[In] rated current 50Â Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 15Â kA Icu at 12…48 V DC conforming to EN/IEC 60947-2
6Â kA Icu at 72 V DC conforming to EN/IEC 60947-2
6000Â A Icn at 240 V AC 50/60 Hz conforming to EN/IEC 60898-1
36Â kA Icu at 10…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
20Â kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
10Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 240 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 27Â kA 75Â % conforming to EN/IEC 60947-2 – 10…60 V AC 50/60 Hz
15Â kA 75Â % conforming to EN/IEC 60947-2 – 100…133 V AC 50/60 Hz
7.5Â kA 75Â % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
6000Â A 100Â % conforming to EN/IEC 60898-1 – 240 V AC 50/60 Hz
15Â kA 100Â % conforming to EN/IEC 60947-2 – 12…48 V DC
6 kA 100 % conforming to EN/IEC 60947-2 – 72 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 2height 85 mmwidth 18 mmdepth 78.5 mmnet weight 0.125 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 3.5 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
Electro, SOLAR POWERED
Solar Homaya Hybrid Home System 850 – Schneider Electric
Features
Recommended Solar Panel Wattage – 800 Wp, 12V with OCV of 17V to 21V
AC Input – 230V AC, 50 Hz
AC output – 850VA – 230V AC, 50 Hz
DC output – 12V, 20A
Recommended Battery Size – 12V, 100Ah to 200Ah
Recommended Battery type – Supports Tubular, Flat plate, GEL/VRLA battery
Product dimensions in mm (LxWxH)Â – 375 x 315 x 135
Safety and reliability – Protected against short-circuit, High temperature and Internal fault protectionBenefits
- Affordable solar hybrid solutions –Â Unleash the power of the sun and grid to energize the home
- AC & DC output –Â 230V AC – 50Hz and 12V DC output
- Achieve more savings –Â Optimizes the use of solar power and saves grid electricity bill
SKU: n/a -
-
ELECTRICAL INDUSTRIAL, Electro, RECLINE CABLES
Cometstar Nigeria Cable NAY 4 X 70.0MM Per Meter
The construction and material are determined by three main factors:
• Working voltage, determining the thickness of the insulation;
• Current-carrying capacity, determining the cross-sectional size of the conductor(s);
• Environmental conditions such as temperature, water, chemical or sunlight exposure, and mechanical impact, determining the form and composition of the outer cable jacketSKU: Cometstar Nigeria Cable NAY 4 X 70.0MM-1 -
Electro, SOCKETS, SOCKETS & SWITCHES
BG 870 mfp Nexus Moulded White 45 Amp Double Pole Cooker Control Unit With 13 Amp Socket And LED 6 x 6 BG870MFP
Electro, SOCKETS, SOCKETS & SWITCHESBG 870 mfp Nexus Moulded White 45 Amp Double Pole Cooker Control Unit With 13 Amp Socket And LED 6 x 6 BG870MFP
BG 870 Nexus Moulded White 45 Amp Double Pole Cooker Control Unit with 13 Amp Socket and LED is a modern design that will blend with any décor. Suitable for use in domestic or commercial installations.
Features
- Stylish modern profile finished in White
- Covers to conceal fixing screws for a clean finish
- Colour Coded Terminals for easy installation
- Supplied with Space Adaptor Plate
- 2 Earth Terminals
SKU: cookerwhite -
CIRCUIT BREAKERS
IC60N – miniature circuit breaker – 3P – 63A – C curve
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 3Pnumber of protected poles 3[In] rated current 63Â Anetwork type DC
ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 6000Â A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
36Â kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
10Â kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
20Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
6Â kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
36Â kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
10Â kA Icu at <= 180 V DC conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards EN 60898-1
EN 60947-2
IEC 60898-1
IEC 60947-2Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 15Â kA 75Â % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
7.5Â kA 75Â % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz
4.5Â kA 75Â % conforming to EN 60947-2 – 440 V AC 50/60 Hz
15Â kA 75Â % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5Â kA 75Â % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz
4.5Â kA 75Â % conforming to IEC 60947-2 – 440 V AC 50/60 Hz
27Â kA 75Â % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz
27Â kA 75Â % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz
6000Â A 100Â % conforming to EN 60898-1 – 400 V AC 50/60 Hz
6000Â A 100Â % conforming to IEC 60898-1 – 400 V AC 50/60 Hz
10Â kA 100Â % conforming to IEC 60947-2 – 125…180 V DC
10Â kA 100Â % conforming to EN 60947-2 – 125…180 V DC[Ui] rated insulation voltage 500Â V AC 50/60 Hz conforming to EN 60947-2
500Â V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6Â kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 6height 85 mmwidth 54 mmdepth 78.5 mmnet weight 0.375 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 3.5 N.m top or bottomearth-leakage protection Separate blockSKU: n/a
There are no reviews yet.