Electro, Low Voltage Products and Systems, SCHNEIDER SECTIONS
EZC250N4200 Circuit breaker Easypact EZC250N – TMD – 200 A – 4 poles 3d
range of product |
EasyPact
|
|
---|---|---|
product or component type |
Circuit breaker
|
|
device short name |
Easypact EZC250N
|
|
circuit breaker name |
Easypact EZC250N
|
|
device application |
Distribution
|
|
poles description |
4P
|
|
protected poles description |
3t
|
|
network type |
DC
AC |
|
network frequency |
50/60 Hz
|
|
[In] rated current |
250 A at 40 °C
|
|
[Ui] rated insulation voltage |
690Â V AC 50/60 Hz conforming to IEC 60947-2
|
|
[Uimp] rated impulse withstand voltage |
6Â kV conforming to IEC 60947-2
|
|
[Ue] rated operational voltage |
550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2 |
|
breaking capacity code |
N
|
|
breaking capacity |
20Â kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
50Â kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2 20Â kA Icu at 125 V DC 1P conforming to IEC 60947-2 20Â kA Icu at 250 V DC 2P conforming to IEC 60947-2 8Â kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 25Â kA Icu at 380…415 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Ics] rated service breaking capacity |
10Â kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
25Â kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2 10Â kA at 125 V DC conforming to IEC 60947-2 10Â kA at 250 V DC conforming to IEC 60947-2 4Â kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 12.5Â kA at 380…415 V AC 50/60 Hz conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to IEC 60947-2
|
|
utilisation category |
Category A
|
|
trip unit name |
TM-D
|
|
trip unit technology |
Thermal-magnetic
|
|
trip unit rating |
200 A at 50 °C
|
|
protection type |
Short-circuit protection
Overload protection |
|
pollution degree |
3 conforming to IEC 60947
|
control type |
Toggle
|
|
---|---|---|
mounting mode |
Fixed
|
|
mounting support |
Backplate
|
|
upside connection |
Front
|
|
downside connection |
Front
|
|
mechanical durability |
10000Â cycles
|
|
electrical durability |
Category A: 5000Â cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
|
|
connection pitch |
35Â mm
|
|
local signalling |
Positive contact indication
|
|
neutral protection setting |
Without protection
|
|
earth-leakage protection |
Without
|
|
height |
165Â mm
|
|
width |
140Â mm
|
|
depth |
60Â mm
|
₦260,000.00
Compare-
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Easy9 miniature circuit breaker- 2P – 32 A – C curve – 6000 A – 230 V EZ9F56232
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSEasy9 miniature circuit breaker- 2P – 32 A – C curve – 6000 A – 230 V EZ9F56232
Main range Easy9device application Distributionproduct or component type Miniature circuit-breakerdevice short name Easy9 MCBPoles 2Pnumber of protected poles 2[In] rated current 32Â Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000Â A Icn at 220 V AC 50/60 Hz conforming to IEC 60898-1
6000Â A Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1suitability for isolation Yes conforming to IEC 60898-1Complementary network frequency 50/60 Hz[Ue] rated operational voltage 220 V AC 50/60 Hz
400 V AC 50/60 Hzmagnetic tripping limit 5…10 x In[Ics] rated service breaking capacity 6 kA 100 % x Icn at 230 V AC 50/60 Hz conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to IEC 60898-1[Uimp] rated impulse withstand voltage 4 kV conforming to IEC 60898-1contact position indicator Yescontrol type Togglelocal signalling Withoutmounting mode Clip-onmounting support DIN rail9 mm pitches 4height 81 mmwidth 36 mmdepth 66.5 mmcolour Grey (RAL 7035)mechanical durability 10000 cycleselectrical durability 4000 cyclesconnections – terminals Tunnel type terminal (top or bottom) 1…25 mm² flexible
Tunnel type terminal (top or bottom) 1…35 mm² rigidtightening torque 3.5 N.m top or bottomearth-leakage protection WithoutSKU: n/a -
ELECTRICAL INDUSTRIAL, TRANSFORMER
ABB 33kV, 2500Amps SF6 Gas Circuit Breaker Outdoor Type OHB
Base Cabinet
The base cabinet is made of painted mild steel. The cabinet houses a spring operated mechanism which is mechanically linked to all three poles. The cabinet also includes the followings:- Anti-condensation heater
- Circuit breaker status indicator
- Mechanical operation counter
- Breaker control switches
- Anti-pumping relay
- AC / DC fuses, MCBs
- Auxiliary wiring
- Terminal blocks
- Gas pressure monitoring relays
Operating mechanism
For high operational reliability and minimal maintenance, a simple and robust spring operated mechanism is used.Features
- O-C-O operation without recharging
- Closing spring is charged by motor in less than 15 secs.
- Mechanical / electrical anti-pumping
- Provision for manual charging
- Suitable for rapid auto-reclosing
- Manual closing and tripping arrangement
- Mechanical ON – OFF and SPRING CHARGED indication
- Auxiliary switch: 13 NO + 13 NC
- Additional tripping solenoid(optional)
SKU: n/a -
LIGHT SWITCHES & ELECTRICAL SOCKETS
20 A 3 gang 1 way switch with ON indicator E8433_1_SZ
Main range ZENceloproduct or component type Switchdevice application Controlload type Fluorescent lamp
Resistive
Inductive
Incandescent lampcolour tint Silver bronzecover frame colour tint Silver bronzeComplementary device mounting Surface
Flushswitch function 1-wayrated current 20 A at 250 V AC 50 Hzlocal signalling Mechanical indicator, neon (amber)number of gangs 3 gangsmaterial Polycarbonate + GF 20 %: grid plate
Polycarbonate: base
Polycarbonate: cover
Polycarbonate: surroundSKU: n/a -
Electro, SOCKETS, SOCKETS & SWITCHES, SURGE PROTECTOR
BG SOCKET 13AMP 2-GANG SWITCHED SOCKET RCD – LUCECO
Electro, SOCKETS, SOCKETS & SWITCHES, SURGE PROTECTORBG SOCKET 13AMP 2-GANG SWITCHED SOCKET RCD – LUCECO
- Maximum load 3120 watts 240V AC
- 30 mA trip speed 40 ms
- Latching type
- Terminal capacity 3 x 2.5mm², 2 x 4.0mm² & 1 x 6.0mm²
- Manufactured to BS 7288:1990
- 10mm Spacer provided for shallow boxes
- Minimum mounting box depth 35mm
SKU: RCD002 -
LIGHT SWITCHES & ELECTRICAL SOCKETS
ZENcelo-16AX 2 Gang 2 Way Full-Flat Switch with Ondicat w/Blister-Silver Bronze E8432_2_SZ
LIGHT SWITCHES & ELECTRICAL SOCKETSZENcelo-16AX 2 Gang 2 Way Full-Flat Switch with Ondicat w/Blister-Silver Bronze E8432_2_SZ
Main range ZENceloproduct or component type Switchload type Incandescent lamp
Resistive
Fluorescent lamp
Inductivecolour tint Silver bronzecover frame colour tint Silver bronzeComplementary device mounting Flush
Surfaceswitch function 2-wayrated current 20 A at 250 V AC 50/60 Hzlocal signalling Mechanical indicator (amber)number of gangs 2 gangsmaterial Polycarbonate + GF 20 %: grid plate
Polycarbonate: base
Polycarbonate: cover
Polycarbonate: surroundconnections – terminals Brass rod terminalswidth 87Â mmheight 87Â mmdepth 31Â mmSKU: n/a -
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
IC60H – miniature circuit breaker – 1P – 4A – C curve A9F84104
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSIC60H – miniature circuit breaker – 1P – 4A – C curve A9F84104
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Hpoles description 1Pnumber of protected poles 1[In] rated current 4Â Anetwork type DC
ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000Â A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
15Â kA Icu at 60…72 V DC conforming to EN/IEC 60947-2
20Â kA Icu at 12…60 V DC conforming to EN/IEC 60947-2
70Â kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
70Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
70Â kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards IEC 60898-1
EN 60947-2
EN 60898-1
IEC 60947-2Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 70Â kA 100Â % conforming to EN 60947-2 – 12…60 V AC 50/60 Hz
70Â kA 100Â % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
70Â kA 100Â % conforming to IEC 60947-2 – 12…60 V AC 50/60 Hz
70Â kA 100Â % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7500Â A 75Â % conforming to EN 60898-1 – 230 V AC 50/60 Hz
7500Â A 75Â % conforming to IEC 60898-1 – 230 V AC 50/60 Hz
70Â kA 100Â % conforming to IEC 60947-2 – 100…133 V AC 50/60 Hz
70Â kA 100Â % conforming to EN 60947-2 – 100…133 V AC 50/60 Hz
15Â kA 100Â % conforming to EN 60947-2 – 72 V DC
15Â kA 100Â % conforming to IEC 60947-2 – 72 V DC
20Â kA 100Â % conforming to EN 60947-2 – 12…60 V DC
20Â kA 100Â % conforming to IEC 60947-2 – 12…60 V DClimitation class 3 conforming to EN 60898-1
3 conforming to IEC 60898-1[Ui] rated insulation voltage 500Â V AC 50/60 Hz conforming to EN 60947-2
500Â V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6Â kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 2height 85 mmwidth 18 mmdepth 78.5 mmnet weight 0.215 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection WithoutSKU: n/a
There are no reviews yet.