IC60H – miniature circuit breaker – 1P – 32A – C curve A9F84132
device application |
Distribution
|
|
---|---|---|
range |
Acti 9
|
|
product name |
Acti 9 iC60
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
IC60H
|
|
poles description |
1P
|
|
number of protected poles |
1
|
|
[In] rated current |
32Â A
|
|
network type |
DC
AC |
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
10000Â A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
15Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 42Â kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2 30Â kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2 15Â kA Icu at 60…72 V DC conforming to EN/IEC 60947-2 20Â kA Icu at 12…60 V DC conforming to EN/IEC 60947-2 |
|
utilisation category |
Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to EN 60898-1
Yes conforming to EN 60947-2 Yes conforming to IEC 60898-1 Yes conforming to IEC 60947-2 |
|
standards |
IEC 60947-2
IEC 60898-1 EN 60898-1 EN 60947-2 |
network frequency |
50/60 Hz
|
|
---|---|---|
magnetic tripping limit |
8 x In +/- 20 %
|
|
[Ics] rated service breaking capacity |
21Â kA 50Â % conforming to EN 60947-2 – 12…60 V AC 50/60 Hz
7.5Â kA 50Â % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz 21Â kA 50Â % conforming to IEC 60947-2 – 12…60 V AC 50/60 Hz 7.5Â kA 50Â % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz 7500Â A 75Â % conforming to EN 60898-1 – 230 V AC 50/60 Hz 7500Â A 75Â % conforming to IEC 60898-1 – 230 V AC 50/60 Hz 15Â kA 50Â % conforming to IEC 60947-2 – 100…133 V AC 50/60 Hz 15Â kA 50Â % conforming to EN 60947-2 – 100…133 V AC 50/60 Hz 15Â kA 100Â % conforming to EN 60947-2 – 72 V DC 15Â kA 100Â % conforming to IEC 60947-2 – 72 V DC 20Â kA 100Â % conforming to EN 60947-2 – 12…60 V DC 20Â kA 100Â % conforming to IEC 60947-2 – 12…60 V DC |
|
limitation class |
3 conforming to EN 60898-1
3 conforming to IEC 60898-1 |
|
[Ui] rated insulation voltage |
500Â V AC 50/60 Hz conforming to EN 60947-2
500Â V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Uimp] rated impulse withstand voltage |
6Â kV conforming to EN 60947-2
6Â kV conforming to IEC 60947-2 |
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Trip indicator
|
|
mounting mode |
Fixed
|
|
mounting support |
DIN rail
|
|
comb busbar and distribution block compatibility |
Top or bottom: YES
|
|
9 mm pitches |
2
|
|
height |
85Â mm
|
|
width |
18Â mm
|
|
depth |
78.5Â mm
|
|
net weight |
0.215Â kg
|
|
colour |
White
|
|
mechanical durability |
20000Â cycles
|
|
electrical durability |
10000Â cycles
|
|
connections – terminals |
Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexible |
|
wire stripping length |
14Â mm for top or bottom connection
|
|
tightening torque |
3.5Â N.m top or bottom
|
|
earth-leakage protection |
Without
|
₦3,999.00
Compare-
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Miniature circuit-breaker, Acti9 iC60H, 2P, 10 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84210
Schneider Circuit Breakers, SCHNEIDER SECTIONSMiniature circuit-breaker, Acti9 iC60H, 2P, 10 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84210
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Hpoles description 2Pnumber of protected poles 2[In] rated current 10Â Anetwork type AC
DCtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000Â A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
42Â kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
10Â kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
15Â kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
30Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
15Â kA Icu at <= 125 V DC conforming to EN/IEC 60947-2
42Â kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards EN 60898-1
IEC 60947-2
IEC 60898-1
EN 60947-2Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 15Â kA 50Â % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
7.5Â kA 50Â % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz
5Â kA 50Â % conforming to EN 60947-2 – 440 V AC 50/60 Hz
15Â kA 50Â % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5Â kA 50Â % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz
5Â kA 50Â % conforming to IEC 60947-2 – 440 V AC 50/60 Hz
7500Â A 75Â % conforming to EN 60898-1 – 400 V AC 50/60 Hz
7500Â A 75Â % conforming to IEC 60898-1 – 400 V AC 50/60 Hz
21Â kA 50Â % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz
21Â kA 50Â % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz
15Â kA 100Â % conforming to IEC 60947-2 – 72…125 V DC
15Â kA 100Â % conforming to EN 60947-2 – 72…125 V DClimitation class 3 conforming to EN 60898-1
3 conforming to IEC 60898-1[Ui] rated insulation voltage 500Â V AC 50/60 Hz conforming to EN 60947-2
500Â V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6Â kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 4height 85 mmwidth 36 mmdepth 78.5 mmnet weight 0.25 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
Electro, INDOOR LIGHTS, LED LIGHTS, LIGHT BULBS, LIGHTING
WINWIN POP Reccessed LED Panel light 18watt
Electro, INDOOR LIGHTS, LED LIGHTS, LIGHT BULBS, LIGHTINGWINWIN POP Reccessed LED Panel light 18watt
Rated Power(W): 3/6/9/12/15/18/24W
Size: Φ85*22mm/Φ120*22mm/Φ145*22mm/Φ174*22mm/Φ200*22mm/Φ225*40mm/Φ300*40mm
Cut out Size: Φ65mm/Φ100mm/Φ125mm/Φ155mm/Φ180mm/Φ200mm/Φ280mm
Input Voltage(V): AC85-265V
LED Type: SMD
Lumen(LM): 65-80LM/W
Frequency Range(Hz): 50-60Hz
Beam angle(Degree): 180°
Color Temperature(K): 2700K-6500K
CRI(Ra): >70
Power factor(PF): >0.55
LED Chip Brand: San’an
Material: Aluminum
Working Temperature: -20℃~+45℃SKU: n/a -
ELECTRICAL FITTINGS, Electro, HOME&OFFICE LIGHTING, INDOOR LIGHTS, INTERIOR LIGHTING
Vellmax 50W LED Modular Fitting 600 x 600
ELECTRICAL FITTINGS, Electro, HOME&OFFICE LIGHTING, INDOOR LIGHTS, INTERIOR LIGHTINGVellmax 50W LED Modular Fitting 600 x 600
- Panel Light
- Modular fitting
LED Panels are the most effective way to light large open plan areas. They are used in hotels, airports, hospitals, office buildings, supermarkets etc.Benefits for LED panel lights; Vellmax LED lighting panels are the energy-efficient alternative to fluorescent grill lights. Choosing high-performance LED panel lighting means many times greater luminosity, with far less energy wasted on heat.
SKU: n/a -
Low Voltage Products and Systems, SCHNEIDER SECTIONS
EZC100N4030 – Circuit breaker Easypact EZC100N – TMD – 30 A – 4 poles 3d
Low Voltage Products and Systems, SCHNEIDER SECTIONSEZC100N4030 – Circuit breaker Easypact EZC100N – TMD – 30 A – 4 poles 3d
Main range of product EasyPactproduct or component type Circuit breakerdevice short name Easypact EZC100Ncircuit breaker name Easypact EZC100Ndevice application Distributionpoles description 4Pprotected poles description 3tnetwork type AC
DCnetwork frequency 50/60 Hz[In] rated current 100 A at 40 °C[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2[Ue] rated operational voltage 550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2breaking capacity code Nbreaking capacity 10Â kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
25Â kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
25Â kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
5Â kA Icu at 125 V DC 1P conforming to IEC 60947-2
5Â kA Icu at 250 V DC 2P conforming to IEC 60947-2
5Â kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
15Â kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2
18Â kA Icu at 380…400 V AC 50/60 Hz conforming to IEC 60947-2[Ics] rated service breaking capacity 5Â kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
2.5Â kA at 125 V DC conforming to IEC 60947-2
2.5Â kA at 250 V DC conforming to IEC 60947-2
2.5Â kA at 550 V AC 50/60 Hz conforming to IEC 60947-2
12.5Â kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
12.5Â kA at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
9Â kA at 380…400 V AC 50/60 Hz conforming to IEC 60947-2
7.5 kA at 415 V AC 50/60 Hz conforming to IEC 60947-2suitability for isolation Yes conforming to IEC 60947-2utilisation category Category Atrip unit name TM-Dtrip unit technology Thermal-magnetictrip unit rating 30 A at 50 °Cprotection type Overload protection
Short-circuit protectionpollution degree 3 conforming to IEC 60947Complementary control type Togglemounting mode Fixedmounting support Backplateupside connection Frontdownside connection Frontmechanical durability 8500Â cycleselectrical durability Category A: 1500Â cycles 415 V AC 50/60 Hz conforming to IEC 60947-2connection pitch 25Â mmlocal signalling Positive contact indicationneutral protection setting Without protectionearth-leakage protection Withoutheight 130Â mmwidth 100Â mmdepth 60Â mmSKU: n/a
There are no reviews yet.