IC60H – miniature circuit breaker – 1P – 4A – C curve A9F84104
device application |
Distribution
|
|
---|---|---|
range |
Acti 9
|
|
product name |
Acti 9 iC60
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
IC60H
|
|
poles description |
1P
|
|
number of protected poles |
1
|
|
[In] rated current |
4Â A
|
|
network type |
DC
AC |
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
10000Â A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
15Â kA Icu at 60…72 V DC conforming to EN/IEC 60947-2 20Â kA Icu at 12…60 V DC conforming to EN/IEC 60947-2 70Â kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2 70Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 70Â kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
|
utilisation category |
Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to EN 60898-1
Yes conforming to EN 60947-2 Yes conforming to IEC 60898-1 Yes conforming to IEC 60947-2 |
|
standards |
IEC 60898-1
EN 60947-2 EN 60898-1 IEC 60947-2 |
network frequency |
50/60 Hz
|
|
---|---|---|
magnetic tripping limit |
8 x In +/- 20 %
|
|
[Ics] rated service breaking capacity |
70Â kA 100Â % conforming to EN 60947-2 – 12…60 V AC 50/60 Hz
70Â kA 100Â % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz 70Â kA 100Â % conforming to IEC 60947-2 – 12…60 V AC 50/60 Hz 70Â kA 100Â % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz 7500Â A 75Â % conforming to EN 60898-1 – 230 V AC 50/60 Hz 7500Â A 75Â % conforming to IEC 60898-1 – 230 V AC 50/60 Hz 70Â kA 100Â % conforming to IEC 60947-2 – 100…133 V AC 50/60 Hz 70Â kA 100Â % conforming to EN 60947-2 – 100…133 V AC 50/60 Hz 15Â kA 100Â % conforming to EN 60947-2 – 72 V DC 15Â kA 100Â % conforming to IEC 60947-2 – 72 V DC 20Â kA 100Â % conforming to EN 60947-2 – 12…60 V DC 20Â kA 100Â % conforming to IEC 60947-2 – 12…60 V DC |
|
limitation class |
3 conforming to EN 60898-1
3 conforming to IEC 60898-1 |
|
[Ui] rated insulation voltage |
500Â V AC 50/60 Hz conforming to EN 60947-2
500Â V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Uimp] rated impulse withstand voltage |
6Â kV conforming to EN 60947-2
6Â kV conforming to IEC 60947-2 |
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Trip indicator
|
|
mounting mode |
Fixed
|
|
mounting support |
DIN rail
|
|
comb busbar and distribution block compatibility |
Top or bottom: YES
|
|
9 mm pitches |
2
|
|
height |
85Â mm
|
|
width |
18Â mm
|
|
depth |
78.5Â mm
|
|
net weight |
0.215Â kg
|
|
colour |
White
|
|
mechanical durability |
20000Â cycles
|
|
electrical durability |
10000Â cycles
|
|
connections – terminals |
Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexible |
|
wire stripping length |
14Â mm for top or bottom connection
|
|
tightening torque |
2Â N.m top or bottom
|
|
earth-leakage protection |
Without
|
₦10,800.00
Compare-
-
CABLE AND CABLE MANAGEMENT, Electro, SINGLE CORE WIRE
Doncaster Cables 10mm Single Core – Black
Product Description
Manufactured to BS 6004:2012 Table 3
Annealed Stranded Copper Conductor / PVC Insulated / PVC Sheathed. 300/500V
Designed for use in light industrial and domestic wiring. These cables are particularly suited for installation as meter tails and are intended for fixed installation in dry or damp premises.
These cables can be installed in conduit, in cable trunking and in cable ducting. Or where there is deemed little risk of mechanical damage these cables can be clipped direct, on cable tray, embedded or in free air. These cables are not intended to be laid underground.
Product Details
 Harmonisation Code Nominal Cross Sectional Area of Conductor (mm2) Nominal Stranding of Conductor (mm) Nominal Radial Thickness of insulation (mm) Nominal Radial Thickness of sheath (mm) Overall Diameter Lower Limit (mm) Overall Diameter Upper Limit (mm) Approximate Weight(kg/km) National Type 1.0 1 / 1.13 0.6 0.8 3.8 4.5 26 National Type 1.5 1 / 1.38 0.7 0.8 4.2 4.9 35 National Type 2.5 1 / 1.78 0.8 0.8 4.8 5.8 55 National Type 4.0 7 / 0.85 0.8 0.9 5.4 6.8 75 National Type 6.0 7 / 1.04 0.8 0.9 6.0 7.4 95 National Type 10.0 7 / 1.35 1.0 0.9 7.2 8.8 155 National Type 16.0 7 / 1.70 1.0 1.0 8.4 10.5 225 National Type 25.0 7 / 2.14 1.2 1.1 10.0 12.5 340 National Type 35.0 7 / 2.52 1.2 1.1 11.0 13.5 445 SKU: n/a -
DISTRIBUTION BOARDS, DISTRIBUTION BOARDS, Electro
ABB 12 Way 100A TPN Distribution Board
Available in kit form for over-the counter-supply, the latest generation sub-distribution solution from ABB has been tailored to meet the needs of all segments of the building industry.
Main construction features:
• Structure in epoxy coated metal sheets, 1mm thickness
• Wall installation for indoor environments
• Degree of protection – IP43 with door / Mechanical resistance IK 07
• Busbar rating: 250A
• Number of ways: 4, 8, 12, 16, 20, 24
• Compliance with IEC BS EN 61439 1-2
• Simple wiring of all cabinets, both horizontally and vertically
• Easy internal accessibility for wiring operations and maintenance
• Pre-packaged kits for specific applications (e.g. surge protection, metering)SKU: n/a -
ELECTRICAL FITTINGS, Electro, HOME&OFFICE LIGHTING, INDOOR LIGHTS, LED LIGHTS, LIGHTING, OUTDOOR FITTINGS, OUTDOOR LIGHTS
PHILIPS WATERPROOF BATTEN WT035CC LED30/CW 30W PSU GM CFW L1200(Cool White, 4FT) Essential Smartbright waterproof
ELECTRICAL FITTINGS, Electro, HOME&OFFICE LIGHTING, INDOOR LIGHTS, LED LIGHTS, LIGHTING, OUTDOOR FITTINGS, OUTDOOR LIGHTSPHILIPS WATERPROOF BATTEN WT035CC LED30/CW 30W PSU GM CFW L1200(Cool White, 4FT) Essential Smartbright waterproof
Light Technical
- Luminous Flux                       –  3,000 lm
- Correlated Color Temperature (Nom)Â Â Â –Â Â 6500 K
- Luminous Efficacy (rated) (Nom)Â Â Â Â Â Â Â –Â Â 90 lm/W
- Color rendering index (CRI)Â Â Â Â Â Â Â Â Â Â Â Â –Â Â >70
- Beam angle of light source              –  120 degree(s)
- Light source color                     –  865 cool daylight
- Optic type                            –  Beam angle 120°
Mechanical and Housing
- Housing Material             –  Polycarbonate
- Reflector material              –  Steel
- Optic material                 –  Polycarbonate
- Optical cover material           – Polycarbonate
- Fixation material               –
- Housing Color                 –  White
- Optical cover finish             – Opal
- Overall length                  – 1,198 mm
- Overall width                  –  35.5 mm
- Overall height                  –  44.5 mm
- Dimensions (Height x Width x Depth)Â Â –Â 45 x 36 x 1198 mm
- Optical cover type               –  Polycarbonate bowl/cover
- Luminaire light beam spread       – 120°
SKU: n/a -
Electro, SOCKETS, SOCKETS & SWITCHES
FBNRJ111- BG TELEPHONE SOCKET
BG Electrical are confident in the quality of our workmanship and materials, the guarantee stated applies from the date of delivery.
Screw terminal connection
Easy to install, supplied with fixing screws and installation instructions
RJ11 socket
Screwless front plate clips on and off easily and has a sleek, flat profile
Moisture control gasket, prevents tarnishing from new plaster
Shuttered socket
Supplied as a kit of Euro module components
SKU: n/a -
Electro, Low Voltage Products and Systems, SCHNEIDER SECTIONS
EZC250N4250 circuit breaker, EasyPact EZC250N, TMD, 250A, 4 poles 3d
Electro, Low Voltage Products and Systems, SCHNEIDER SECTIONSEZC250N4250 circuit breaker, EasyPact EZC250N, TMD, 250A, 4 poles 3d
Main
Range of product EasyPact
Product or component type Circuit breaker
Device short name Easypact EZC250N
Circuit breaker name Easypact EZC250N
Device application Distribution
Poles description 4P
Protected poles description 3t
Network type AC
DC
Network frequency 50/60 Hz
[In] rated current 250 A at 40 °C
[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2
[Ue] rated operational voltage 550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2
Breaking capacity code N
Breaking capacity 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
20 kA Icu at 125 V DC 1P conforming to IEC 60947-2
20 kA Icu at 250 V DC 2P conforming to IEC 60947-2
8 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 380…415 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity 10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
25 kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
10 kA at 125 V DC conforming to IEC 60947-2
10 kA at 250 V DC conforming to IEC 60947-2
4 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 380…415 V AC 50/60 Hz conforming to IEC 60947-2
Suitability for isolation Yes conforming to IEC 60947-2
Utilisation category Category ASKU: n/a